INSTALLATION MANUAL
MANUEL DINSTALLATION
INSTALLATIONS-HANDBUCH
MANUALE DI INSTALLAZIONE
MANUAL DE INSTALACIÓN
Outdoor Unit
Unité extérieure
Außengerät
Unità esterna
Unidad exterior
Model/ Modèle / Modell / Modello / Modelo
MCY-MAP0401HT
MCY-MAP0401HT2D
MCY-MAP0501HT
MCY-MAP0501HT2D
MCY-MAP0601HT
MCY-MAP0601HT2D
VOLUME-1
Mini-SMMS MULTI SYSTEM
AIR CONDITIONER
Mini-SMMS
CLIMATISEUR
Mini-SMMS
KLIMASYSTEM
Mini-SMMS
CONDIZIONATORE DARIA
Mini-SMMS
DE AIRE ACONDICIONADO
ADOPTION OF NEW REFRIGERANT
This air conditioner features a new HFC type
refrigerant (R-410A) which does not deplete the
ozone layer.
UTILISATION DU NOUVEAU REFRIGERANT
Ce climatiseur utilise le nouveau réfrigérant HFC
(R410A), qui ne détruit pas la couche d’ozone.
VERWENDUNG EINES NEUEN KÄLTEMITTELS
Dieses Klimagerät arbeitet mit dem neuen HFC
Kältemittel R410A. Dieses Kältemittel greift die
Ozonschicht nicht an.
IMPIEGO DI NUOVO REFRIGERANTE
Questo condizionatore d’aria utilizza il nuovo
refrigerante HFC (R 410A) che non svuota lo strato
d’ozono.
Thank you very much for purchasing TOSHIBA Air Conditioner.
This manual describes the installation method at the outdoor unit
side.
Before installation, please read this Manual thoroughly to perform
correct installation.
For pipe connection for the indoor and outdoor units, flow selector unit
Y-shape branching joint or branch header required sold separately.
Select it according to the capacity.
For pipe connection between the outdoor units, T-shape branching
joint which is sold separately is required.
ADOPCIÓN DE NUEVO REFRIGERANTE
Este acondicionador de aire presenta el nuevo tipo
de refrigerante HFC (R-410A) que no daña la capa
de ozono.
Nous vous remercions pour avoir choisi un climatiseur TOSHIBA.
Ce manuel décrit la méthode d’installation du côté de l’unité
intérieure.
Avant de procéder à l’installation, veuillez lire attentivement ce
manuel pour que l’installation soit correcte.
Pour effectuer le raccordement de la tuyauterie entre les unités
intérieure et extérieure vous devez vous procurer sur place un joint de
ramification en Y ou un joint collecteur, vendu séparément.
Choisissez-le en fonction de la puissance.
Pour effectuer le raccordement de la tuyauterie entre les unités
extérieures vous devez vous procurer sur place un joint de
ramification en T.
Wir danken Ihnen, dass Sie sich für ein TOSHIBA Klimagerät
entschieden haben.
In diesem Handbuch wird die Installation der Außeneinheit
beschrieben.
Bevor Sie mit der Installation beginnen, lesen Sie die dieses
Handbuch sorgfältig und installieren Sie das Produkt entsprechend.
Für die Rohrleitungsverbindungen zwischen Innen- und Außeneinheit
sind Y-Abzweig oder Verteiler erforderlich, die bauseits beigestellt
werden müssen.
Wählen Sie diese Teile entsprechend der Leistung des Systems.
Für die Rohrleitungsverbindungen zwischen den Außeneinheiten sind
T-Abzweige erforderlich, die bauseits beigestellt werden müssen.
Grazie di aver acquistato un condizionatore d’aria TOSHIBA.
Questo manaule spiega come installare l’unità esterna.
Prima d’iniziare l’installazione, leggere attentamente questo manuale,
per eseguire l’installazione correttamente.
Per il collegamento dei tubi relativi alle unità interne ed esterne, sono
necessari l’unità di selezione del flusso, il giunto di derivazione a Y o il
collettore di derivazione, da acquistare a parte.
Selezionarli in base alla capacità.
Per il collegamento dei tubi tra unità esterne, serve il giunto di
derivazione a T da acquistare a parte.
Muchas gracias por haber adquirido este aparato de aire
acondicionado TOSHIBA.
Este manual describe el método de instalación de la unidad exterior.
Lea con atención este manual antes de instalar la unidad para
hacerlo correctamente.
Para la conexión de tubos entre las unidades interiores y exteriores,
es necesario utilizar un colector de derivación o una junta de
derivación en forma de Y para la unidad selectora de caudal
(vendidos por separado).
Seleccione este accesorio según la capacidad del sistema.
Para la conexión de tubos entre las unidades exteriores, es necesario
utilizar una junta de derivación en forma de T (vendido por separado).
CONTENTS
SOMMAIRE
INHALT
INDICE
VOLUME-1
CONTENIDO
ENGLISHITALIANO FRANCAISDEUTSCHESPAÑOL
PIECES ACCESSOIRES .................................................................................................................................................40
MESURES DE SECURITE ..............................................................................................................................................40
1
INSTALLATION DU CLIMATISEUR UTILISANT LE NOUVEAU REFRIGERANT ..................................................42
2
SELECTION DU LIEU DINSTALLATION ................................................................................................................43
3
INSTALLATION DE LUNITE EXTERIEURE ............................................................................................................47
4
INSTALLATION ELECTRIQUE ................................................................................................................................59
5
INSTALLATION DE LUNITE EXTERIEURE ............................................................................................................65
6
REGLAGE DADRESSE ..........................................................................................................................................66
7
ESSAI DE FONCTIONNEMENT ..............................................................................................................................75
8
DEPANNAGE ...........................................................................................................................................................77
ZUBEHÖR .......................................................................................................................................................................79
SICHERHEITSHINWEISE ...............................................................................................................................................79
1
INSTALLATION VON KLIMAGERÄTEN MIT MODERNEN KÄLTEMITTELN .........................................................81
2
AUSWAHL DES AUFSTELLUNGSORTES .............................................................................................................82
3
LTEMITTELLEITUNGEN.....................................................................................................................................86
4
ELEKTRISCHE VERDRAHTUNG ............................................................................................................................98
5
INSTALLATION DER AUSSENEINHEIT ................................................................................................................104
6
ADRESS-EINSTELLUNG ......................................................................................................................................105
7
TESTLAUF .............................................................................................................................................................114
8
FEHLERSUCHE.....................................................................................................................................................116
ACCESSORY PARTS ........................................................................................................................................................1
SAFETY CAUTION ............................................................................................................................................................1
1
INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER ...............................................................................3
2
SELECTION OF INSTALLATION PLACE ..................................................................................................................4
3
REFRIGERANT PIPING.............................................................................................................................................8
4
ELECTRIC WIRING ..................................................................................................................................................20
5
INSTALLATION OF OUTDOOR UNIT ......................................................................................................................26
6
ADDRESS SETUP ...................................................................................................................................................27
7
TEST OPERATION...................................................................................................................................................36
8
TROUBLESHOOTING..............................................................................................................................................38
ACCESSORI ..................................................................................................................................................................118
PRECAUZIONI DI SICUREZZA.....................................................................................................................................118
1
INSTALLAZIONE DI UN NUOVO REFRIGERANTE PER IL CONDIZIONATORE DARIA ...................................120
2
SCELTA DEL POSTO DINSTALLAZIONE ............................................................................................................121
3
TUBAZIONI DEL REFRIGERANTE .......................................................................................................................125
4
COLLEGAMENTI ELETTRICI................................................................................................................................137
5
INSTALLAZIONE DELLUNITÀ ESTERNA............................................................................................................143
6
IMPOSTAZIONE DELLINDIRIZZO ........................................................................................................................144
7
FUNZIONAMENTO DI PROVA ...............................................................................................................................153
8
RISOLUZIONE DEI PROBLEMI ............................................................................................................................155
COMPONENTES ACCESORIOS ..................................................................................................................................157
PRECAUCIONES DE SEGURIDAD ..............................................................................................................................157
1
INSTALACIÓN DEL AIRE ACONDICIONADO CON NUEVO REFRIGERANTE...................................................159
2
SELECCIÓN DEL LUGAR DE INSTALACIÓN ......................................................................................................160
3
TUBERÍA DE REGRIGERANTE ............................................................................................................................164
4
Cableado elECtrico ...............................................................................................................................................176
5
INSTALACIÓN DE LA UNIDAD EXTERIOR ..........................................................................................................182
6
CONFIGURAR LAS IDENTIFICACIONES.............................................................................................................183
7
PRUEBA DE FUNCIONAMIENTO .........................................................................................................................192
8
RESOLUCIÓN DE PROBLEMAS ..........................................................................................................................194
1
ACCESSORY PARTS
r Accessory parts
SAFETY CAUTION
Please read this “Safety Cautions” thoroughly before installation to install the air conditioner
correctly.
The important contents concerned to the safety are described in the “Safety Cautions”.
Be sure to keep them. For Indications and their meanings, see the following description.
n Explanation of indications
WARNING
Indicates possibilities that a death or serious injury of personnel is caused by an incorrect handling.
CAUTION
Indicates contents that an injury (1) or property damage (2) only may be caused when an incorrect work has
been executed.
1 : “Injury” means a hurt, a burn, or an electric shock which does not require hospitalization or a long-term going to
the hospital.
2 : “Property damage” means an enlarged damage concerned to property, or breakage of materials.
After the installation work has been completed, perform a trial operation to check for possible
problems.
Follow the owner’s manual and explain to the customer how to use and maintain the unit.
n The outdoor air conditioner requires the following additional components in order to complete
a MiNi-SMMS system. (Indoor unit, remote controller, Y-shape branch joint or branching
header.) These items must be selected in accordance to the system capacity.
MCY-
Part name
Installation Manual
Owner’s Manual
Joint socket
Protective bush
Guard material for
passage part
Drain nipple
Waterproof rubber cap
Q’ty
0401 type 0501 type 0601 type
222
111
—— 1
111
111
111
111
Shape
Usage
(Be sure to handover to customers.)
(Be sure to handover to customers.)
Connecting pipes for gas side (Ø15.9 to Ø19.1)
Protection for wiring
Protection for knockout
2
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air
conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
Using the tool or piping materials exclusive to R410A, install the air conditioner surely according
to this Installation Manual.
The pressure of the used HFC system R410A refrigerant is higher approx. 1.6 times of that of the former
refrigerant. If the exclusive piping materials are not used, or there is imperfection in installation, a crack or an
injury is caused and also a water leak, an electric shock, or a fire may be caused.
Take measures so that the refrigerant does not exceed the limit concentration even if it leaks
when installing the air conditioner in a small room.
For the measures not to exceed the limit of concentration, contact the dealer. If the refrigerant leaks and it
exceeds the limit of concentration, an accident of oxygen shortage is caused.
The location of the installation must be able to protect from abnormal environmental conditions,
such as earthquake and typhoons.
An incorrect installation will cause a risk of unit movement resulting in a possible accident.
Perform a specified installation work against a strong wind such as typhoon or earthquake.
If the air conditioner is imperfectly installed, an accident by falling or dropping may be caused.
If refrigerant gas leaks during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes into contact with fire, noxious gas may generate.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks onto the room and flows near to a source of fire, noxious gas maybe generated.
Never recover refrigerant in the outdoor unit.
Be sure to use a refrigerant recovery device to recover refrigerant in reinstallation or repair work.
Recovery of refrigerant in the outdoor unit is unavailable; otherwise a serious accident such as crack or human
injury is caused.
Electrical work must be performed by a qualified electrician in accordance with the installation
manual. Ensure the air conditioner uses a designated power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
When connecting the installation wiring, be sure that all fixing terminals are securely fixed.
Ensure earth connection.
If earth wiring is poor, this will cause risk of electric shock.
If grounding is incomplete, an electric shock is caused.
CAUTION
Ensure that the unit is to placed where there is no risk of flammable gases.
If flammable gases accumulate around the outside of the unit combustion may occur.
Ensure the outdoor unit is fixed to the base, to prevent movement of the unit.
Ensure an electrical leakage breaker is fitted. This is to prevent the risk of electric shock.
Using a torque wrench, tighten the flare nuts to the specified torque setting.
Over tightening will risk damaging the flare nut, and may cause refrigerant to leak after a period of time.
ENGLISH
3
1
INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membrane, or oils because the
pressure of R410A refrigerant is higher than that of the former refrigerant by approx. 1.6 times. Accompanied with
adoption of the new refrigerant, refrigerating oil has been also changed. Therefore pay attention so that water,
dust, former refrigerant, or refrigerating oil does not enter into the refrigerating cycle of the new refrigerant air
conditioner during installation work.
To prevent from mixing of refrigerant or refrigerating oil, the size of charge port of the main unit or connecting
section of installation tool differs from that of the air conditioner for the former refrigerant. Accordingly the
exclusive tools are required for the new refrigerant (R410A) as shown below.
For connecting pipes, use the new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts as described below for the installation work.
The tools and parts which will be newly prepared in the following items should be restricted to the exclusive use.
Explanation of symbols
l
: Newly prepared (It is necessary to use it properly exclusive to R410A separated from those for R22 or R407C.)
¡ : Former tool is available.
Used tools
Gauge manifold
Charging hose
Charging cylinder
Gas leak detector
Vacuum pump
Vacuum pump with counter-
flow preventive adapter
Flare tool
Bender
Refrigerant recovery device
Torque wrench
Pipe cutter
Refrigerant cylinder
Welding machine/
Nitrogen gas cylinder
Refrigerant charging balance
Usage
Vacuuming or charging of
refrigerant and operation check
Charges refrigerant
Checks gas leak
Vacuum drying
Vacuum drying
Flare processing of pipes
Bending processing of pipes
Recovers refrigerant
Tightens flare nut
Cuts pipes
Charges refrigerant
Welding of pipes
Charges refrigerant
Proper use of tools/parts
l
Newly prepared, Exclusive to R410A
l
Newly prepared, Exclusive to R410A
Unusable (Use the Refrigerant charging balance.)
l
Newly prepared
Usable if a counter-flow preventive adapter is attached
¡
: R22 (Existing article)
¡
: Usable by adjusting size
¡
: R22 (Existing article)
l
Exclusive to R410A
l
Newly prepared, exclusive to Ø12.7mm and Ø15.9mm
¡
: R22 (Existing article)
l
Exclusive to R410A
ID : Refrigerant name entered
¡
: R22 (Existing article)
¡
: R22 (Existing article)
4
Equivalent HP
Outdoor unit capacity type
Cooling capacity (kW)
Heating capacity (kW)
Inverter unit
0401 type 0501 type 0601 type
4 HP 5 HP 6 HP
12.1 14.0 15.5
12.5 16.0 18.0
Appearance
2
SELECTION OF INSTALLATION PLACE
WARNING
The installation of the air conditioning unit must be positioned in a location that can sufficiently
support its weight and give protection against adverse environmental conditions.
Failure to do so may result in unit damage and possible human injury.
CAUTION
Ensure that the unit is to placed where there is no risk of flammable gases.
If flammable gases accumulate around the outside of the unit combustion may occur.
Ensure the outdoor unit is fixed to the base, to prevent movement of the unit.
Obtain permission from the customer to install the unit in a location that satisfies the following
requirements :
A location that permits level installation of the unit.
A location that provides enough space to service the unit safely
A location where water draining from the unit will not pose a problem
Apply electric insulation between metal section of the building and metal section of the air
conditioner in conformance with the Local Regulation.
Avoid installing in the following places.
Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas
(hot spring). (Should the unit be used in these places, special protective measures are needed.)
Place exposed to oil, vapor, oil smoke or corrosive gas.
Place where organic solvent is used nearby.
Place close to a machine generating high frequency.
Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)
Place where noise of the outdoor unit is easily transmitted.
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)
Place with poor ventilation.
(Especially in Concealed duct type indoor unit, before air ducting work, check whether value of air volume,
static pressure and duct resistance are correct.)
Equipments
5
AInstallation space
Considering functions, reserve space necessary for
installation work and servicing.
Installation place
A place which provides a specified space around the
outdoor unit.
A place where the operation noise and discharged air
are not given to your neighbors.
A place that is not exposed to a strong wind.
A place that does not block a passage.
When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
There must be sufficient space for carrying in the unit.
A place where the drain water does not make any
problem.
CAUTION
1. Install the outdoor unit at a place where dis-
charge air is not blocked.
2. When an outdoor unit is installed in a place that
is always exposed to a strong wind like a coast or
on a high story of a building, secure a normal fan
operation by using a duct or a wind shield.
3. When installing the outdoor unit in a place that is
constantly exposed to a strong wind such as the
upper stairs or rooftop of a building, apply the
windproof measures referring to the following
examples.
1) Install the unit so that its discharge port faces
to the wall of the building.
Keep a distance 500 mm
or more between the unit
and the wall surface.
2) Supposing the wind direction during the
operation season of the air conditioner, install
the unit so that the discharge port is set at
right angle to the wind direction.
4. Installation in the following places may result in
some troubles. Do not install the unit in such
places below.
A place full of machine oil.
A place full of sulfuric gas.
