Instructions for the installer
3.16 - CONDENSATE DRAIN
Avoid the condensate stagnation inside the combustion products
evacuation system, (for this reason the evacuation duct must
have an inclination toward the drain of at least 30 mm/m (3/8 in. /
ft) except the liquid column, inside the condensate siphon, which
needs to be filled with water after installation: its minimum height,
when all the fans are in operation, must be at least 25 mm (1 in.).
In order to avoid ice formation while the boiler is operating,
which can cause the stop of the boiler, the whole condensate
evacuation system has to be well insulated. It is forbidden to
evacuate the condensate through a gutter: risk of ice forming
and corrosion.
The condensate, before being evacuated to the sewer, has to
The outlet of the condensate drain pipe will be on the same
side of the smoke chamber, passing below the smoke chamber.
Before commissioning the boiler fill the con-
densate siphon with water, from the dedicated
filling-up plug.
* Min. height of the condensate column, with all fans
operating at max. speed, requested by the EN stan-
dards.
** Min. height of the condensate column, with all fans
operating at max. speed. In the case it is not possible
to create a 100 mm basement, install the boiler on the
floor and foresee a min. 100 mm well to lodge the siphon.
be neutralized, neutralisation which can be obtained by mixing
the drain water coming from washing maschines, dish washing
maschines, etc., which normally have a basic pH.
The connection to the sewer will be through a visible drain. Given
the high acidity degree (pH 3 to 5) only plastic material can be
used for the condensate evacuation pipes. Moreover it must be
dimensioned and constructed so as to allow the correct out-flow
of drains, preventing any bottleneck and any leakage.
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Unical MODULEX EXT 100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Unical MODULEX EXT 100 in the language / languages: English as an attachment in your email.

The manual is 8,87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Unical MODULEX EXT 100

Unical MODULEX EXT 100 Installation Guide - Dutch - 57 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info