Service info
2.8 FAILURE CODES
In case of failure the burner is automatically deactivated and the symbol on the display
is shown. By pushing the reset button the failure blinking code is shown on the display.
Each fault is characterised by a priority level : if different failures are detected at the same time,
the code with the highest priority level is shown.
The following failure codes are recognised:
2.10.1 Lock-out (priority 1)
Description:
Modureg coil interrupted
Possible solution:
verify the wiring, replace the modureg
2.10.2 Lock-out (priority 2)
Description:
Fault at the fan pressure switch
Possible solution:
Verify the fan pressure switch (TFS version) and the electric connections or
replace the main PCB.
2.10.3 High temperature (priority 3)
Description:
Overheating of the boiler
Possible solution:
verify the correct operation of the pump and, eventually, descale the heat exchanger.
2.10.4 Difficult smoke evacuation (priority 4)
Description:
Difficult smoke evacuation
Possible solution:
TN boilers: verify the chimney draught, or the smoke thermostat.
TFS boilers: verify the fan and its own pressure switch operations.
2.10.5 Lack of water (priority 5)
Description:
Insufficient water pressure: intervention of minimum water pressure switch.
Possible solution:
Set the water pressure by the filling valve and look for possible leakages. If the code appears
again, call the service technician.
2.10.6 FROST (priority 6)
Description:
Freezing of the heat exchanger is detected if CH sensor < 2°C; ignition in inhibited until CH
sensor reaches 5°C.
Possible solution:
Cut off the voltage, close the gas feeding, call the service technician.
2.10.7 High Limit thermostat (priority 7)
Description:
High limit thermostat intervention
Possible solution:
Verify the water circulation into the heat exchanger; verify that the high limit thermostat and its
own connections are not interrupted
°C
°C
°C
°C
°C
°C
°C
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Unical EVE 05 RTFS 24 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Unical EVE 05 RTFS 24 in the language / languages: English as an attachment in your email.

The manual is 1,36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info