A place where high-frequency radio waves are
likely to be generated as from audio equipment,
welders, and medical equipment.
500
Strong wind
Strong wind
Necessary space for installation
Obstacle at rear side
[Upper side is free]
1. Single unit installation
2. Obstacles at both right and left sides.
3. Serial installation of two or more units
[Obstacle also at the upper side]
Obstacle at front side
[Upper side is free]
1. Single unit installation
2. Serial installation of two or more units
150
or more
150
or more
300
or more
200
or more
The height of the
obstacle should be
lower than the height
of the outdoor unit.
150
or more
300
or more
300
or more
300
or more
200 or more
The height of the obstacle should be lower
than the height of the outdoor unit.
500
or more
1000
or more
2
SELECTION OF INSTALLATION PLACE
500
or more
150
or more
6
[Obstacle also at the upper side]
Obstacles at both front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear side,
should be lower than the height of the outdoor unit.
[Standard installation]
1. Single unit installation
2. Serial installation of two or more units
Serial installation at front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear sides
should be lower than the height of the outdoor unit.
[Standard installation]
1000
or more
1000
or more
1000
or more
150
or more
300
or more
300
or more
1000
or more
200
or more
1000
or more
300
or more
1500
or more
2000
or more
200
or more
Installation of outdoor unit
Before installation, check strength and horizontally
of the base so that abnormal sound does not
generate.
According to the following base diagram, fix the
base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
Set the out margin of the anchor bolt to 15mm or less.
In case of draining through the drain hose, attach
the following drain nipple and the waterproof rubber
cap, and use the drain hose (Inner diam.: 16mm)
sold on the market. And also seal the screws
securely with silicone material, etc. so that water
does not drop down. Some conditions may cause
dewing or dripping of water.
When there is a possibility of freezing of drain at the
cold district or a snowfall area, be careful for
drainage ability of drain. The drainage ability
increases when a knockout hole on the base plate
is opened. (Open the knockout hole to outside using
a screwdriver, etc.)
600150 150
430
365
40
400
Drain hole
Knockout hole
Drain nipple mounting hole
15 or less
Drain nipple Waterproof rubber cap
Knockout hole
Waterproof rubber cap
Open
Drain nipple
7
Refrigerant piping connection
CAUTION
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak at connected points.
For reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.
Knockout of pipe cover
2
SELECTION OF INSTALLATION PLACE
Knockout procedure
The indoor/outdoor connecting pipes can be con-
nected to 4 directions.
Take off the knockout part of the pipe cover in which
pipes or wires pass through the base plate.
As shown in the figure, do not remove the pipe cover
from the cabinet so that the knockout hole can be
easily punched. To knock out, it is easily taken off by
hands by punching a position at the lower side of 3
connected parts with screwdriver along the guide line.
How to remove the front panel
1. Remove screws of the front panel.
2. Pull the front panel downward.
Removing the front panel, the electric parts appear at
the front side.
The metal pipes are attachable to the piping holes.
If the size of the used power pipe does not match
with the hole, adjust the hole size to match with pipe
size.
Be sure to fix the power cable and indoor/outdoor
connecting cable with bundling band sold on the
market so that they do not make contact with the
compressor and discharge pipe.
(Temperature of the compressor and discharge pipe
becomes high.)
In order to avoid the force applied to on the connect-
ing section, be sure to fix the cables to the cord
clamps provided on the pipe valve fixing plate and
the electric parts box.
Front direction
Rear direction
Pipe cover
Side direction
Down direction
After marking the knockout hole, remove the burr
and mount the attached protective bush and guard
material for pass-through part in order to protect
pipes and wires.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
Cord clamp
Electric parts box
Front panel
Terminal
plate
8
3
REFRIGERANT PIPING
WARNING
If the refrigerant gas leaks during
installation work, ventilate the room
immediately.
If the leaked refrigerant gas comes into contact
with a source of fire, noxious gas maybe
generated.
After installation work is complete, check
refrigerant gas does not leak.
If the refrigerant leaks into the room and comes
into contact with a naked flame, noxious gas
maybe generated.
Pipe forming/End positioning
Flaring
1. Cut the pipe with a pipe cutter.
2. Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly
manufactured for R410A are recommended.
However, the conventional tools can be used by
adjusting projection margin of the copper pipe.
* In case of flaring for R410A with the conventional flare
tool, pull it out approx. 0.5 mm more than that of R22
to adjust to the specified flare size.
The copper pipe gauge is useful for adjusting
projection margin size.
Projection margin in flaring :
B (Unit : mm)
Rigid (Clutch type)
Imperial (Wing nut type)
Flaring size : A (Unit : mm)
Outer dia. of copper pipe
9.5
15.9
R410A R22
1.5 to 2.0 1.0 to 1.5
2.0 to 2.5 1.5 to 2.0
Outer dia.
of copper
pipe
9.5
15.9
R410A tool used
R410A R22
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
Conventional tool used
R410A R22
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
+0
-
0.4
Outer dia. of copper pipe
9.5
15.9
A
R410A R22
13.2 13.0
19.7 19.4
90˚
Obliquity Roughness Warp
NO GOODOK
A
B
9
Tightening of connecting part
(Unit: Nm)
REQUIREMENT
1. Do not put the spanner on the cap.
The valve may be broken.
2. If applying excessive torque, the nut may be
broken according to some installation
conditions.
After the installation work, be sure to check gas leak
of connecting part of the pipes with nitrogen.
Align the centers of the connecting pipes and tighten
the flare nut strong as far as possible with your
fingers.
Then fix the nut with a spanner and tighten it with
torque wrench as shown in the figure.
As shown in the figure, be sure to use a double
spanner to loosen or tighten the flare nut of the valve
at gas side. If using a single spanner, the nut cannot
be tightened with necessary tightening torque.
On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.
Outer dia. of copper pipe
9.5 mm (diam.)
15.9 mm (diam.)
Tightening torque
33 to 42 (3.3 to 4.2 kgfm)
68 to 82 (6.8 to 8.2 kgfm)
Valve at gas side
Pressure of R410A is higher than that of R22
(Approx. 1.6 times). Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor/outdoor units at the
specified tightening torque. Incomplete connections
may cause not only a gas leak, but also a trouble of
the refrigeration cycle.
Do not apply refrigerating machine oil to the
flared surface.
Externally
threaded side
Internally
threaded side
Fix with spanner.
Tighten with torque wrench.
Half union or packed valve Flare nut
Cover
Cap
Piping valve
Tightened
Flare nut
Loosened
Cover
NO GOOD
3
REFRIGERANT PIPING
10
Pipe connecting method of valve at gas side
Outdoor unit
capacity type
0401 type
0501 type
0601 type
Gas pipe
diameter
Ø15.9
Ø19.1
Pipe connecting method of valve at gas side
Connect Ø15.9 pipe with flaring.
For braze connection of Ø19.1 gas pipe, refer to the following method.
1. Form the pipe so that the end part of the pipe will be out from the
outdoor unit along the taking-out direction of the pipe.
The Ø15.9 gas pipe to be supplied locally.
2. Using the joint socket (Accessory), connect with braze Ø15.9 gas
pipe and Ø19.1 gas pipe at outside of the outdoor unit.
3. After connecting the pipes, apply thermal insulation process to the
gas pipe until near the valve.
Flare
connection
Gas pipe Ø15.9
(Local supply)
Ball valve of
gas side Ø15.9
Braze connection
(Aconnect with braze)
Gas pipe Ø19.1
(Local supply)
Flare
connection
Gas pipe Ø15.9
(Local supply)
Ball valve of
gas side Ø15.9
Joint socket
(Accessory)
p.4
Ac
11
Coupling size of brazed pipe
(Unit: mm)
Connected section
External size Internal size
Connected section
External size Internal size
Standard outer dia. (Allowable difference)
Min. depth
of insertion
Standard outer dia. of
connected copper pipe
CFKG
Oval value
Min. thickness
of coupling
6.35 6.35 (±0.03) 6.45 (
+0.04
0.02
) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 (
+0.04
0.02
) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 (
+0.04
0.02
) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 (
+0.04
0.02
) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 (
+0.03
0.03
) 11 10 0.15 or less 0.80
Minimum wall thickness for R410A application
Soft Harf Hard or Hard OD (Inch) OD (mm) Minimum wall thickness (mm)
OK OK 1/4 6.35 0.80
OK OK 3/8 9.52 0.80
OK OK 1/2 12.70 0.80
OK OK 5/8 15.88 1.00
NG * OK 3/4 19.05 1.00
* If the pipe size is Ø19.0 or more, use a
suitable material.
Table 1 Table 2
Capacity code Capacity code
Total capacity code of
connectable indoor units
Indoor unit
capacity type
Equivalent to HP Equivalent to capacity
Outdoor unit
capacity type
Equivalent to HP
No. of
connectable
indoor units
Min. (HP) Max. (HP)
007 type 0.8 2.2 0401 type 4 6 3.2 5.2
009 type 1 2.8 0501 type 5 8 4.0 6.5
012 type 1.25
3.6
0601 type 6 9 4.8 7.8
015 type 1.7
4.5
018 type 2
5.6
024 type 2.5
7.1
027 type 3
8
030 type 3.2
9
036 type 4
11.2
048 type 5
14
K
ØC
G
ØF
Selection of pipe materials and size
Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank.
The capacity codes of the outdoor units are decided at each capacity rank.
The maximum No. of connectable indoor unit and the total value of capacity codes of the indoor units are also
decided.
3
REFRIGERANT PIPING
12
Selection of refrigerant piping
No. Piping parts Name Selection of pipe size
Size of main pipe
Outdoor unit capacity type Gas pipe Liquid pipe
0401 type 15.9 9.5
0501 type 15.9 9.5
0601 type 19.1 9.5
Outdoor unit
1st branching section
Main pipe
Pipe size between branching sections
Total capacity codes of indoor units
at down stream side
Equivalent to HP
Gas pipe Liquid pipe
Below 2.8 12.7 9.5
2.8 to below 6.4 15.9 9.5
6.4 to below 7.2 19.1 9.5
Branching section
Branching section
Branching pipe
Note)
If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of outdoor units.
Connecting pipe size of indoor unit
Indoor unit capacity type Gas pipe Liquid pipe
007, 009, 012 type 9.5 6.4
015, 018 type 12.7 6.4
024, 030, 036, 048 type 15.9 9.5
Branching section
Indoor unit
Indoor unit
connecting pipe
Selection of branching section
Total capacity codes of indoor
units at down stream side
Equivalent to HP
Model name
Below 6.4 RBM-BY53E
Y-shape branch joint
6.4 or more and up to 7.8 RBM-BY103E
For 4 branches Up to 7.8 RBM-HY1043E
Branch header
For 8 branches Up to 7.8 RBM-HY1083E
Branching section
Y-shape branch joint
Branch header
Note)
*1 :
*2 :
When using a Y-shape branching joint for the 1st branch, select according to
capacity code of the outdoor unit.
For 1 line after branching header indoor units with a maximum capacity code of
6.0 in total can be connected.
4
4
4
4
Outdoor unit
1
1st branching
section
Main pipe
Gas pipe
Liquid pipe
Indoor unit
Branching
pipe
Y-shape
branch joint
3
3 3 3
2
Branching
pipe
Branch header
2
2
3
3 3
13
4
4
4
4
Outdoor unit
1
1st branching
section
Main pipe
Gas pipe
Liquid pipe
Indoor unit
PMV Kit
Indoor unit
Branching
pipe
Y-shape
branch joint
3
5
3 3 3
Branching
pipe
Branch header
2
2
2
3
3 3
5 5 5
5 5 5
Selection of refrigerant piping for quiet place (with PMV Kit)
No. Piping parts Name Selection of pipe size
Size of main pipe
Outdoor unit capacity type Gas pipe Liquid pipe
0401 type 15.9 9.5
0501 type 15.9 9.5
0601 type 19.1 9.5
Outdoor unit
1st branching section
Main pipe
Pipe size between branching sections
Total capacity codes of indoor units
at down stream side
Equivalent to HP
Gas pipe Liquid pipe
Below 2.8 12.7 9.5
2.8 to below 6.4 15.9 9.5
6.4 to below 7.2 19.1 9.5
Branching section
Branching section
Branching pipe
Note)
If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of outdoor units.
Connecting pipe size of indoor unit
Indoor unit capacity type Gas pipe Liquid pipe
007, 009, 012 type 9.5 6.4
015, 018 type 12.7 6.4
024, 030, 036, 048 type 15.9 9.5
Branching section
Indoor unit
Indoor unit
connecting pipe
Selection of branching section
Total capacity codes of indoor
units at down stream side
Equivalent to HP
Model name
Below 6.4 RBM-BY53E
Y-shape branch joint
6.4 or more and up to 7.8 RBM-BY103E
For 4 branches Up to 7.8 RBM-HY1043E
Branch header
For 8 branches Up to 7.8 RBM-HY1083E
Branching section
Y-shape branch joint
Branch header
Note)
*1 :
*2 :
When using a Y-shape branching joint for the 1st branch, select according to
capacity code of the outdoor unit.
For 1 line after branching header indoor units with a maximum capacity code of
6.0 in total can be connected.
Selection of PMV Kit
Indoor unit capacity type Model name
007, 009, 012 type RBM-PMV0361E
015, 018, 024 type RBM-PMV0901E
PMV Kit PMV Kit
3
REFRIGERANT PIPING
15
Allowable length/height difference of refrigerant piping for quiet places (with PMV Kit)
Allowable
value
Piping section
Total extension of pipe (Liquid pipe, real length) 150 m
L1 + L2 + L3 + L4
+ a + b + c + d + e + f + g + h + I + j + k+ l + m + n
Real length 65 m
Furthest piping length L (
1)
Equivalent length 80 m
L1 + L3 + L4 + g + n
Max. equivalent length of main pipe 50 m L1
Equivalent length of furthest piping from
1
st
branching Li (
1)
15 m L3 + L4 + g + n
Max. real length of indoor unit connecting pipe 15 m a + h, b + i, c + j, d + k, e + l, f + m. g + n
Piping
Length
Real length between PMV KIT and indoor unit
2 m or more
Below 10 m
h, i, j, k, l, m, n
Upper outdoor unit 30 m ———
Height between indoor
and outdoor units H1
Lower outdoor unit 20 m ———
Height
Difference
Height between indoor unit and PMV kit H2 15 m ———
1 : Furthest indoor unit from 1
st
branch to be named “A”.
PMV Kit
Indoor unit Indoor unit
PMV Kit
NO GOOD OK
Note)
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
Outdoor unit
1st branching
section
Main pipe
L1
Height difference
between indoor
and outdoor units
H1
Height difference
between indoor unit
and PMV Kit
H2
* Between highest unit
and lower units.
Example)
Indoor unit
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
L4
e
f
lm
n
g
Branching pipe L2
Branch header
Branching pipe
L3
ab
hi jk
cd
Y-shape
branch joint
PMV Kit
H2
H2
H2
A
1
3
REFRIGERANT PIPING
16
Airtight test
After the refrigerant piping has finished, execute an airtight test. For an airtight test, connect a nitrogen gas bomb as
shown in the figure below, and apply pressure.
Be sure to apply pressure from the service ports of the packed valves (or ball valves) at liquid side, discharge gas
side, and suction gas side.
An air tight test can be only performed to the service ports at liquid side, discharge gas side, and suction gas side
of the outdoor unit.
Close fully valves at liquid side, discharge gas side, and suction gas side. As there is possibility that nitrogen gas
enters in the refrigerant cycle, re-tighten the valve rods before applying pressure.
(Re-tightening of the valve rods are unnecessary for valves at discharge gas side because they are ball valves.)
For each refrigerant line, apply pressure gradually with steps at liquid side, discharge gas side, and suction gas
side.
Be sure to apply pressure to suction gas side, discharge gas side, and liquid side.
REQUIREMENT
Never use Oxygen, Flammable gas and Noxious gas in an airtight test.
STEP 1 : Apply pressure 0.3MPa (3.0kg/cm
2
G) for 3 minutes or more.
Available to detect a gross leakage
STEP 2 : Apply pressure 1.5MPa (15kg/cm
2
G) for 3 minutes or more.
STEP 3 : Apply pressure 3.73MPa (38kg/cm
2
G) for approx. 24 hours. Available to detect slow leakage
Check pressure down.
No pressure down: Accepted Pressure down: Check the leaked position.
However, if there is difference of ambient temp. between when pressure has been applied and when
24 hours passed, pressure changes by approx. 0.01MPa (0.1kg/cm²G) per 1°C. Correct the pressure.
Leaked position check
When a pressure-down is detected in STEP 1, STEP 2, or STEP 3, check the leakage at the connecting points.
Check leakage with hearing sense, feeler, foaming agent, etc, and perform re-brazing or re-tightening of flare if
leakage is detected.
VL VH
Connected to indoor unit
Packed valve fully closed
(Gas side)
Outdoor unit
Low-
pressure
gauge
High-
pressure
gauge
Gauge
manifold
Brazed
Service port
Ø6.4
Copper pipe
Ø6.4
Copper pipe
Fully closed
Reducing
valve
Nitrogen gas
Ball valve fully closed
(Liquid side)
Service port
Main pipe
17
Air purge
For the air purge at installation time (Discharge of air in connecting pipes), use Vacuum pump method from
viewpoint of the protection of the earths environment.
