652333
21
Zoom out
Zoom in
Previous page
1/36
Next page
21
Installation info
fig. 17
152
100
95
Up to
ΔΔ
ΔΔ
Δ P = 20 Pa
Rubber foam
gasket
Diaphragm
Ø 42
fig. 18
It is not allowed to position the 2 termi-
nals in opposite walls, see configuration
type C52.
DIMENSIONS FOR CONNECTION TO COAXIAL FLUE GAS DUCTS
2.2.10 - FLUE GAS DISCHARGE
AND AIR SUCTION WITH
DUAL DUCTS WITH 80 mm
DIAMETER
NB: The maximum allowable pressure loss,
irrespective of the type of installation, must
not exceed 50 Pa .
For all installations with a pressure loss of the
ducts not exceeding 20 Pa, the diaphragm
supplied with the boiler must be installed insi-
de the flue gas outlet pipe (see fig. 18).
WARNING! In case the flue duct
has to cross walls or floors, or if
it is easily reachable, it is ne-
cessary to foresee a convenient
insulation of such a duct. The
flue duct, during the operation
of the boiler can reach tempera-
tures higher than 120°C.
IMPORTANT
Flue gas pressure switch operation
The boiler is fitted with a device control-
ling flue gas pressure.
This device shuts down the boiler in the
event of a malfunction.
This situation is indicated by the failure led
lighting on the display; by pressing the
reset push-button the failure code “AF” is di-
splayed and the boiler will repeat it's ignition
sequence. If the reset button is not pressed
the boiler will in any case repeat it's ignition
sequence after 10 minutes.
WARNING: Per For the smo-
ke outlet configuration (see
fig. 18) it is necessary to clo-
se the hole of air entry ''1''
with the provided for closing
Closing cover
with gasket in
neoprene
cover and the gasket delivered with the
boiler. Note: in case the air aspiration will
be effected by the hole ''1'', close the hole
''2''.
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Unical EVE 05 CTN 24 F at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Unical EVE 05 CTN 24 F in the language / languages: English as an attachment in your email.

The manual is 1,36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info