652335
20
Zoom out
Zoom in
Previous page
1/36
Next page
20
Installation info
fig. 15
fig. 16
Ø 80/125
Ø 80/125
Ø 60/100
Ø 80/125
Rubber foam gasket
Up to 2 m
Up to 1 m
Up to 2,5 m
Rubber foam
gasket
Diaphragm Ø 42
Diaphragm
Ø 42
2.2.9 - DISCHARGE OF FLUE
GAS INTO
COAXIAL DUCTS
Ø 100/60 mm
Type C12 Ø 100/60 mm
The minimum length of horizontal coaxial
ducts is 0.5 metres. The maximum allowable
length of horizontal co-axial ducts is 3 me-
tres; for each additional bend the maximum
allowable length must be reduced by 1 metre.
Moreover, the duct must have a downward dip
of 1% towards the outlet point to prevent rain
water from getting into the duct.
Type C32 100/60 mm
The minimum length of vertical coaxial ducts
is 0.5 metres. The maximum allowable length
of vertical coaxial ducts is 4 metres exclu-
ding the stack (Ø 80/125); for each additional
bend the maximum allowable length must be
reduced by 1 metre.
The diaphragm Ø 42 supplied with the boi-
ler must be inserted in the flue gas exhaust
pipe as shown in figure 15, for installa-
tions with horizontal coaxial pipe up to 1
m and with vertical coaxial pipe up to 2
m.
VERTICAL FLUE DUCT WITH
COAXIAL DUCT Ø 80/125
Tipo C32 Ø 80 / 125
The minimum length of vertical coaxial ducts
is 1,2 metres. The maximum allowable length
of vertical coaxial ducts is 6 metres exclu-
ding the stack (Ø 80/125); for each additional
bend the maximum allowable length must be
reduced by 1 metre.
The diaphragm Ø 42 supplied with the boi-
ler must be inserted in the flue gas exhaust
pipe, as shown in figure 16, for installa-
tions with a coaxial pipe up to 2,5 m.
Fitting of the diaphragm Ø 42
Closing cover
with gasket in
neoprene
Closing cover
with gasket in
neoprene
Closing cover
with gasket in
neoprene
Closing cover
with gasket in
neoprene
WARNING: For the smoke ou-
tlet configuration (see fig. 15-
16) it is necessary to close the
holes of air entry ''1-2'' with
the provided for closing co-
vers and the gaskets delive-
red with the boiler.
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Unical EVE 05 CTN 24 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Unical EVE 05 CTN 24 in the language / languages: English as an attachment in your email.

The manual is 1,36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info