For protection of the earths environment, do not discharge the refrigerant gas in the air.
Using a vacuum pump, eliminate the remaining air (nitrogen gas, etc.) in the unit. If gas remains, performance
and reliability of the unit may be reduced.
After the airtight test, discharge nitrogen gas. Then connect the gauge manifold to the service ports at suction gas
side, discharge gas side and liquid side, and connect the vacuum pump as shown in the following figure.
Be sure to perform vacuuming for suction gas side, discharge gas side and liquid side.
Be sure to perform vacuuming from both suction gas side, discharge gas side and liquid side.
Be sure to perform vacuuming from both liquid and gas sides.
Use a vacuum pump with counter-flow preventive function so that oil in the pump does not back up in the pipe of
the air conditioner when the pump has been stopped. (If oil in the vacuum pump enters in to the air conditioner
with R410A refrigerant, an error may occur in the refrigeration cycle.)
Use a vacuum pump that has a high vacuum (below -755mmHg) and a large exhaust gas amount (over 40L/
minute).
Perform vacuuming for 2 or 3 hours though time differs due to pipe length. In this time, check all packed valves at
liquid, gas and balance sides are fully closed.
If vacuuming valve amount is not decreased to below -755mmHg even after vacuuming for 2 hours or more,
continue vacuuming for 1 hour or more. If -755mmHg or less cannot be obtained by 3 hours or more vacuuming,
detect and repair the leak.
When the vacuuming valve has reached -755mmHg or less after vacuuming for 2 hours or more, close valves VL
and VH on the gauge manifold fully. Stop the vacuum pump, leave it as it is for 1 hour and then check the vacuum
does not change. If it does change then there may be a leak within the system.
After the above procedure for vacuuming has finished, exchange the vacuum pump with a refrigerant cylinder and
advance to the additional charging of refrigerant.
P
VL VH
Connected to indoor unit
Packed valve fully closed
(Gas side)
Outdoor unit
Low-
pressure
gauge
High-
pressure
gauge
Gauge manifold
Brazed
Service port
Fully closed
Ball valve fully closed
(Liquid side)
Vacuum pump
Service port
Main pipe
3
REFRIGERANT PIPING
18
Addition of refrigerant
After vacuuming work, exchange the vacuum pump with the refrigerant bomb and then start the additional charging
work of refrigerant.
Calculating the amount of additional refrigerant required
When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes on site is
not included. Calculate the additional amount required, and add that amount to the system.
Additional refrigerant charge amount is calculated from size of liquid pipe at site and its real length.
Additional
refrigerant charge
R (kg)
amount at site
Real length
of liquid pipe
+
Additional refrigerant charge
amount per liquid pipe 1m
(Table 1)
Compensation
by outdoor HP
(Table 2)
Example : (0501 type)
Note)
If the additional refrigerant amount indicates a negative result from the calculation, use air conditioner without
the adding of any additional refrigerant.
Charging of refrigerant
Keeping valve of the outdoor unit closed, be sure to charge the liquid refrigerant into service port at liquid side.
If the specified amount of refrigerant cannot be charged, open fully valves of outdoor unit at liquid and discharge/
suction gas sides, operate the air conditioner in COOL mode under condition that valve at suction gas side is a
little returned to close side, and then charge refrigerant into service port at suction gas side. In this time, choke the
refrigerant slightly by operating valve of the bomb to charge liquid refrigerant. The liquid refrigerant may be
charged suddenly, therefore be sure to charge refrigerant gradually.
When refrigerant leaks and refrigerant shortage occurs in the system, recover the refrigerant in the system and
recharge refrigerant newly up to the correct level.
REQUIREMENT
Entry of refrigerant charge amount
Complete the refrigerant record column found on the wiring diagram, with detail of the additional refrigerant
amount and name of service engineer at the time of installation.
The total amount of refrigerant refers to the shipment charge plus any additional refrigerant at the time of
installation. The refrigerant amount at shipment is indicated on the unit name plate.
Lx : Real total length of liquid pipe Ø6.4 (m)
Ly : Real total length of liquid pipe Ø9.5 (m)
L1 Ø9.5 : 10m L2 Ø9.5 : 10m L3 Ø9.5 : 5m a Ø9.5 : 3m
b Ø6.4 : 3m c Ø6.4 : 4m d Ø6.4 : 5m
Additional charge amount R (kg)
= (Lx × 0.025kg/m) + (Ly × 0.055kg/m) + (0.4kg)
= (12 × 0.025kg) + (28 × 0.055kg) + (0.4kg)
= 1.44kg
a
L2
L3
L1
bcd
Table 1
Table 2
0401 type 0501 type 0601 type
0.8 0.4 0
Pipe dia. at liquid side
Additional refrigerant amount/1m
(kg)
Outdoor unit capacity type
Compensation by outdoor HP
(kg)
Ø6.4 Ø9.5
0.025 0.055
19
Full opening of the valve
Open the valve of the outdoor unit fully.
Using a 4mm-hexagonal wrench, open fully the
valve key on the liquid side.
Using a spanner open fully the valve key on the
packed valve at suction gas side.
Using a pair of pinchers, open fully the handle on the
ball valve at the discharge gas side.
Be careful that the handling of the ball valve differs
from that of the packed valve.
How to open the ball valve at gas side
Valve handling precautions
Open the valve stem or the handle until it strikes
the stopper.
It is unnecessary to apply further force.
Securely tighten the cap with a torque wrench.
Cap tightening torque
Position of grooves for driver
*1. When opened fully, do not apply an excessive
torque after the screwdriver hit the stopper;
otherwise a trouble may be caused on the valve.
Heat insulation for pipe
Apply the heat insulation to the pipework separately.
(liquid, suction and discharge).
Use thermal heat insulation which can withstand
temperatures of 120°C or more.
CAUTION
Upon completion of the pipework connections fit
the piping/wiring panel and the pipe cover.
Gaps between the pipes and the cover are to be
filled using a suitable putty or silicone.
If the pipework is fitted in the downward or
sideways position, ensure that the base plate
and side plate are closed and sealed.
If an opening is left unsealed there is a risk of a
fault due to the entering of water or dust.
Valve size
Ø9.5
Ø15.9
Charge port
33 to 42Nm (3.3 to 4.2kgfm)
20 to 25Nm (2.0 to 2.5kgfm)
14 to 18Nm (1.4 to 1.8kgfm)
Valve unit
Charge port
Using a minus screwdriver,
turn it counterclockwise by
90˚ until it hits the stopper.
(Full open)
Flare nut
Grooves
for driver
Closed completely Opened fully
3
REFRIGERANT PIPING
20
4
ELECTRIC WIRING
WARNING
Electrical work must be performed by a qualified electrician in accordance with the installation manual.
Ensure the air conditioner uses a designated power supply.
An insufficient power supply capacity or inappropriate installation may cause a fire.
When connecting the installation wiring, be sure that all fixing terminal are securely fixed.
Ensure earthling practice is correctly performed.
Grounding is necessary, if earthling practice is incomplete an electric shock maybe caused.
CAUTION
The installation fuse must be used for the power supply line of this outdoor unit.
Incorrect/incomplete wiring might cause an electrical fire or smoke.
Prepare the exclusive power supply for the outdoor unit.
Ensure an electrical leakage breaker is fitted. This is to prevent the risk of electric shock.
To Disconnect the Appliance from Main Power Supply.
This appliance must be connected to a main power supply by means of a switch with a contact separation of at
least 3 mm.
REQUIREMENT
Perform wiring of the power supply in conformance with the regulations of the local authorities.
For wiring of the power supply in the indoor unit, refer to the Installation Manual of the relevant indoor unit.
Never connect 220240V to the terminal block (U1, U2, U3, U4). (Fault will be caused.)
Arrange the electrical wiring so that they do not come into contact with high-temperature parts of the pipework;
this is to prevent the risk of insulation melting and causing a possible accident.
After connecting wires to the terminal block, secure wiring with cable clamp.
Install control wiring and refrigerant piping within the same line.
Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe has finished.
For cabling of the power supply of the indoor units cabling between indoor and outdoor units, refer to the
Installation Manual of the indoor unit.
Knockout for
control wiring and
refrigerant piping
Knockout for
power supply wiring
Connection of power supply wire with control wire
Insert power supply wire and control wire after
removing knockout of the piping/wiring panel at front
side of the outdoor unit.
The knockout piping and the wiring hole are also
provided to the front surface, the right side, and the
rear side.
Note :
Be sure to separate the power supply wires and each control wire.
Arrange the power supply wires and each control wire so that they do not contact with the bottom surface of the
outdoor unit.
A terminal block (U3, U4 terminal blocks) for connecting an optional part Central remote controller etc. is
provided on the inverter unit, so be careful to miswiring.
21
Power supply specifications
Select the power supply cabling and fuse of each outdoor unit from the following specifications.
Ensure an earth leakage breaker is installed, failure to install, may result in electric shock.
The installation fuse must be used for the power supply line of this outdoor unit.
Be sure to use the appropriate type of overcurrent breaker (fuse) switch.
Observe local regulation regarding wire size selection and installation.
3-core cable in conformance with Design 60245 IEC 66.
Do not connect the units looping via the terminal blocks (L, N).
Outdoor unit
capacity type
0401 type
0501 type
0601 type
Wire size*
6 mm², Max. 28 m
6 mm², Max. 25 m
6 mm², Max. 22 m
Maxim running
current
25A
28A
31A
Installation
fuse
32A
32A
40A
Over current breaker (fuse) switch
Outdoor unit
Outdoor unit power supply
Earth leakage breaker
Earth
LN
* Design 60245 IEC66
(Terminal block) (Stripping length power cable)
(Cord clamp)
(Protective bush : Accessory)
Power cable
NL
10
LN
10
50
90
Earth line
Power cable
Power
supply
MCY-MAP###HT series
MCY-MAP###HT2D series
1N~ 50Hz 220V-240V
1N~ 60Hz 220V
(Connection example)
Connection of power supply
n Power supply wire
Connect the power supply cables and earthling wire to the power supply terminal block.
Tighten the screws on the terminal block and secure the cables with the cord clamp.
(Do not apply tension to the connecting section of the terminal block.)
4
ELECTRIC WIRING
22
Power supply wiring
Item
Model
Wire size
All models of indoor units 2.0 mm² Max. 20m 3.5 mm² Max. 50m
[Indoor unit]
NL
Earth
NL
Earth
NL
Earth
NL
Earth
Earth leakage breaker
Indoor unit
Connection cable
Connector conversion cable
(MMK-AP∗∗∗2H (High Wall) does not use a this conversion cable.)
Indoor control P.C. board
Pulse motor valve (Indoor unit side)
CN82 connector
Pull box
Main switch
Indoor unit power supply
1N~ 50Hz, 220 240V
1N~ 60Hz, 220V
PMV
PMV Kit
For Indoor unit power supply (The outdoor unit has a separate power supply.)
Note)
Power supply cord specification : Cable 3-core 2.5 mm², inconformity with Design 60245 IEC57.
The connecting length indicated in the table represents the length from the pull box to the outdoor unit when the
indoor units are connected in parallel for power, as shown in the illustration below. A voltage drop of no more than
2% is also assumed. If the connecting length will exceed the length indicated in the table, select the wire
thickness in accordance with indoor wiring standards.
Determine the wire size for indoor unit according to the number of connected indoor units downstream.
For details of the PMV Kit, refer to the Installation Manual.
Connection of PMV Kit
23
Design of control wiring
1. All control wiring is 2-core and non-polarity wire.
2. Ensure use of shielded wiring in the following cases to prevent noise issues.
Indoor-indoor / outdoor-indoor control wiring, Central control wiring.
Table-1 Control wiring between indoor and
outdoor units (L1, L2, L3),
Central control wiring (L4)
Note 1 : Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table-3 Remote controller wiring (L6, L7)
Wiring
Type
Size
Length
1
2-core, non-polarity
Shield wire
1.25 mm² : Up to 1000 m
2.0 mm² : Up to 2000 m
Wiring
Type
Size
Length
2-core, non-polarity
Shield wire
1.25 mm² to 2.0 mm²
Up to 100 m (L5)
Wire
Size
Length
2-core
0.5 mm² to 2.0 mm²
Up to 500 m ( L6 + L7 )
Up to 400m with of wireless remote controller in group control.
Up to 200m total length of control wiring between indoor units ( L6 )
U3 U4
U1 U2
U1
U3
U2
U4
U1 U2
A B
Remote controller
Outdoor unit
Indoor unit
U3 U4
U1 U2
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1 U2
A B
Central control
device
U1 U2
A B
Mini-SMMS
S-MMS
(Super modular multi system)
U3 U4
U1 U2
U5 U6
U1 U2
A B
Remote controllerRemote controller
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2
U5 U6
L1
L5
L6
L6
L7
L7
L4
L2 L3
Header
unit
Follower
unit
Table-1
Table-2
Table-3
Table-1
AB AB AB AB AB AB
(A, B)
No.8No.7No.4No.3No.2
Indoor unit No.1
Remote
controller
Table-2 Control wiring between outdoor
units (L5) (S-MMS)
Group Control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller
4
ELECTRIC WIRING
24
Design of control wiring
Connect each wire for controlling as shown below.
Size
Name Qty
Up to 500m Up to 1000m 1000 to 2000m
Specification
Control wiring
(indoor-indoor / indoor-outdoor / outdoor-
indoor control wiring, central control wiring)
2 cores 1.25mm² 2.0mm² Shield wire
Remote controller wiring 2 cores 0.5 to 2.0mm²—
Wire specification, quantity, size of crossover wiring and remote controller wiring
1. The crossover wiring and central control wiring use 2-core non-polarity transmission wires. Use 2-core shield
wires to prevent noise trouble. In this case, close (connect) the end of shield wires, and perform the functional
grounding for the end of the shield wires which are connected to both indoor and outdoor units.
For the shield wires which are connected between the central remote controller and the
outdoor unit, perform the functional grounding at only one end of central control wiring.
2. Use 2-core and non-polarity wire for remote controller. (A, B terminals)
Use 2-core and non-polarity wire for wiring of group control. (A, B terminals)
Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor unit)
U2U1
For control
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
Relay
connector
(Open)
(Open)
To other
refrigerant
system
Relay connector
(At shipment from factory : No connection)
Control wiring between indoor and outdoor units
Control wiring between indoor units
Indoor control
P.C. board
CN82
Central remote controller (Option)
U1
U3
U2
U4
Shield earth screw
Control wiring between indoor
and outdoor units
Cable clamp
U3 U4U2U1
U2U1 U2U1 U2U1 U2U1
PMV Kit
(Option)
[Outdoor unit]
[Indoor unit]
25
n Example of system wiring design
Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor unit)
Relay connector (As shipment from factory : No connection)
Communication wiring between indoor and outdoor units
Communication wiring between indoor units
Indoor control
P.C. board
Remote controller
[Group control]
CN82
U2U1 A B
U2U1 U3 U4LN
U3 U4
U1 U2
LN
NL
BA
PMV Kit
(Option)
[Indoor unit]
[Outdoor unit]
Earth
Earth
Earth
Central remote controller power supply
1N~ 50Hz, 220 240V
1N~ 60Hz, 220V
Outdoor unit
Indoor unit
Remote controller
Central remote controller (Option)
Over current breaker (Fuse) switch
Earth leakage breaker
Main switch
Pull box
PMV Kit (Option)
Outdoor power supply
MCY-MAP###HT series : 1N~ 50Hz, 220 240V
MCY-MAP###HT2D series : 1N~ 60Hz, 220V
8
3
2
1
4
1
2
3
4
5
6
7
8
9
U2U1 A B
NL
BA
Earth
8
3
2
U2U1 A B
NL
BA
Earth
8
3
2
U2U1 A B
NL
Earth
2
67
9
6
5
(Option)
4
ELECTRIC WIRING
CAUTION
1. Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together.
2. When running power supplies and control wires parallel to each other, run them through separate conduits or
maintain a suitable distance between them.
(Current capacity of power wires: 10A or less for 300mm, 50A or less for 500mm)
26
5
INSTALLATION OF OUTDOOR UNIT
When using the outdoor unit under the following conditions, it is necessary to set up DIP switch on the outdoor unit
interface P.C. board.
CAUTION
When anyone of the following condition is applied, set up DIP switch.
1. When using PMV Kit in the Mini-SMMS system
2. When using the indoor unit under high humidity condition
[Reference]
Indoor side: 27°C dry bulb temperature
24°C wet bulb temperature
Operation time 4 hours or more.
Setup method
Turn on DIP switch [SW08] on the interface P.C. board of the outdoor unit.
SW11
1
ON
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
Outdoor unit interface P.C. board
Switch [SW08]
27
6
ADDRESS SETUP
In this air conditioner, it is necessary to set up the indoor address before starting the operation. Set
up the address in the following procedure.
CAUTION
1. Set up the address after the wiring work has been completed.
2. Be sure to turn on the power in order of indoor unit outdoor unit. If turning on the power in the reverse
order, a check code [E19] is displayed. When a check code is displayed, turn on the power again.
