Installation instructions
When selecting a location, please ensure that the FrostControl
is not installed in the vicinity of external heat sources (e.g.
power supplies) or in the immediate proximity of warm air
pipes.
The FrostControl must be installed in front of the boiler in the
cold water supply.
To operate the water supply, all pressure and submergible
pumps can be used at a pressure of up to 2.8 bar.
For the boiler, the FrostControl
replaces the manually operated
safety/drain valve ABO.
For the Trumatic C heating sys-
tem, the FrostControl replaces
the electrically operated safety/
drain valve ELASI.
To allow safe drainage of
the content of the boiler
if there is a risk of frost, an
automatic aeration valve must
be fitted to the warm water
supply of the boiler. Standard
for all warm water devices from
Truma.
Drain directly to the outside at a position protected against
splash water (apply splash guard, if necessary).
Before commencing any work, carefully read the operating
and installation instructions to familiarise yourself with the
product before installation.
The FrostControl heating element (accessory for Combi
heating systems) cannot be used for boilers and the
Trumatic C because they lack the required connection.
Installation instructions and installation place
5
2
3
1
4
1 Boiler
2 Automatic aeration valve
3 FrostControl (safety/drain valve)
4 Drain hose
5 Non-return valve (not included in delivery)
The FrostControl must be mounted on the floor close to the
boiler that is to be protected in a place that is easily accessible
to the user. Ensure that the rotary switch (1) and the push but-
ton (2) can still be operated.
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Truma FrostControl at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Truma FrostControl in the language / languages: English, German, Dutch, Danish, French, Italian, Spanish as an attachment in your email.

The manual is 2,59 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info