8-5-1. Refrigerant Piping Connection
<Flaring>
(1) Cut the pipe with a pipe cutter.
90˚
Obliquity
Roughness
Warp
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.
Outer
dia.
6,35mm
9,52mm
A (mm) R22/R410A
Imperial Rigid
1,0 ~ 1,5/ 0,5 ~ 1,0/
1,5 ~ 2,0 1,0 ~ 1,5
1,0 ~ 1,5/ 0,5 ~ 1,0/
1,5 ~ 2,0 1,0 ~ 1,5
Die Pipe
A
Fig. 8-5-3
Fig. 8-5-4
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.
Then tighten the nut with a spanner and torque
wrench as shown in the figure.
CAUTION
Do not apply excess torque. Otherwise, the
nut may crack depending on the installation
conditions.
Half union or packed valve
Flare nut
Externally
threaded
side
Internally
threaded
side
Use a wrench
to secure.
Use a torque wrench
to tighten.
8-5-2. Vacuum Pumping
INFORMATION
In order to prevent any other refrigerant from being
charged accidentally, each port of the manifold has
been changed in shape.
Differences in Port Size between
Conventional R22 and R410A
Outer dia.
6,35mm
9,52mm
Tightening touque
Nm (kgfm)
16 ~ 18 (1,6 ~ 1,8)
30 ~ 42 (3,0 ~ 4,2)
Port
size
Manifold for R22 Manifold for R410A
7/16 UNF 1/2 UNF
20 threads per inch 20 threads per inch
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manifold
valve to the charge inlet of the gas side packed
valve.
(2) Connect the charge hose (B) to the port of
vacuum pump.
(3) Open fully the low pressure side handle of the
manifold valve.
(4) Operate the vacuum pump.
(5) Close the low pressure side handle of manifold
valve after vacuumizing and stop the vacuum
pump.
Continue vacuumizing more than 15 minutes and
check the pressure gage indicates 0,1MPa
(76 cmHg).
(6) Open the stems of packed valves A and B all the
way.
(7) Securely tighten the stem cap to each of the
packed valve stems.
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Toshiba RAS-10YAX-T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Toshiba RAS-10YAX-T in the language / languages: English as an attachment in your email.

The manual is 10,23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info