3. It requires a maximum of 10 minutes (Usually, approx. 5 minutes) to automatically set-up an address for 1
system.
4. To set up an address automatically, the set-up of the outdoor unit needs to be completed.
(Address setup cannot be performed by power-ON only.)
5. To set up an address, the air conditioner does not need to be in operation.
6. Manual address setup is also available besides automatic setup.
Automatic address : Setup from SW15 on the interface P.C. board of the outdoor unit
Manual address : Setup from the wired remote controller
* It is temporarily necessary to set-up the indoor unit as a 1:1 using a wired remote controller.
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control : To the address setup procedure 2
(However, go to the procedure 1 when the central control is performed in a single refrigerant system.)
(Example)
Address setup procedure
Wire systematic diagram
In case of central control in a single refrigerant system
To procedure 1
In case of central control over refrigerant system
To procedure 2
Outdoor
Indoor Indoor
Remote
controller
Remote
controller
Central remote
controller
Outdoor
Indoor Indoor
Remote
controller
Central remote
controller
Outdoor
Indoor Indoor
Remote
controller
Remote
controller
Outdoor
Indoor Indoor
Remote
controller
Central remote
controller
Address setup procedure 1
Turn on power of indoor/outdoor units.
(In order of indoor
Outdoor)
After approx. 1 minute, check that U. 1. L08 (U. 1. flash)
is displayed in 7-segment display section on the interface
P.C. board of the outdoor unit.
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 Auto 2 Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to
U. 1. - - - (U. 1. light) , the setup finished.
When perform a central control, connect a relay
connector between [U1U2] of the outdoor unit and
[U3U4] terminals.
28
Outdoor
IndoorIndoor
Remote
controller
Outdoor
Indoor Indoor
(Example)
Wire
systematic
diagram
Group control over
multiple refrigerant system
Address setup procedure 2
Using SW13 and 14 on the interface P.C. board on the outdoor
unit in each system, set up the system address for each system.
(At shipment the address is set to 1 from the factory)
Note) Be careful not to duplicate with any other refrigerant systems
or other line (system) addresses.
Line (System) address switch on outdoor interface P.C. board (
¡
: Switch ON, × : Switch OFF)
: Is not used for setup of line address. (Do not change setup.)
Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all outdoor units to which
the central control is connected. (At shipment from factory: No connection of connector)
Line
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SW13 SW14
12341234
×××××
×
¡
×××
××
¡
××
×
¡¡
××
×××
¡
×
×
¡
×
¡
×
××
¡¡
×
×
¡¡¡
×
××××
¡
×
¡
××
¡
××
¡
×
¡
×
¡¡
×
¡
×××
¡¡
×
¡
×
¡¡
Line
address
15
16
17
18
19
20
21
22
23
24
25
26
27
28
SW13 SW14
12341234
××
¡¡¡
×
¡¡¡¡
¡
××××
¡¡
×××
¡
×
¡
××
¡¡¡
××
¡
××
¡
×
¡¡
×
¡
×
¡
×
¡¡
×
¡¡¡¡
×
¡
×××
¡
¡¡
××
¡
¡
×
¡
×
¡
¡¡¡
×
¡
2
U2U1
For control
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
Relay connector
Turn on power of indoor/outdoor.
(In order of indoor
outdoor)
After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board.
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 Auto 2 Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup
finished.
Procedure
to
are repeated in other refrigerant systems.
REQUIREMENT
When a group control is performed over multiple
refrigerant systems, be sure to turn on the power
supplies to all of the indoor units connected , so that
the address set-up can be completed correctly.
If turning on the power for each refrigerant system
to set up the addresses, a header indoor unit must
be set for each system. Therefore, an alarm code
L03 (Duplicated header indoor units) will be
displayed during in operation after the address
setup has been completed. In this case, change the
group address using the wired remote controller so
that only one header indoor unit is set-up.
29
When address setup has finished in all the systems, turn
off SW30-2 on the interface P.C. boards of the lines
connected to the identical central control except a line
with least line address number.
(Terminator resistors of the wires in the central control
line of indoor/outdoor are unified.)
Connect the relay connector between [U1U2] and [U3U4]
terminals of the outdoor unit for each refrigerant line.
Then set up the central control address.
(For the central control address setup, refer to the Instal-
lation manual of the central control devices.)
Interface P.C. board
SW11
1
ON
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
SW30
SW30
1
ON
2
SW04
SW01
1
SW05 SW15
D600 D601 D602 D603 D604
1 1
SW02 SW03
SW15
7-segment
display
Switch setup
(Example in case of central control over refrigerant system)
Outdoor side (Manual setup)
* Manual setup is necessary for column of which letter color is reversed.
CAUTION
For relay connector
Never connect a relay connector until address setup for all the refrigerant systems finishes;
otherwise address cannot be correctly set up.
U3 U4
U1 U2
U1 U2
A B
Outdoor unit
Individual
Central
remote controller
Group
Remote
controller
U1 U2
A B
Remote
controller
U1 U2
A B
Outdoor unit
Remote
controller
U1 U2
A B
U1 U2
A B
Outdoor unit
Remote
controller
Relay
connector
U3 U4 U3 U4
U1 U2
Relay
connector
U3 U4
U1 U2
Relay
connector
Line address
Indoor unit address
Group address
Indoor side
(Automatic setup)
Outdoor interface
P.C. board
Setup at shipment
from factory
SW13, 14
(Line address)
Relay connector
Outdoor unit Outdoor unit
Open
OFF after
address setup
Short after
address setup
Short after
address setup
ON
1
ON
12
Outdoor unit
OFF after
address setup
Short after
address setup
3
SW30-2
Terminator resistor of
indoor/outdoor communi
cation line/central control
communication line
1
1
0
1
2
0
2
1
1
2
2
2
3
1
0
6
ADDRESS SETUP
30
Line 1
Header Follower
Indoor
Outdoor
Line address 1
Indoor address 1
Group address 1
Line 2
Remote
controller
1
2
2
1
3
2
2
1
2
2
2
2
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor electric wiring work and unpracticed outdoor
electric wiring work (Manual setup from wired remote controller)
Arrange indoor unit in which address is
set up and the wired remote controller to 1 : 1.
(Wiring example in 2 lines)
Turn on the power.
1
Push simultaneously
SET
+
CL
+
TES
T
buttons for
4 seconds or more.
LCD changes to flashing.
2
Using the setup temp. / buttons, set
12 to the item code.
3
Using the timer time / buttons, set up
the line address.
(Match it with the line address on the interface P.C.
board of the outdoor unit in the identical refrigerant
system.)
4
Push
SET
button.
(OK when display goes on.)
5
Using the setup temp. / buttons, set
13 to the item code.
6
Using the timer time / buttons, set up
the indoor address.
7
Push
SET
button.
(OK when display goes on.)
8
Using the setup temp. / buttons, set
14 to the item code.
9
Using the timer time / buttons, set
Individual =
0000 , Header unit = 0001 ,
Follower unit =
0002 .
10
Push
SET
button.
(OK when display goes on.)
11
Push
TES
T
button.
Setup operation finished.
(Status returns to normal stop status.)
(Line
address)
(Indoor
address)
(Group address)
In the above example, under condition of
no inter-unit wire of the wired remote
controller, set the address after individual
connecting of the wired remote controller.
Group address
Individual : 0000
Header unit : 0001
Follower unit : 0002
}
In case of group control
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Operation procedure
1 2 3 4 5 6
7 8 9 10 11
End
11
4, 7, 10
2, 5, 8
3, 6, 9
1
Data Item code
31
Note 1)
When setting the line address from the wired remote controller, do not use addresses 29 and 30.
The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check code
[E04] (Indoor/outdoor communication circuit error) will be displayed.
Note 2)
When an address has been manually setup from the wired remote controller and you wish to set up a central control
over the refrigeration system and setup the outdoor unit for each system using the following steps.
Using SW13 and 14 on the interface P.C. board of the header unit in each system, set up the line address for
each system.
Turn off SW30-2 on all other interface P.C. boards on the header outdoor units that are connected to the same
central control, not including the system with the least number of address lines.
(The terminator resistor of the cables in the central control system of indoor/outdoor are unified.)
Connect the relay connector between [U1U2] and [U3U4] of the header outdoor unit for each refrigerant system.
Then set up the central control address.
(For the central control address setup, refer to the Installation manual of the central control devices.)
Confirmation of indoor address and the main unit position on the remote controller
[Confirmation of indoor unit No. and position]
1. When you want to know the indoor address though position of the indoor unit itself can be
recognized;
In case of individual operation (Wired remote controller : Indoor unit = 1 : 1) or group control
[Procedure] (Operation while the air conditioner operates)
1
If it stops, push
ON / OFF
button.
2
Push
UNIT
button.
The unit NO 1-1 is displayed on the LCD. (Disappears after several seconds)
The displayed unit number indicates the line address and indoor address. (If there is other indoor unit connected
to the same remote controller (Group control unit), other unit number is displayed every pushing
UNIT
button.)
Operation procedure
1 2
Operate
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
6
ADDRESS SETUP
32
2. When you want to know position of the indoor unit using the address
To confirm the unit numbers in a group control;
[Procedure] (Operation while the air conditioner stops)
The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan is turned on.
1
Push
VENT
+
TES
T
buttons simultaneously for 4
seconds or more.
Unit No is displayed.
The fans of all the indoor units in a group control are
turned on.
2
Every pushing
UNIT
button, the indoor unit num-
bers in the group control are successively
displayed.
The firstly displayed unit number on number indicates
the address of the header unit.
Only fan of the selected indoor unit is turned on.
3
Push
TES
T
button to finish the procedure.
All the indoor units in group control stop.
To confirm all the unit numbers from an arbitrary wired remote controller;
[Procedure] (Operation while the air conditioner stops)
The indoor unit number and position in the same refrigerant line can be confirmed. An header unit is selected, the
indoor unit numbers in the same refrigerant system are successively displayed, and then its indoor unit fan is
turned on.
1
Push the timer time +
TES
T
buttons simultaneously for 4 seconds or more.
Firstly, the line 1, item code AC (Address Change) is displayed. (Select outdoor unit.)
2
Using
UNIT
and
SWING/FIX
buttons, select the line
address.
3
Using
SET
button, determine the selected line
address.
The indoor address, which is connected to the
refrigerant system of the selected refrigerant system is
displayed and the fan is turned on.
4
Every pushing
UNIT
button, the indoor unit
numbers in the same refrigerant system are suc-
cessively displayed.
Only fan of the selected indoor unit operates.
[To select another line address]
5
Push
CL
button to return to procedure
2
.
The indoor address of another line can be successively
confirmed.
6
Push
TES
T
button to finish the procedure.
Operation procedure
1 2 3
End
End
3
1
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Operation procedure
1 2 3
4
5 6
End
5
6
1
3
2
4
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
33
Change of indoor address from wired remote controller
To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or
group control (When the setup operation with automatic address has finished, this change is available.)
[Procedure] (Operation while air conditioner stops)
1
Push simultaneously
SET
+
CL
+
TES
T
buttons for 4 seconds or more.
(The firstly displayed unit No. indicates the header indoor unit in group control.)
2
In group control, select an indoor unit No. to be changed by
UNIT
button.
(The fan of the selected indoor unit is turned on.)
3
Using the setup temp. / buttons, set 13 to the item code.
4
Using the timer time / buttons, change the displayed setup data to a data which you want to
change.
5
Push
SET
button.
6
Using the
UNIT
button, select the unit No. to be changed at the next time.
Repeat the procedure
4
to
6
and change the indoor address so that it is not duplicated.
7
After the above change, push
UNIT
button to confirm the changed contents.
8
If it is acceptable, push
TES
T
button to finish confirmation.
Operation procedure
1 2 3 4 5 6 7 8
End
3
5
8
1
4
2, 6, 7
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
6
ADDRESS SETUP
34
To change all the indoor addresses from an arbitrary wired remote controller.
(When the setup operation for automatic address has finished, this change is available.)
Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each unit within
the same refrigerant system.
* Change the address in the address check/change mode.
[Procedure] (Operation while air conditioner stops)
1
Push the timer time +
TES
T
buttons simultaneously for 4 seconds or more.
Firstly, the line 1, item code AC (Address Change) is displayed.
2
Using
UNIT
/
SWING/FIX
buttons, select the line address.
3
Push
SET
button.
The indoor address, which is connected to the refrigerant system of the selected header unit is displayed and
the fan is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
4
The indoor address of the setup data moves up/down by the timer time / buttons.
Change the setup data to a new address.
5
Push
SET
button to determine the setup data.
6
Every pushing
UNIT
button, the indoor unit numbers in the same refrigerant line are successively
displayed. Only fan of the selected indoor unit operates.
Repeat the procedure
4
to
6
and change all the indoor addresses so that they are not duplicated.
7
Push
SET
button.
(All the displays on LCD go on.)
8
Push
TES
T
button to finish the procedure.
Operation procedure
1 2 3 4 5 6 7 8
End
4
8
3
1
5, 7
To finish the set
2
6
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Deletion of line selection
Here, if the unit No. is not called up, the
header unit in this system does not exist.
Push
CL
button, and then select a line
according to procedure
2
.
35
Clearance of address (Return to status (Address undecided) at shipment from factory)
Method 1
An address is individually cleared from a wired remote controller.
0099 is set up to line address, indoor address, and group address data from the wired remote controller.
(For the setup procedure, refer to the above-mentioned address setup from the wired remote controller.)
Method 2
Clear the indoor addresses in the same refrigerant system from the outdoor unit.
1. Turn off the power of the refrigerant system to be returned to the status at shipment from factory, and change the
outdoor unit to the following status.
1) Remove the relay connector between [U1U2] and [U3U4].
(If it has been already removed, leave it as it is.)
2) Turn on SW30-2 on the interface P.C. board of the outdoor unit if it is ON.
(If it has been already ON, leave it as it is.)
2. Turn on the indoor/outdoor power of which address is to be cleared. After approx. 1 minute, check that
U.1. - - - is displayed, and then execute the following operation on the interface P.C. board of the outdoor unit of
which address is to be cleared in the refrigerant system.
3. After A.d. c.L. has been displayed on 7-degment display, return SW01/SW02/SW03 to 1/1/1.
4. When the address clearing has correctly finished, U.1.L08 is displayed on 7-degment display after a while.
If A.d. n.G. is displayed on 7-degment display, there is a possibility which is connected with the other
refrigerant system. Check again the relay connector between [U1U2] and [U3U4] terminals.
Note) Be careful that the other refrigerant system address may be also cleared if clearing operation is not
correctly executed.
5. After clearing of the address, set up an address again.
SW01 SW02 SW03
212
222
SW04
After checking that A.d.buS is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
After checking that A.d.nEt is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
Address which can be cleared
Line + Indoor + Group address
Central address
U3 U4
U1 U2
U1 U2
A B
Outdoor unit
Remote
controller
U1 U2
A B
Remote
controller
U3 U4
U1 U2
U1 U2
A B
Remote
controller
U1 U2
A B
U3 U4
U1 U2
U1
U3
U2
U4
U1 U2
A B
Remote
controller
Center unit Center unit
Outdoor unit Outdoor unit
Central control
device
Unit of which address is to be returned to the initial status
6
ADDRESS SETUP
36
7
TEST OPERATION
Before test operation
Check valve of the refrigerant pipe of the outdoor unit is OPEN”.
Using 500V-megger, check there is 1M or more between
the terminal block of the power supply and the earth.
If the value is below 1M, do not operate the air conditioner.
How to perform a test operation
In case of test operation on the wired remote controller
Check the operation of the air conditioner in usual operation by the wired remote controller.
For the procedure of the operation, refer to the attached Owners Manual.
For a case of using a wireless remote controller, refer to the Installation Manual of the indoor unit.
A forced test operation is available in the following procedure under condition that the thermostat-OFF in the room.
In a forced test operation, the test operation is cleared after operation for 60 minutes and then returns to the usual
operation in order to prevent a serial operation.
Note) Do not use the forced test operation for cases
other than the test operation because it applies
an excessive load to the air conditioner.
In case of wired remote controller
WARNING
In order to protect the
compressor, keep the power ON
for a period of 12 hours or more
before starting the air conditioner.
Procedure
1
2
3
4
5
Operation
When pushing
TES
T
button for 4 seconds or more, [TEST] is displayed
on the display part and the mode changes to test operation mode.
([TEST] is displayed on the display part during test operation.)
Push
ON / OFF
button.
Using
MODE
button, change the operation mode to [COOL] or [HEAT].
Do not drive the air conditioner with a mode other than [COOL] or [HEAT].
The temperature cannot be adjusted during test operation.
An error is detected as usual.
After the test operation has finished, push
ON / OFF
button to stop the operation.
(Display is same to that in procedure
1
.)
Push
TES
T
button to clear the test operation mode.
([TEST] in the display part disappears and the status changes to the
usual stop status.)
1, 5
3
2, 4
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
TEST
37
In case of test operation on the interface P.C. board of the outdoor unit
This air conditioner has a function which executes a test operation by operation of the switches on the interface P.C.
board of the outdoor unit.
This function is classified into Individual test operation which performs a test operation individually in each indoor
unit and Collective test operation which performs a test operation for all the connected indoor units.
[Individual test operation]
[Collective test operation]
Start
operation
Stop
operation
Procedure
1
2
3
1
Operation
Set operation mode on wired remote controller of the indoor
unit which is operated with test mode to [COOL] or [HEAT].
(When it is not set up, operate the air conditioner with the
current operation mode.)
Set the rotary switch SW01 on the interface P.C. board of the
outdoor unit to [16], and match SW02 and SW03 to the
address of the indoor unit to be operated with test mode.
Push SW04 for 10 seconds or more.
Operation mode changes to the operation mode of wired
remote controller of the corresponding indoor unit.
Temperature cannot be adjusted during Test operation”.
Error is detected as usual.
Test operation is not performed 3 minutes after power was
turned on or operation has stopped.
Return the rotary switches on the interface P.C. board of the
outdoor unit, SW01 = [1], SW02 = [1], SW03 = [1].
7-segment display
[A]
[U1]
[A]
[ ]
Address display of the
corresponding indoor unit
[A]
[ ]
Address display of the
corresponding indoor unit
[A]
[U1]
[B]
[ ]
[B]
[ ]
[B]
[ ]
[FF] is displayed
for 5 seconds.
[B]
[ ]
Start
operation
Stop
operation
Procedure
1
2
1
Operation
Set the rotary switches of interface P.C. board of the outdoor unit;
All cooling operation: SW01 = [2], SW02 = [5], SW03 = [1]
All heating operation: SW01 = [2], SW02 = [6], SW03 = [1]
Push SW04 for 2 seconds or more.
Temperature cannot be adjusted during Test operation”.
Error is detected as usual.
Test operation is not performed 3 minutes after power was turned on
or operation has stopped.
Return the rotary switches on the interface P.C. board of the outdoor
unit, SW01 = [1], SW02 = [1], SW03 = [1].
7-segment display
[A]
[C ]
[H ]
[A]
[C ]
[H ]
[A]
[U1]
[B]
[ ]
[ ]
[B]
[ C ]
[ H ]
[B]
[ ]
Interface P.C. board
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
SW02
1
SW01
1
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
Push switchPush switch
7-segment
display [B]
7-segment
display [A]
Rotary switch
SW02
1
SW01
1
7
TEST OPERATION
38
8
TROUBLESHOOTING
In addition to the check code on the remote controller of the indoor unit, a trouble of the outdoor unit can be
diagnosed by 7-segment display of the control P.C. board of the outdoor unit. Make good use of this function for
various checks. After check, return each bit of Dip switch to OFF position.
n Segment display and check code
Rotary switch setup value
SW01 SW02 SW03
111
Displayed contents
Check code of outdoor unit
LED
A
B
Outdoor unit No. (U1 only)
Check code display
However, when there is an auxiliary code, the check code (for 3 seconds) and the auxiliary code (for 1 second)
are alternately displayed.
Check Code (Outdoor 7-segment display [B])
Displayed when SW01: 1, SW02: 1, SW03: 1
Check code
Outdoor 7-segment display
E06
E07
E08
E12
E15
E16
E19
E20
E31
F04
F06
F07
F08
F12
F13
F15
F16
F23
F24
F31
Auxiliary code
Number of indoor unit which received normally
——
Duplicated indoor addresses
01: Communication between indoor and outdoor
02: Communication between outdoor units
——
00: Capacity over 01~: No. of connected units
00: Header is nothing
02: Two or more header units
01: Other system outdoor connected
02: Other system indoor connected
IPDU quantity information
——
——
——
——
01: TS1 sensor error
01: Compressor 1
——
——
——
——
——
Check code name
Decrease of number of indoor units
Indoor/Outdoor communication circuit error
Duplication of indoor addresses
Automatic address start error
Indoor is nothing during automatic addressing
Capacity over / Number of connected indoor units
Number of header outdoor units error
Other refrigerant system connected during
automatic addressing
IPDU communication error
TD1 sensor error
TE1 sensor error
TL sensor error
TO sensor error
TS1 sensor error
TH sensor error
Outdoor temp. sensor miswiring (TE, TL)
Outdoor pressure sensor miswiring (Pd, Ps)
Ps sensor error
Pd sensor error
Outdoor EEPROM error
D600
AB
D601 D602 D603 D604
39
Check code
Outdoor 7-segment display
H01
H02
H03
H04
H06
L04
L06
L08
L10
L18
L29
L30
L31
P03
P04
P07
P10
P13
P15
P19
P20
P22
P26
P29
Auxiliary code
01: Compressor 1
01: Compressor 1
01: Compressor 1
——
——
——
Number of indoor units with priority
——
——
Detected indoor address
IPDU quantity information
Detected indoor address
——
——
01: Compressor 1
01: Compressor 1
Detected indoor address
——
01: TS condition 02: TD condition
Detected outdoor unit number
——
A : Fan motor circuit error
d : Fan motor lock
01: Compressor 1
01: Compressor 1
Check code name
Compressor breakdown
Magnet switch error
Overcurrent relay operation
Compressor trouble (Lock)
Current detective circuit system error
Compressor 1 case thermo operation
Low-pressure protective operation
Outdoor line address duplicated
Duplication of indoor units with priority
Indoor group/Address unset
Outdoor capacity unset
Flow selector unit error
IPDU quantity error
External interlock of indoor unit
Extended I/C error
Discharge temp TD1 error
High-pressure SW system operation
Heat sink overheat error
Indoor overflow error
Outdoor liquid back detection error
Gas leak detection
4-way valve inverse error
High-pressure protective operation
Outdoor fan IPDU error
IGBT short protection error
Compressor position detective circuit system error
8
TROUBLESHOOTING
79
ZUBEHÖR
r Zubehör
SICHERHEITSHINWEISE
Bevor Sie mit der Installation beginnen, lesen Sie die diese „Sicherheitshinweise“ sorgfältig und
installieren Sie das Produkt entsprechend.
Diese “Sicherheitshinweise” sind wichtig für Ihre persönliche Sicherheit.
Achten Sie darauf, dass Sie alle Anweisungen befolgen. In der folgenden Tabelle finden Sie den
Vorgang und die entsprechende Beschreibung.
n Erklärung der Symbole
WARNUNG
Weist auf eine mögliche gefährliche Situation hin, die zum Tod oder zu schweren Verletzungen führen kann.
VORSICHT
Weist auf eine Situation hin, die zur Verletzung (1) oder Sachschäden (2) durch falsche Handhabung führen kann.
1 : “Verletzung” bedeutet, Schmerzen, Verbrennungen, Stromschlag usw., die keinen längeren Krankenhausaufenthalt
zur Folge haben.
2 : “Sachschäden” bedeutet Schäden am Haus, Gegenstände des Haushalts usw.
Führen Sie nach der Installation einen Testlauf durch, um das System auf mögliche Fehler zu
prüfen. Erklären Sie dem Kunden anhand der Betriebsanleitung, wie das Gerät bedient und
gewartet wird.
n Die Außeneinheit benötigt für ein Mini-SMMS-System zusätzlichen die folgenden
Elemente. (Inneneinheit, Fernbedienung, Y-Abzweig oder Verteiler.)
Diese Elemente müssen entsprechend der Systemleistung ausgewählt werden.
MCY-
Teilebezeichnung
Installations-Handbuch
Betriebsanleitung
Muffenverbindungen
Schutzhülse
Schutzkanal
Drainage-Nippel
Wasserdichte
Gummikappe
Anzahl
Typ 0401 Typ 0501 Typ 0601
222
111
—— 1
111
111
111
111
Form
Verwendung
(Händigen Sie es dem Kunden aus)
(Händigen Sie es dem Kunden aus)
Gasseitige Auslassleitung (Ø15.9 bis Ø19.1)
Kabeltülle
Durchbruchschutz
80
WARNUNG
Zur Installation und Wartung des Klimagerätes wenden Sie sich an einen autorisierten Händler
oder einen qualifizierten Installateur.
Durch eine nicht fachgerechte Installation kann es zu Wasserschäden, Stromschlägen oder sogar zu Bränden kommen.
Verwenden Sie ausschließlich Werkzeuge und Rohrleitungen für R410A und führen Sie die
Installation anhand des Handbuchs aus.
Der Druck des benutzten HFC R410A Kältemittels liegt um das 1.6 fache höher als der eines herkömmlichen
ltemittels. Daher können bei falschen Rohrmaterialien oder nicht korrekter Installation Leitungsbruch,
Verletzungen, Wasserschäden, Stromschlag oder ein Brand verursacht werden.
Wenn Sie Geräte in einem kleinen Raum installieren, treffen Sie Vorkehrungen, damit bei
ltemittellecks die zulässige Konzentration nicht überschritten wird.
Fragen Hierzu beantwortet Ihnen Ihr Händler. Sollte die Menge austretenden Kältemittels den Grenzwert
überschreiten, kann es zu Sauerstoffmangel kommen.
Der Installationsort muss so gewählt werden, dass er sicher vor extremen Umwelteinflüssen, wie
Erdbeben oder Wirbelstürme, ist.
Wird dies nicht beachtet, kann sich das Gerät bewegen und Unfälle verursachen.
Falls Sie in einem erdbebengefährdeten Gebiet leben oder mit einer hohen Windlast rechnen
ssen, achten Sie bei der Installation auf eine entsprechende Auslegung der Befestigung.
Wurde das Klimagerät von Ihnen nicht fachgerecht installiert, kann das Gerät herunterfallen und einen Unfall
verursachen.
Belüften Sie den Raum sofort, wenn während der Installationsarbeiten Kältemittel austreten
sollte.
Kommen Kältemitteldämpfe in Kontakt mit Feuer, können sich gesundheitsschädliche Gase bilden.
Vergewissern Sie sich daher nach der Installation noch einmal, das kein Kältemittel austreten
kann.
Treten Kältemitteldämpfe aus und gelangen in einen Raum mit einem Herd oder Ofen, kann es bei einer offenen
Flamme zur Bildung von gesundheitsschädlichen Gasen kommen.
Versuchen Sie nicht Kältemittel in der Außeneinheit zurück zu gewinnen.
Verwenden Sie bei Neuinstallationen oder Reparaturen das Kältemittel nur mit dafür geeigneten Geräten zurück.
ckgewinnung in der Außeneinheit ist nicht möglich. Hierbei kann es zu schweren Unfällen kommen.
Die im Installationshandbuch beschriebenen Elektroarbeiten müssen von einem ausgebildeten
Elektriker ausgeführt werden. Stellen Sie sicher, dass das Klimagerät einen eigenen Stromkreis
hat.
Eine nicht ausreichende Leistung der Stromversorgung oder eine nicht fachgerechte Installation kann zu einem
Brand führen.
Achten Sie bei der Verkabelung darauf, dass alle Kontakte der Klemmenleisten fest angezogen
sind.
Prüfen Sie die Erdung des Systems.
Bei einer schlechten Erdung kann es zu einem Stromschlag kommen.
Ist das System nicht geerdet, kann dies zu einem Stromschlag führen.
VORSICHT
Das Gerät darf nicht dort installiert werden, wo brennbare Gase frei werden.
Wenn sich brennbare Gase um das Gerät ansammeln, kann dies einen Brand verursachen.
Stellen Sie sicher, dass die Außeneinheit fest montiert ist, damit sie sich nicht bewegen kann.
Stellen Sie sicher, dass eine Erdschluss-Sicherung installiert ist. Es besteht sonst die Gefahr
eines Stromschlags.
Ziehen Sie die Bördelmuttern wie angegeben mit einem Drehmomentschlüssel an.
Wird die Bördelmutter zu stark angezogen, kann sie beschädigt werden und Kältemittel kann austreten.
DEUTSCH
81
1
INSTALLATION VON KLIMAGERÄTEN MIT MODERNEN KÄLTEMITTELN
Dieses Klimagerät arbeitet mit dem neuen HFC Kältemittel R410A. Dieses Kältemittel greift die
Ozonschicht nicht an.
Das R410A Kältemittel ist anfällig gegen Verunreinigungen wie Wasser, oxydierte Membrane und Öle, da der Druck
des R410A Kältemittels etwa 1.6 mal so hoch wie der der älteren Kältemittels ist. Gleichzeitig mit dem Einsatz des
neuen Kältemittels, wurde auch das bisher verwendete Kühlmaschinenöl gewechselt. Stellen Sie daher sicher, dass
bei den Installationsarbeiten kein Wasser oder Staub und kein altes Kältemittel oder Kühlmaschinenöl in den
hlkreislauf mit dem neuen Kältemittel gelangen kann.
Um zu verhindern, das Kältemittel und Kühlmaschinenöl gemischt werden können, wurden, verglichen mit Systemen,
die mit konventionellen Kältemitteln arbeiten, die Größe der Anschlüsse zur Befüllung der Haupteinheit geändert und
komplett neue Installationswerkzeuge konzipiert, so dass eine Verwechslung ausgeschlossen werden kann. Folglich
sind Spezialwerkzeuge - wie unten beschrieben - für das neue Kältemittel (R410A) erforderlich.
Um zu verhindern, dass Wasser und Staub in das Rohrsystem eindringt, verwenden Sie für die Anschlussleitungen
ausschließlich neue, saubere und hochdruckfeste Rohre, die eigens für R410A gefertigt sind.
Erforderliche Werkzeuge und Vorsichtsmaßnahmen
r die Installation ist es erforderlich die Werkzeuge und Teile wie nachfolgend beschrieben vorzubereiten.
Die neuen Werkzeuge und Teile der folgenden sind ausschließlich auf die Verwendung mit R410A beschränkt.
Erklärung der Symbole
l
: Neue Teile (Verwenden Sie diese Teile nur für R410A und trennen Sie sie von Teilen für R22 oder R407C.)
¡ : Alte Werkzeuge vorhanden
Verwendete Teile
Mehrwegmanometer
llschlauch
llzylinder
Gasleck-Prüfgerät
Vakuumpumpe
Vakuumpumpe mit Adapter für
ckschlagventil
rdelwerkzeug
Biegegerät
ltemittelauffangeinheit
Drehmomentschlüssel
Rohrschneider
ltemittelflasche
Schweißgerät/Stickstoffgasflache
Vorschaltgerät zur Kältemittelbefüllung
Anwendung
Entlüften oder Befüllung des
ltemittels und
Funktionsprüfung
ltemittelbefüllung
Prüfen auf Gaslecks
Entlüften
Entlüften
Aufbördeln der Rohre
Biegen der Rohre
ltemittelrückgewinnung
Anziehen der Bördelmuttern
Rohre schneiden
ltemittelbefüllung
Schweißen von Rohren
ltemittelbefüllung
Einsatzbereich Werkzeuge/Teile
l
neu, exklusiv für R410A
l
neu, exklusiv für R410A
Nicht verwenden (Verwenden Sie vorschaltgerät
zur Kältemittelbefüllung)
l
neu
Einsetzbar, wenn Rückschlagventil
angeschlossen ist
¡
: R22 (vorhandenes Gerät)
¡
: verwendbar, Größe anpassen
¡
: R22 (vorhandenes Gerät)
l
exklusiv für R410A
l
Neues Werkzeug, ausschließlich für
Ø12.7 mm und Ø15.9 mm
¡
: R22 (vorhandenes Gerät)
l
exklusiv für R410A
ID : Kältemittelname aufgedruckt
¡
: R22 (vorhandenes Gerät)
¡
: R22 (vorhandenes Gerät)
82
2
AUSWAHL DES AUFSTELLUNGSORTES
WARNUNG
Das Klimagerät muss an einer Stelle installiert werden, die das Gewicht aufnehmen kann und an
der keine negativen Umwelteinflüsse auf das Gerät einwirken.
Wird dies nicht beachtet, kann dies zu einer Beschädigung des Geräts oder zu Verletzungen führen.
VORSICHT
Das Gerät darf nicht dort installiert werden, wo brennbare Gase frei werden.
Wenn sich brennbare Gase um das Gerät ansammeln, kann dies einen Brand verursachen.
Stellen Sie sicher, dass die Außeneinheit fest montiert ist, damit sie sich nicht bewegen kann.
Sprechen Sie mit Ihrem Kunden einen Installationsort ab, der den folgenden Anforderungen
gerecht wird:
Ein Platz, an dem das Gerät waagerecht ausgerichtet werden kann.
Ein Platz, an dem genügend Platz für Wartungsarbeiten ist.
Ein Platz, an dem aus dem Gerät laufendes Wasser nicht zu Problemen führt.
Sorgen Sie entsprechend der örtlichen Vorschriften für eine elektrische Isolierung zwischen
Metallteilen des Gebäudes und Metallteilen des Geräts.
Vermeiden Sie es, das Gerät an den folgenden Stellen zu installieren:
Eine Stelle, an der es mit sehr salzhaltiger Luft (in Strandnähe) oder mit großen Mengen schwefelhaltiger Dämpfe
(heiße Quellen) in Kontakt kommt. (Soll das Gerät in einem solchen Bereich eingesetzt werden, müssen
zusätzliche Schutzmaßnahmen vorgesehen werden.)
Eine Stelle, an der es mit Öl, Wasserdampf, Öldämpfen oder korrosiven Gasen in Kontakt kommt.
Eine Stelle, in deren Nähe organische Lösungsmittel benutzt werden.
Eine Stelle, die in der Nähe von Maschinen liegt, die hohe Frequenzen erzeugen.
Eine Stelle, an der die Abluft direkt in das Fenster eines benachbarten Hauses geblasen wird. (bei der
Außeneinheit)
Eine Stelle, an der die Geräusche der Außeneinheit leicht übertragen werden. (Wenn Sie ein Klimagerät direkt an
der Grenze zu Ihrem Nachbarn installieren, achten Sie unbedingt auf den Geräuschpegel.)
Eine Stelle mit schlechter Lüftung. (Prüfen Sie, speziell bei Zwischendeckengeräten, ehe Sie die Luftkanäle
verlegen, ob die Luftmenge, der statische Druck und der Reibungswiderstand des Kanals in Ordnung sind.)
Geräte
Entsprechend HP
Leistung Außeneinheit
hlleistung (kW)
Heizleistung (kW)
Inverter-Einheit
Typ 0401 Typ 0501 Typ 0601
4 HP 5 HP 6 HP
12.1 14.0 15.5
12.5 16.0 18.0
Erscheinungsbild
83
Platzbedarf
Achten Sie darauf, dass genügend Platz für die
Installation und Wartung des Systems vorhanden ist.
Installationsort
Ein Platz, der genügend Raum um das Außengerät läßt.
Ein Platz, an dem das Betriebsgeräusch und die Abluft
Ihre Nachbarn nicht belästigen.
Ein Platz, der keinem starken Wind ausgesetzt ist.
Ein Platz, der keinen Durchgang blockiert.
Wenn das Außengerät in erhöhter Lage installiert
werden soll, achten Sie darauf die Standbeine zu
sichern.
Achten Sie auf genügend Platz für den Transport der
Einheit.
Ein Ort, an dem das ablaufende Kondenswasser keine
Probleme verursacht.
VORSICHT
1. Installieren Sie die Außeneinheit so, dass die
Abluft nicht blockiert wird.
2. Wenn das Außengerät an einem Platz installiert
ist, der ständig starkem Wind ausgesetzt ist, wie
zum Beispiel an einer Küste oder in einem
hochgelegenen Stockwerk eines Gebäudes,
schützen Sie den Ventilator durch einen
Luftkanal oder einen Windschutz.
3. Wenn das Außengerät an einem Platz installiert
ist, der ständig starkem Wind ausgesetzt ist, wie
zum Beispiel in einem hochgelegenen Stockwerk
eines Gebäudes oder auf dem Dach, schützen
Sie es durch folgende Maßnahmen.
1) Installieren Sie die Einheit so,
dass die Abluftöffnung
zum Gebäude zeigt.
Halten Sie einen Abstand
von 500 mm oder mehr
zum Gebäude.
2) Installieren Sie die Außeneinheit in einem
Winkel von 90° zu der Hauptwindrichtung.
500
4. Die Installation an folgenden Plätzen könnte
Probleme verursachen.
Installieren Sie das Gerät nicht an folgenden Orten:
Ein Platz voll mit Maschinenöl.
Ein Platz voller Schwefelgase.
Ein Platz, an dem Hochfrequenzwellen erzeugt
werden, wie beispielsweise durch
Audioanlagen, Schweißgeräte oder
medizinische Apparate.
Zur Installation benötigter Platz
Hindernis auf der Rückseite
[Oberseite frei]
1. Einzelgerät
2. Hindernis auf rechter und linker Seite
3. Zwei oder mehr Einheiten in Reihe geschaltet
[Hindernis auf der Oberseite]
Hindernis auf der Vorderseite
[Oberseite frei]
1. Einzelgerät
2. Zwei oder mehr Einheiten in Reihe geschaltet
Starker
Wind
Starker
Wind
150
oder größer
150
oder größer
300
oder größer
200
oder größer
Die Höhe des
Hindernisses muß
kleiner sein als die
he der Außeneinheit.
150
oder größer
300
oder größer
300
oder größer
300
oder größer
200 oder größer
Die Höhe des Hindernisses muß
kleiner sein als die Höhe der Außeneinheit.
500
oder größer
150
oder größer
500
oder größer
1000
oder größer
2
AUSWAHL DES AUFSTELLUNGSORTES
84
[Hindernis auf der Oberseite]
Hindernisse auf der Vorder- und Rückseite
Öffnen Sie die Oberseite sowie die rechte und die linke
Seite.
Die Höhe des Hindernisses an Vorder- und Rückseite
muß kleiner sein als die Höhe der Außeneinheit.
[Standardinstallation]
1. Einzelgerät
2. Zwei oder mehr Einheiten in Reihe geschaltet
Reiheninstallation - Vorder- und
ckseiten zeigen zueinander
Öffnen Sie die Oberseite sowie die rechte und die linke
Seite.
Die Höhe des Hindernisses an Vorder- und Rückseite
muß kleiner sein als die Höhe der Außeneinheit.
[Standardinstallation]
Installation der Außeneinheit
Prüfen Sie vor der Installation die Stabilität und die
Ebenheit des Installationsortes, um eine übermäßige
Geräuschentwicklung zu vermeiden.
Befestigen Sie entsprechend der nachfolgenden
Zeichnung die Basis fest mit Ankerbolzen.
(Ankerbolzen, Muttern M10 × 4 Paare)
Der Bolzen darf maximal 15 mm überstehen.
Erfolgt der Wasserablauf über einen Schlauch,
installieren Sie den Drainage-Nippel und die
Wasserdichte Gummikappe und verwenden Sie einen
Schlauch (Innendurchmesser 16 mm), wie er überall
erhältlich ist. Dichten Sie die Schrauben mit Silikon ab,
damit sich kein Kondenswasser bilden und herab
tropfen kann.
Unter bestimmten Bedingungen kann sich an diesen
Stellen Kondenswasser bilden.
Wird das Gerät in einer Gegend installiert, in der Frost
und Schneefall auftreten, beachten Sie dies bei der
Installation des Wasserablaufs. Das Wasser läuft
leichter a, wenn auch die perforierten Öffnungen an
der Bodenplatte heraus gebrochen werden.
(Benutzen Sie hierzu einen Schraubenzieher o.ä.)
1000
oder größer
1000
oder größe
r
1000
oder größer
150
oder größe
r
300
oder größer
300
oder größer
1000
oder größer
200
oder größer
1000
oder größer
300
oder größer
1500
oder größer
2000
oder größer
200
oder größer
600150 150
430
365
40
400
Ablauföffnung
Perforierte
Öffnung
Befestigungsbohrung
Drainage-Nippel
15 mm
oder weniger
Drainage-Nippel Wasserdichte Gummikappe
Perforierte Öffnung
Wasserdichte Gummikappe
Öffnen
Drainage-Nippel
85
hlmittel-Rohrleitungsanschluss
VORSICHT
BEACHTEN SIE BEI DER VERLEGUNG DER
ROHRLEITUNGEN IMMER DIE FOLGENDEN
4 WICHTIGE PUNKTE:
1. Entfernen Sie Staub und Feuchtigkeit aus den
Rohranschlüssen
2. Achten Sie auf dichte Verbindungen zwischen
Rohren und Gerät
3. Entlüften Sie die Rohrleitungen mit einer
VAKUUMPUMPE.
4. Überprüfen Sie die Anschlusspunkte auf
Gaslecks
Als Beispiel
Wenn bei Außentemperaturen unter dem Gefrierpunkt
bei 0°C oder darunter kontinuierlich über längere Zeit der
Heizbetrieb ausgeführt wird, kann das Ablassen des
Abtauwassers durch das Gefrieren der Bodenplatte unter
Umständen nicht möglich sein, wodurch Probleme am
Gehäuse oder Ventilator verursacht werden können.
r die sichere Installation des Klimageräts wird die
bauseitige Bereitstellung einer Frostschutzheizung
empfohlen.
Wenden Sie sich für nähere Informationen hierzu an
Ihren Fachhändler.
Ausbrechen der Leitungsdurchführung
Vorgehensweise
Die Rohrleitungen für Raum- und Außeneinheit können
auf 4 Seiten angeschlossen werden.
Brechen Sie den Deckel der Leitungsdurchführung in
der Basisplatte da heraus, wo Sie die Leitung
anbringen wollen.
Entfernen Sie, wie in der Zeichnung dargestellt, nicht
den gesamten Deckel, da dann das Loch leichter
herausgebrochen werden kann. Die Öffnungen können
leicht mit Hilfe eines Schraubenziehers heraus
gebrochen werden, indem Sie gegen die untere
Verbindung schlagen.
Nachdem Sie die Öffnung heraus gebrochen haben,
entfernen Sie den Grat und montieren Sie die
Schutztülle, um Kabel und Leitungen zu schützen.
Nachdem die Leitungen angeschlossen sind, montieren
Sie die Abdeckung. Sie läßt sich leicht montieren, wenn
Sie den Schlitz im unteren Teil abtrennen.
Entfernen der Frontplatte
1. Entfernen Sie die Verschraubung der Frontplatte.
2. Ziehen Sie die Frontplatte nach unten.
Nachdem Sie die Frontplatte entfernt haben, erscheint
vorn die Elektroinstallation.
Die Kupferrohre können an den Durchführungen
befestigt werden.
Sollte der Durchmesser von Rohrleitungen und Kabeln
nicht der Öffnung entsprechen, arbeiten Sie die
Öffnung nach.
Binden Sie die Kabel der Außen- und Raumeinheit und
das Netzkabel mit Isolierband zusammen. Achten Sie
darauf, dass sie nicht mit Kompressor und
hlmittelleitung in Kontakt kommen können. (Der
Kompressor und die Kühlmittel-Versorgungsleitung
nnen sehr heiß werden.)
Zur Zugentlastung der Anschlüsse befestigen Sie die
Kabel mit Kabelklemmen des Schaltkastens und an
der Ventilplatte.
Vorn
Hinten
Anschlußdeckel
Richtung
Unten
Kabelklemme
Schaltkasten Frontplatte
Anschlussplatte
2
AUSWAHL DES AUFSTELLUNGSORTES
86
3
KÄLTEMITTELLEITUNGEN
WARNUNG
Belüften Sie den Raum sofort, wenn während
der Installationsarbeiten Kältemittel austreten
sollte.
Kommen Kältemitteldämpfe in Kontakt mit Feuer,
nnen sich gesundheitsschädliche Gase bilden.
Vergewissern Sie sich daher nach der
Installation noch einmal, dass kein Kältemittel
austreten kann.
Tritt Kältemittel aus und kommt mit heißen Geräten
wie Heizlüfter, Herde oder Küchengeräte in Kontakt,
nnen sich gesundheitsschädliche Gase bilden.
Biegen und Positionieren
rdeln
1. Trennen Sie das Rohr mit einem Rohrschneider.
FALSCHOK
90˚
Unregelmäßig Rau Verbogen
A
B
2. Führen Sie eine Bördelmutter in das Rohr ein und
rdeln sie es damit auf.
Da die Größe des Bördelanschlusses für R410A von
der für R22 abweicht, verwenden Sie falls eben
glich die speziell für R410A hergestellten
rdelwerkzeuge.
Sie können trotzdem die herkömmlichen Werkzeuge
benutzen. In diesem Fall müssen Sie jedoch die
rdelhöhe des Kupferrohres entsprechend
einstellen.
rdeldurchmesser:
A (Maßeinheit: mm)
* Wenn Sie Leitungen für R410A mit einem
herkömmlichen Bördelwerkzeug aufbördeln, ziehen
Sie es etwa 0.5 mm weiter heraus als bei R22, um so
die erforderliche Größe der Bördelverbindung zu
erreichen.
Die Kupferrohrlehre hilft Ihnen, die erforderliche Größe
der Aufbördelung richtig einzustellen.
rdelhöhe:
B (Einheit: mm)
Starr (Kupplung)
Englisch (flügelmutterartig)
Außendurchmesser
des Kupferrohrs
9.5
15.9
R410A
A
13.2
19.7
R22
13.0
19.4
+0
0.4
Außendurchmesser
des Kupferrohrs
Spezielles
R410A Werkzeug
Herkömmliches
Werkzeug
Außendurchmesser
des Kupferrohrs
R410A
9.5
15.9
1.5 bis 2.0
2.0 bis 2.5
1.0 bis 1.5
1.5 bis 2.0
R22
9.5
15.9
R410A
0 bis 0.5
0 bis 0.5
(wie links)
(wie links)
R22 R410A
1.0 bis 1.5
1.0 bis 1.5
R22
0.5 bis 1.0
0.5 bis 1.0
87
Anziehen der Verbindungen
(Maßeinheit: Nm)
Richten Sie die Rohre mittig zueinander aus und
ziehen Sie die Bördelmutter so weit es geht mit den
Fingern fest. Danach ziehen Sie die Mutter, wie
abgebildet, mit einem Schraubenschlüssel und einem
Drehmomentschlüssel an.
Arbeiten Sie, wie in der Abbildung dargestellt, beim
sen oder Festziehen der gasseitigen Bördelmutter
des Ventils mit zwei Schraubenschlüsseln. Mit nur
einem Schlüssel kann die Mutter nicht fest genug
angezogen werden.
Verwenden Sie aber für den gleichen Vorgang auf der
Flüssigkeitsseite nur einen Schraubenschlüssel.
VORAUSSETZUNG
1. Setzen Sie den Schraubenschlüssel nicht an der
Ventilkappe an. Das Ventil kann beschädigt
werden.
2. Wenden Sie zuviel Kraft an, kann die Mutter
brechen.
Prüfen Sie nach der Installation die Verbindungen mit
Stickstoff auf Leckstellen.
Der Druck in einem R410A System liegt um etwa das
1.6-fache höher als bei R22 Systemen. Ziehen Sie
daher die gebördelten Rohrverbindung, die Raum- und
Außeneinheit miteinander verbindet, mit Hilfe eines
Drehmomentschlüssels bis zum angegebenen
Drehmoment fest. Durch fehlerhafte Verbindungen
kann Gas austreten oder es kann zu Störungen des
hlkreislaufs kommen.
Bringen Sie niemals Kühlmaschinenöl auf
die Oberfläche der Bördelverbindung.
Ventil auf Gasseite
Außendurchmesser
des Kupferrohrs
Drehmoment
9.5 mm (Durchmesser)
15.9 mm (Durchmesser)
33 bis 42 (3.3 bis 4.2 kgfm)
68 bis 82 (6.8 bis 8.2 kgfm)
Halbkoppelstück
Bördelmutter
Seite mit
Außengewinde
Seite mit
Innengewinde
Festziehen mit einem
Schraubenschlüssel
Festziehen mit einem
Drehmomentschlüssel.
Deckel
Kappe
Sperrventil
Festziehen
Bördelmutter
Lösen
Deckel
FALSCH
3
LTEMITTELLEITUNGEN
88
Rohrleitungsanschluss am gasseitigen Ventil
Leistung
Außeneinheit
Typ 0401
Typ 0501
Typ 0601
Gasseitiger
Rohrleitungsdurchmesser
Ø15.9
Ø19.1
Rohrleitungsanschluss am gasseitigen Ventil
Schließen Sie die Ø15. 9 Rohrleitung mit einer Bördelverbindung an.
Beachten Sie beim Verlöten der Ø19.1 gasseitigen Leitung die
folgenden Hinweise:
1. Biegen Sie das Rohr so, dass das Ende in Richtung des
Leitungsverlaufs aus der Außeneinheit ragt.
Die gasseitigen Rohrleitungen Ø15.9 sind Bauseits beizustellen.
2. Verlöten Sie außerhalb der Außeneinheit mit Hilfe einer
Muffenverbindung (Zubehör) die gasseitige Rohrleitung mit Ø15.9
mit der Rohrleitung mit Ø19.1.
3. Isolieren Sie die gasseitige Leitung nach dem Verlöten bis zum
Ventil mit einer Wärmeisolierung.
Bördelverbindung
Gasseitige
Rohrleitung Ø 15.9
(Bauseits beizustellen)
Kugelhahn
Gasseite Ø15.9
Lötverbindung
(Hartlöten)
Gasseitige
Rohrleitung Ø19.1
(Bauseits beizustellen)
Bördelverbindung
Gasseitige Rohrleitung Ø15.9
(Bauseits
beizustellen)
Kugelhahn
Gasseite Ø15.9
Muffenverbindung (Zubehör)
89
Kupplungslänge der Hartgelöteten Leitung
(Maßeinheit: mm)
K
ØC
G
ØF
Auswahl von Rohrleitungsmaterial und Abmessung
Auswahl des Rohrleitungsmaterials
Material: Nahtlose phosphorfreie Kupferleitung
Leistung der Innen- und Außeneinheiten
Für die Inneneinheit wird der Leistungscode anhand des jeweiligen Leistungsbereichs festgelegt.
r die Außeneinheit wird der Leistungscode anhand des jeweiligen Leistungsbereichs festgelegt. Außerdem werden
die maximale Anzahl der anschließbaren Inneneinheiten und die Gesamtleistung der Inneneinheiten festgelegt.
Anschlussbereich
Außenliegender Bereich Interne Länge
Anschlussbereich
Außenliegender Bereich Interne Länge
Standard-Außendurchmesser (Zulässige Differenz)
Min.
Einschublänge
Standard-
Außendurchmesser des
Kupferrohrs
CFKG
Ovalmaß
Min. Dicke der
Kupplung
6.35 6.35 (±0.03) 6.45 (
+0.04
0.02
) 7 6 0.06 oder weniger 0.50
9.52 9.52 (±0.03) 9.62 (
+0.04
0.02
) 8 7 0.08 oder weniger 0.60
12.70 12.70 (±0.03) 12.81 (
+0.04
0.02
) 9 8 0.10 oder weniger 0.70
15.88 15.88 (±0.03) 16.00 (
+0.04
0.02
) 9 8 0.13 oder weniger 0.80
19.05 19.05 (±0.03) 19.19 (
+0.03
0.03
) 11 10 0.15 oder weniger 0.80
Minimale Wandstärke für R410A
Weich Halbhart oder hart AD (Zoll) AD (mm) Minimale Wandstärke (mm)
OK OK 1/4 6.35 0.80
OK OK 3/8 9.52 0.80
OK OK 1/2 12.70 0.80
OK OK 5/8 15.88 1.00
FALSCH * OK 3/4 19.05 1.00
* Verwenden Sie bei einem
Rohrdurchmesser von mindestens Ø19.0
ein entsprechendes Material.
Tabelle 1 Tabelle 2
Leistungscode Leistungscode
Gesamtleistung der
anschließbaren Innengeräte
Leistung
Inneneinheit
Entsprechend HP
Entsprechend
der Leistung
Leistung
Außeneinheit
Entsprechend HP
Anzahl der
anschließbaren
Inneneinheiten
Min. (HP) Max. (HP)
Typ 007 0.8 2.2 Typ 0401 4 6 3.2 5.2
Typ 009 1 2.8 Typ 0501 5 8 4.0 6.5
Typ 012 1.25
3.6
Typ 0601 6 9 4.8 7.8
Typ 015 1.7
4.5
Typ 018 2
5.6
Typ 024 2.5
7.1
Typ 027 3
8
Typ 030 3.2
9
Typ 036 4
11.2
Typ 048 5
14
3
LTEMITTELLEITUNGEN
90
Auswahl der Kältemittelleitung
4
4
4
4
Außeneinheit
1
1. Abzweigung
Hauptrohrleitung
Gasseitige
Rohrleitung
Flüssigkeitsseitige Rohrleitung
Inneneinheit
Abzweigung
Y-Abzweigung
3
3 3 3
2
Abzweigung
Hauptabzweig
2
2
3
3 3
Nr. Rohrleitungsteil Name Auswahl der Rohrleitungsabmessung
Hauptleitungsabmessung
Leistung der Außeneinheit
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Typ 0401 15.9 9.5
Typ 0501 15.9 9.5
Typ 0601 19.1 9.5
Außeneinheit
1. Abzweigung
Hauptrohrleitung
Rohrleitungsabmessung der Abzweigung
Gesamtleistung der Inneneinheiten
nachgeschaltete Seite
Entsprechend HP
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Unter 2.8 12.7 9.5
2.8 bis unter 6.4 15.9 9.5
6.4 bis unter 7.2 19.1 9.5
Abzweigung
Abzweigung
Abzweigung
Hinweis)
Überschreitet die Gesamtleistung der Inneneinheiten die der Außeneinheiten, wählen Sie
eine Leistung, die der der Außeneinheiten entspricht.
Anschlussleitungen Inneneinheit
Kapazität der Inneneinheit
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Typ 007, 009, 012 9.5 6.4
Typ 015, 018 12.7 6.4
Typ 024, 030, 036, 048 15.9 9.5
Abzweigung
Inneneinheit
Verbindun
g
srohr
Inneneinheit
Auswahl des Abzweigs
Gesamtleistung der Inneneinheiten
nachgeschaltete Seite
Entsprechend HP
Modellbezeichnung
Unter 6.4 RBM-BY53E
Y-Abzweigung
Mindestens 6.4 und höchstens 7.8 RBM-BY103E
r 4 Abzweigungen Bis zu 7.8 RBM-HY1043E
Hauptabzweig
r 8 Abzweigungen Bis zu 7.8 RBM-HY1083E
Abzweigung
Y-Abzweigung
Hauptabzweig
Hinweis)
*1 :
*2 :
Wird als erster Abzweig ein Y-Abzweig verwendet, muss dieser anhand der Leistung
der Außeneinheit ausgewählt werden.
An den 1. Kreis nach dem Hauptabzweig können Inneneinheiten mit der
Gesamtleistung 6.0 angeschlossen werden.
91
Auswahl von Kältemittelleitungen für geräuschberuhigte Orte (mit PMV-Kit)
4
4
4
4
1
PMV-Kit
3
5
3 3 3
2
2
2
3
3 3
5 5 5
5 5 5
Außeneinheit
1. Abzweigung
Hauptrohrleitung
Gasseitige
Rohrleitung
Flüssigkeitsseitige Rohrleitung
Inneneinheit
Inneneinheit
Abzweigung
Y-Abzweigung
Abzweigung
Hauptabzweig
Nr. Rohrleitun
g
steil Name Auswahl der Rohrleitungsabmessung
Hauptleitungsabmessung
Leistung der Außeneinheit
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Typ 0401 15.9 9.5
Typ 0501 15.9 9.5
Typ 0601 19.1 9.5
Außeneinheit
1. Abzweigung
Hauptrohrleitun
g
Rohrleitungsabmessung der Abzweigung
Gesamtleistung der Inneneinheiten
nachgeschaltete Seite
Entsprechend HP
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Unter 2.8 12.7 9.5
2.8 bis unter 6.4 15.9 9.5
6.4 bis unter 7.2 19.1 9.5
Abzweigung
Abzweigung
Abzweigung
Hinweis
)
Überschreitet die Gesamtleistung der Inneneinheiten die der Außeneinheiten, wählen Sie
eine Leistung, die der der Außeneinheiten entspricht.
Anschlussleitungen Inneneinheit
Kapazität der Inneneinheit
Gasseitige
Rohrleitung
Flüssi
g
keitsseiti
g
e
Rohrleitung
Typ 007, 009, 012 9.5 6.4
Typ 015, 018 12.7 6.4
Typ 024, 030, 036, 048 15.9 9.5
Abzweigung
Inneneinheit
Verbindun
g
srohr
Inneneinheit
Auswahl des Abzweigs
Gesamtleistung der Inneneinheiten
nachgeschaltete Seite
Entsprechend HP
Modellbezeichnun
g
Unter 6.4 RBM-BY53E
Y-Abzweigung
Mindestens 6.4 und höchstens 7.8 RBM-BY103E
r 4 Abzwei
g
un
g
en Bis zu 7.8 RBM-HY1043E
Hauptabzwei
g
r 8 Abzwei
g
un
g
en Bis zu 7.8 RBM-HY1083E
Abzweigung
Y-Abzweigung
Hauptabzweig
Hinweis
)
*1 :
*2 :
Wird als erster Abzweig ein Y-Abzweig verwendet, muss dieser anhand der Leistung
der Außeneinheit ausgewählt werden.
An den 1. Kreis nach dem Hauptabzweig können Inneneinheiten mit der
Gesamtleistung 6.0 angeschlossen werden.
Auswahl des PMV-Kits
Kapazität der Inneneinheit Modellbezeichnung
Typ 007, 009, 012 RBM-PMV0361E
Typ 015, 018, 024 RBM-PMV0901E
PMV-Kit PMV-Kit
3
LTEMITTELLEITUNGEN
92
Erlaubte Länge/Höhendifferenz der Kältemittelleitung
Außeneinheit
1. Abzweigung
Hauptrohrleitung
L1
Höhendifferenz
zwischen
Außen- und
Inneneinheiten H1
Höhendifferenz
zwischen
Innengeräten H2
Inneneinheit
Länge entspricht der längsten Rohrleitung L
nge entspricht der längsten Rohrleitung nach der 1. Abzweigung Li
L4
ef
g
Y-Abzweigung
Abzweigleitung L2
Hauptabzweig
Abzweigleitung
L3
abcd
A
1
Zulässiger
Wert
Rohrleitungsauswahl
Gesamte Rohrleitungslänge
(flüssigkeitsseitige Rohrleitung, effektive Länge)
180 m L1 + L2 + L3 + L4 + a + b + c + d + e + f + g
Effektive Länge 100 m
ngste Rohrleitung
nge L (
1)
Entsprechende Länge 125 m
L1 + L3 + L4 + g
Maximale Länge der Hauptleitung 65 m L1
Gleiche Länge der größten Rohrleitungslänge
vom 1. Abzweig Li (
1)
35 m L3 + L4 + g
Rohrleitungslänge
Maximale effektive Länge der
Verbindungsleitung zwischen Inneneinheiten
15 m a, b, c, d, e, f. g
Obere Außeneinheit 30 m ———
hendifferenz
zwischen Außen- und
Inneneinheiten H1
Untere Außeneinheit 20 m ———
hendifferenz
he zwischen Inneneinheiten H2 15 m ———
1 : Weiteste Inneneinheit vom ersten Abzweig mit der Bezeichnung “A”.
93
Erlaubte Länge/Höhendifferenz von Kältemittelleitungen für geräuschberuhigte Orte (mit PMV-Kit)
Höhendifferenz
zwischen
Innen- und PMV-Kit
H2
* Zwischen höchster
und niedrigster Einheit
Beispiel)
L4
e
f
lm
n
g
ab
hi jk
cd
PMV-Kit
H2
H2
H2
A
1
Außeneinheit
1. Abzweigung
Hauptrohrleitung
L1
Höhendifferenz
zwischen
Außen- und
Inneneinheiten
H1
Inneneinheit
nge entspricht der längsten Rohrleitung L
nge entspricht der längsten Rohrleitung nach der 1. Abzweigung Li
Y-Abzweigung
Abzweigleitung L2
Hauptabzweig
Abzweigleitung
L3
PMV-Kit
PMV-Kit
FALSCH OK
Inneneinheit Inneneinheit
Hinweis)
Schließen Sie nie mehr als eine Inneneinheit an ein PMV-Kit an. Inneneinheiten und PMV-Kits müssen immer im
Verhältnis 1 zu 1 installiert werden.
Zulässiger
Wert
Rohrleitungsauswahl
Gesamte Rohrleitungslänge
(flüssigkeitsseitige Rohrleitung, effektive Länge)
150 m
L1 + L2 + L3 + L4
+ a + b + c + d + e + f + g + h + I + j + k+ l + m + n
Effektive Länge 65 m
ngste Rohrleitung
nge L (
1)
Entsprechende Länge 80 m
L1 + L3 + L4 + g + n
Maximale Länge der Hauptleitung 50 m L1
Gleiche Länge der größten Rohrleitungslänge
vom 1. Abzweig Li (
1)
15 m L3 + L4 + g + n
Maximale effektive Länge der
Verbindungsleitung zwischen Inneneinheiten
15 m a + h, b + i, c + j, d + k, e + l, f + m. g + n
Rohrleitungslänge
Gemessene Länge zwischen PMV-KIT und
Inneneinheit
Ab 2 m aber
unter 10 m
h, i, j, k, l, m, n
Obere Außeneinheit 30 m ———
hendifferenz
zwischen Außen- und
Inneneinheiten H1
Untere Außeneinheit 20 m ———
hendifferenz
he zwischen Innen- und PMV-Kit H2 15 m ———
1 : Weiteste Inneneinheit vom ersten Abzweig mit der Bezeichnung “A”.
3
LTEMITTELLEITUNGEN
94
Dichtetest
Nach dem Verlegen der Kältemittelleitungen wird ein Dichtetest durchgeführt. Schließen Sie hierzu wie in der Abbildung
dargestellt eine Stickstoffflasche an und setzen Sie das Leitungssystem unter Druck.
hren Sie den Druck über die Anschlüsse der Kompaktventile (oder Kugelhähne) auf der Flüssigkeitsseite, der
Gasauslass-Seite und der Gasansaugseite zu.
Der Dichtetest kann nur über die Anschlüsse der Flüssigkeitsseite, der Gasauslass-Seite und der Gasansaugseite der
Außeneinheit erfolgen.
Schließen Sie die Ventile der Flüssigkeitsseite, der Gasauslass- und der Ansaugseite ganz. Da die Möglichkeit
besteht, dass Stickstoff in den Kühlkreislauf gelangt, ziehen Sie die Ventilstangen noch einmal fest, ehe Sie die
Stickstoffflasche öffnen.
(Ein Festziehen ist auf der Gasauslass-Seite nicht erforderlich, da es sich hier um Kugelhähne handelt.)
Erhöhen Sie den Druck für jede Kältemittelleitung der Flüssigkeitsseite, der Heißgasauslass-Seite und der
Ansaugseite langsam und schrittweise.
Stellen Sie sicher, dass Flüssigkeitsseite, Gassauslass- und auch die Gasansaugleitung getestet
werden.
VORAUSSETZUNG
Verwenden Sie für den Dichtetest nie Sauerstoff, brennbare oder schädliche Gase”.
SCHRITT 1: Legen Sie für mindestens 3 Minuten einen Druck von
0.3 MPa (3,0 kg/cm² G) an.
SCHRITT 2: Legen Sie für mindestens 3 Minuten einen Druck von
1.5 MPa (15 kg/cm² G) an.
SCHRITT 3: Legen Sie für etwa 24 Stunden einen Druck von
3.73 MPa (38 kg/cm² G) an.
Prüfen Sie, ob ein Druckabfall entsteht.
Kein Druckabfall: In Ordnung Druckabfall: Prüfen Sie, wo sich die Leckstelle befindet.
Ergibt sich jedoch eine innerhalb der 24 Stunden eine Änderung der Umgebungstemperatur, kann ich der
Druck um etwa 0101 Mpa (0.1 kg/cm² G) pro 1° C ändern. Korrigieren Sie den Druck dann entsprechend.
Prüfen auf Gaslecks
Wenn in den Schritten 1, 2 oder 3 ein Druckabfall festgestellt wird, prüfen Sie die Verbindungsstellen. Prüfen Sie mit
Ihrem Gehör, mit einem Fühler oder mit einem Schaumbildner und verlöten Sie die Stelle oder ziehen Sie die Bördelung
fest an.
Große Leckstellen sind erkennbar.
Kleine Leckstellen sind erkennbar.
VL VH
Anschluss an Innengeräte
Kompaktventil voll geschlossen
(Gasansaugseite)
Außeneinheit
Niederdruckanzeige
Hochdruckanzeige
Mehrweg
manometer
Hartlötverbindung
Anschluss
Ø6.4
Kupferrohr
Ø6.4
Kupferrohr
Voll
geschlossen
Reduzierventil
Stickstoff
Kompaktventil voll
geschlossen
(Flüssigkeitsseite
Anschluss
Hauptrohrleitung
97
Öffnen der Ventile
•Öffnen Sie die Ventile der Außeneinheit ganz.
•Öffnen Sie die Ventilstangen auf der Flüssigkeitsseite
mit einem 4 mm Sechskantschlüssel ganz.
•Öffnen Sie die Ventilstange des Kompaktventils auf
der Ansaugseite mit einem Schraubenschlüssel.
•Öffnen Sie den Hebel des Kugelhahns auf der
Gasseite mit einer Zange.
Achten Sie darauf, dass Sie Kugelhahn und
Kompaktventil auf unterschiedliche Weise öffnen
ssen.
Wie wird das Ventil geöffnet
Vorsichtsmaßnahmen bei
der Bedienung des Ventils
•Öffnen Sie den Ventilschaft oder den Hebel bis
zum Anschlag. Versuchen Sie das Ventil nicht mit
Gewalt weiter zu öffnen.
Ziehen Sie den Deckel des Ventils fest an.
Anzugsdrehmoment der Kappe
Position der Kerben für den Schraubendreher
*1. Stößt der Schraubendreher an den Anschlag,
nachdem das Ventil voll geöffnet ist, drehen Sie
nicht mit Kraft weiter, da sonst Schäden entstehen
nnen. (5 Nm überstehen)
rmeisolierung der Rohrleitungen
Versehen Sie die flüssigkeits-, ansaug- und
auslassseitigen Rohrleitungen jeweils mit einer
rmeisolierung.
Verwenden Sie Isoliermaterial, das für Temperaturen
von 120° C und mehr ausgelegt ist.
VORSICHT
Nachdem die Rohrleitungen angeschlossen
wurden, verkleiden Sie die Öffnung in der Platte
mit einer Rohrummantelung oder füllen Sie sie mit
Silikon oder Kitt.
Wurden die Rohrleitungen nach unten oder zur
Seite verlegt, schließen Sie die entsprechenden
Öffnungen in der Grundplatte oder in dem
Seitenteil.
Sind die Öffnungen nicht geschlossen kann
eindringendes Wasser oder Staub Fehler
verursachen.
Ventileinheit
Füllanschluss:
Drehen Sie den
Schlitzschraubendreher
um 90˚ nach links, bis der
Anschlag erreicht ist.
(ganz geöffnet)
Bördelmutter
Kerben für
Schraubendreher
Ganz geschlossen Ganz geöffnet
33 bis 42Nm (3.3 bis 4.2kgfm)
20 bis 25Nm (2.0 bis 2.5kgfm)
14 bis 18Nm (1.4 bis 1.8kgfm)
Ventilgröße:
Ø9.5
Ø15.9
Anschluss:
3
LTEMITTELLEITUNGEN
98
4
ELEKTRISCHE VERDRAHTUNG
WARNUNG
Die im Installationshandbuch beschriebenen Elektroarbeiten müssen von einem ausgebildeten
Elektriker ausgeführt werden.
Stellen Sie sicher, dass das Klimagerät einen eigenen Stromkreis hat.
Eine nicht ausreichende Leistung der Stromversorgung oder eine nicht fachgerechte Installation kann zu einem
Brand führen.
Achten Sie bei der Verkabelung darauf, dass alle Kontakte der Klemmenleisten fest angezogen sind.
Prüfen Sie, ob das Gerät korrekt geerdet ist.
Ist das System nicht geerdet, kann dies zu einem Stromschlag führen.
VORSICHT
Für die Stromversorgung der Außeneinheit muss eine Sicherung installiert werden.
Wird die Verkabelung nicht fachgerecht ausgeführt, kann dies zu einem Kabelbrand führen.
Die Außeneinheit muss an einen eigenen Stromkreis angeschlossen werden.
Stellen Sie sicher, dass eine Erdschluss-Sicherung installiert ist.
Es besteht sonst die Gefahr eines Stromschlags.
Trennen des Geräts von der Hauptstromversorgung
Das Gerät muss über eine Sicherung oder einen Schalter, dessen Anschlüsse einen Mindestabstand von 3 mm haben, an
die Hauptstromversorgung angeschlossen werden.
VORAUSSETZUNG
Beachten Sie beim Anschluss der Stromversorgung immer die lokalen Vorschriften.
Zum Anschluss der Versorgungsleitungen der Außeneinheiten, befolgen Sie die Anweisungen des Handbuchs,
das der Außeneinheit beiliegt.
Schließen Sie niemals die Kabel der Netzstromversorgung an die Anschlüsse (U1, U2, U3, U4) an.
(Hierdurch kann es zu einer Fehlfunktion kommen.)
Verlegen Sie die Elektroleitungen so, dass sie nicht mit heißen Rohren in Kontakt kommen. Hierdurch kann die
Isolierung schmelzen und einen Unfall verursachen.
Sichern Sie die Kabel, nachdem Sie sie an die Klemmenleisten angeschlossen haben mit Kabelklemmen.
Verlegen Sie Kühlmittelleitung und Steuerleitung zusammen.
Schalten Sie die Inneneinheit erst dann ein, wenn Sie alle Kühlmittelleitungen entlüftet haben.
Details zu den Stromversorgungskabeln der Inneneinheit und der Verbindung zwischen Innen- und Außeneinheit
finden Sie im Installationshandbuch der Inneneinheit.
Anschluss der Stromversorgung und der Steuerungsverdrahtung
Führen Sie die Stromversorgung und die
Steuerungsverkabelung nachdem Sie die Ausbrüche in der
Platte auf der Vorderseite der Außeneinheit geöffnet haben,
durch die jeweiligen Öffnungen.
Die Durchbrüche für die Rohrleitungen und die
Kabeldurchführung befinden sich auf der Frontseite, dem
Seitenteil und auch auf der Rückseite.
Hinweis)
Achten Sie darauf, dass Stromversorgung und Steuerungskabel getrennt verlegt werden.
Verlegen Sie die Stromversorgung und die Steuerungskabel so, dass Sie keinen Kontakt zum Boden der Außeneinheit
haben.
In der Invertereinheit befindet sich eine Klemmleiste (Klemmen U3, U4) für optionale Teile wie beispielsweise “Zentrale
Fernbedienung”. Achten Sie darauf, dass Sie die Kabel nicht versehentlich falsch anschließen.
Kabeldurchführung
r Steuerungskabel und
Durchbruch für Rohrleitung
Kabeldurchführung der
Stromversorgung
99
Spezifikation der Stromversorgung
hlen Sie Stromversorgungskabel und Sicherung für jede Außeneinheit aus der folgenden Spezifikation:
Installieren Sie eine Erdschluss-Sicherung, Beachten Sie dies nicht, kann ein Stromschlag die Folge sein.
r die Stromversorgung der Außeneinheit muss eine Sicherung installiert werden.
Verwenden Sie einen Überstromschütz (Sicherung), die der Aufnahmeleistung des Geräts entspricht.
Beachten Sie dabei die örtlichen Vorschriften für Installation und Kabelquerschnitt.
Kabel 3-adrig, konform zu 60245 IEC 66
Schließen Sie an die Klemmen (L, N) keine Ringleitung an.
Stromversorgung
Serie MCY-MAP###HT
Serie MCY-MAP###HT2D
1N~ 50Hz 220V-240V
1N~ 60Hz 220V
Leistung der
Außeneinheit
Typ 0401
Typ 0501
Typ 0601
Kabelquerschnitt*
6 mm², Max. 28 m
6 mm², Max. 25 m
6 mm², Max. 22 m
Maximale
Stromaufnahme
25A
28A
31A
Absicherung
32A
32A
40A
Abzweigschalter/Überstromsicherung
Außeneinheit
Stromversorgung
Außeneinheit
Erdschluss-Sicherung
Masse
LN
(Klemmenleiste) (Abisolierungslänge Stromversorgungskabel)
(Kabelklemme)
(Schutzhülse: Zubehör)
Netzkabel
NL
10
LN
10
50
90
Masseleitung
Netzkabel
* Konform mit 60245 IEC66
(Anschlussbeispiel)
Anschluss Stromversorgung
n Stromversorgungskabel
Schließen Sie das Netzkabel und das Erdungskabel an die Netzanschlussleiste an.
Ziehen Sie die Schrauben der Klemmenleiste fest und fixieren Sie die Kabel mit der Kabelklemme.
(Achten Sie darauf, dass kein Zug auf die Klemmenleiste wirkt.)
4
ELEKTRISCHE VERDRAHTUNG
100
Stromversorgung Inneneinheit (Außeneinheit hat separate Stromversorgung)
Hinweis)
Spezifikation der Stromversorgungskabel: Kabel 3-adrig 2.5 mm², konform zu 60245 IEC 57
Die Anschlusslängen in der Tabelle beziehen sich auf die Länge vom Anschlusskasten bis zur Außeneinheit, wenn die
Inneneinheiten wie in der nachstehenden Abbildung parallel geschaltet sind. Es wird von einem Spannungsabfall nicht
größer als 2% ausgegangen. Überschreitet die Anschlusslänge die Angaben in der Tabelle, wählen Sie einen
Kabelquerschnitt entsprechend der Richtlinien für die Verdrahtung der Inneneinheiten.
Legen Sie den Kabelquerschnitt für die Inneneinheiten entsprechend der Anzahl der nachgeschalteten Inneneinheiten
fest.
Auswahl des PMV-Kits
Details zum PMV-Kit finden Sie im Installationshandbuch.
[Inneneinheit]
NL
Masse
NL
Masse
NL
Masse
NL
Masse
Erdschluss-Sicherung
Inneneinheit
Anschlusskabel
Übergangskabel
(MMK-AP∗∗∗2H (Wandmodell) benötigt kein Übergangskabel.)
Steuerungs-Leiterplatte Inneneinheit
Pulsmoduliertes Ventil (Inneneinheit)
Stecker CN82
Anschlusskasten
Hauptschalter
Stromversorgung
Raumeinheit
1N~ 50Hz, 220 – 240V
1N~ 60Hz, 220V
PMV
PMV-Kit
Netzstromkabel
Einheit
Modell
Kabelquerschnitt
Alle Inneneinheiten-Modelle 2.0 mm² Max. 20 m 3.5 mm² Max. 50 m
101
Steuerungsverdrahtung
1. Verwenden Sie für die Verdrahtung der Steuerung 2-adriges Kabel ohne Polarität.
2. Verwenden Sie zur Unterdrückung von Störungen in folgenden Fällen abgeschirmtes Kabel.
Innen - Innen/Regelung Außen - Innen/Zentrale Fernbedienung
Tabelle -1
Steuerungsverkabelung zwischen Innen- und
Außeneinheit (L1, L2, L3), Zentrale
Fernbedienung (L4)
Tabelle -2
Steuerungsverkabelung zwischen
Außeneinheiten (L5) (S-MMS)
Hinweis *1 : Gesamtlänge der Steuerungsverdrahtung für alle Kühlkreise ( L1 + L2 + L3 + L4 )
Tabelle -3
Verkabelung der Fernbedienung (L6, L7)
Gruppensteuerung über Fernbedienung
Gruppensteuerung von mehreren Inneneinheiten (8 Einheiten) über eine einzelne Fernbedienung
U3 U4
U1 U2
U1
U3
U2
U4
U1 U2
A B
Fernbedienung
Außeneinheit
Inneneinheit
U3 U4
U1 U2
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1 U2
A B
Zentrale
Steuerung
U1 U2
A B
Mini-SMMS
S-MMS
(Super-Modulares Multi-System)
U3 U4
U1 U2
U5 U6
U1 U2
A B
FernbedienungFernbedienung
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2
U5 U6
L1
L5
L6
L6
L7
L7
L4
L2 L3
Haupteinheit Untereinheit
Tabelle-1
Tabelle-2
Tabelle-3
Tabelle-1
AB AB AB AB AB AB
(A.B)
Inneneinheit
8
Inneneinheit
7
Inneneinheit
4
Inneneinheit
3
Inneneinheit
2
Inneneinheit
1
Fernbedienung
Verkabelung
Typ
Querschnitt
nge
1
2-adrig keine Polarität
Kabelabschirmung
1.25 mm² bis zu 1000 m
2.0 mm² bis zu 2000 m
Verkabelung
Typ
Querschnitt
nge
2-adrig keine Polarität
Kabelabschirmung
1.25 mm² bis 2.0 mm²
Bis zu 100 m (L5)
Kabel
Größe
nge
2-adrig
0.5 mm² bis 2.0 mm²
Bis zu 500 m (L6 + L7)
Bei Infrarot-Fernbedienung in Gruppensteuerung bis zu 400 m
Gesamtlänge für die Verbindung zwischen Inneneinheiten (L6) bis zu 200 m
4
ELEKTRISCHE VERDRAHTUNG
102
Steuerungsverdrahtung
Schließen Sie alle Steuerungskabel wie unten dargestellt an.
nge
Bezeichnung Anzahl
bis zu 500 m bis zu 1000 m bis zu 2000 m
Spezifikation
Geräteverbindungskabel
(Innen - Innen/Innen - Außen/Regelung
Außen - Innen/Zentrale Fernbedienung)
2-polig 1.25 mm² 2.0 mm² Kabelabschirmung
Verkabelung der Fernbedienung 2-polig 0.5 bis 2.0 mm²—
Kabelabschirmung muss angeschlossen werden
(Anschluss an alle entsprechenden Klemmen der Inneneinheiten)
U2U1
Steuerungsverdrahtung
zwischen Innen- und
Außeneinheit
U3 U4
Verkabelung
der zentralen
Steuerung
Relais
(Offen)
(Offen)
Zu anderem
System
Relais-Anschluss
(Werkseinstellung: kein Anschluss)
Steuerungsverkabelung
zwischen Innen- und Außeneinheiten
Steuerungsverkabelung
zwischen Inneneinheiten
Steuerungs-Leiterplatte
Inneneinheit
CN82
Zentrale Fernbedienung (Option)
U1
U3
U2
U4
Masseschraube
Steuerungsverkabelung zwischen
Innen- und Außeneinheiten
Kabelklemme
U3 U4U2U1
U2U1 U2U1 U2U1 U2U1
PMV-Kit
(Option)
[Außeneinheit]
[Inneneinheit]
Kabelspezifikation, Anzahl, Querschnitt der Geräteverbindungen und Fernbedienungsverkabelung
1. Für die Geräteverbindung und die zentrale Fernbedienung wird ein 2-adriges Kabel ohne Polarität benötigt.
Um Störungen zu vermeiden, verwenden Sie 2-adriges, abgeschirmtes Kabel. Für die Erdung des Systems verbinden
Sie die Kabelabschirmungen und schließen Sie die Abschirmungen, die an Innen- und Außeneinheit angeschlossen
sind, an der Erdung an.. Die abgeschirmten Kabel, die die zentrale Fernbedienung und die Außeneinheit verbinden,
werden nur an einem Ende geerdet.
2. Verwenden Sie für die Fernbedienung 2-adriges Kabel ohne Polarität. (Anschlüsse A, B)
Verwenden Sie für die Verdrahtung der Gruppenregelung 2-adriges Kabel ohne Polarität. (Anschlüsse A, B)
105
6
ADRESS-EINSTELLUNG
Bevor der betrieb gestartet werden kann, müssen die Inneneinheiten eingerichtet werden.
Richten Sie die Adressen wie folgt ein.
VORSICHT
1. Richten Sie die Adressen nach der Verdrahtung ein.
2. Schalten Sie zuerst die Innen- und dann die Außeneinheit ein. Beachten Sie diese Reihenfolge nicht, wird der
Fehler [E19] ausgegeben. Schalten Sie in dem Fall die Stromversorgung neu ein.
3. Es dauert maximal 10 Minuten (normalerweise etwa 5 Minuten) bis die Adresse des ersten Kreises automatisch
eingerichtet ist.
4. Zur automatischen Einstellung einer Adresse, muss auch die Außeneinheit eingeschaltet sein.
(Die Adressen kann nicht eingerichtet werden, wenn nur das Gerät eingeschaltet ist.)
5. Um eine Adresse einzurichten, muss das Klimagerät nicht arbeiten.
6. Neben der automatischen Einrichtung ist auch eine manuelle Einrichtung der Adresse möglich.
Automatische Adressierung : Einrichten über SW15 auf der Schnittstellen-Leiterplatte der Außeneinheit
Manuelle Adressierung : Einrichtung erfolgt über die Kabel-Fernbedienung
* Es ist vorübergehend erforderlich Inneneinheit und Kabelfernbedienung 1 : 1 einzustellen. 1.
(In Gruppensteuerung und wenn keine Fernbedienung vorhanden ist)
Automatische Adress-Einstellung
Ohne zentrale Fernbedienung : Weiter mit Vorgehensweise 1
Mit zentraler Fernbedienung : Weiter mit Vorgehensweise 2
(Fahren Sie mit Schritt 1 fort, wenn nur 1 Kühlkreis mit einer zentralen Fernbedienung eingerichtet werden soll.)
(Beispiel)
Adress-Einstellung
Verkabelungsdiagramm
Zentrale Fernbedienung mit einem Kühlkreis
zu Vorgehensweise 1
Zentrale Fernbedienung mit mehreren Kühlkreisen
zu Vorgehensweise 2
Vorgehensweise 1
Schalten Sie die Stromversorgung für die Innen-/Außeneinheiten
ein. (Reihenfolge Inneneinheit
Außeneinheit)
Prüfen Sie nach 1 Minute ob auf der 7-Segment-Anzeige der
Schnittstellen-Leiterplatte der Außeneinheit
U. 1. L08 (U. 1. blinkend) angezeigt wird.
Drücken Sie SW15, um die automatische Adressierung zu
starten.
(Max. 10 Minuten für 1 Kreis (normalerweise etwa 5 Minuten))
Wenn der Zähler Auto 1
Auto 2
Auto 3 auf der 7-
Segmentanzeige angezeigt wird, und die Darstellung von
U. 1. - - - (U. 1. blinkend) nach
U. 1. - - - (U. 1. konstant) wechselt, ist die Einrichtung beendet.
Wenn Sie mit einer zentralen Steuerung arbeiten, schließen Sie
zwischen den Kontakten [U1 U2] und [U3 U4] der Außeneinheit
ein Relais an.
Außeneinheit
Inneneinheit Inneneinheit
Fernbedienung
Fernbedienung
Fernbedienung
Fernbedienung
Zentrale
Fernbedienung
Außeneinheit
Inneneinheit Inneneinheit
Zentrale
Fernbedienung
Außeneinheit
Inneneinheit Inneneinheit
Außeneinheit
Inneneinheit Inneneinheit
Zentrale
Fernbedienung
106
(
¡
: Schalter ON (EIN),
×
: Schalter OFF (AUS))
SW13 SW14 SW13 SW14
hlkreisadresse
12341234
hlkreisadresse
12341234
1
×××××
15
××
¡¡¡
2
×
¡
×××
16
×
¡¡¡¡
3
××
¡
××
17
¡
××××
4
×
¡¡
××
18
¡¡
×××
5
×××
¡
×
19
¡
×
¡
××
6
×
¡
×
¡
×
20
¡¡¡
××
7
××
¡¡
×
21
¡
××
¡
×
8
×
¡¡¡
×
22
¡¡
×
¡
×
9
××××
¡
23
¡
×
¡¡
×
10
×
¡
××
¡
24
¡¡¡¡
×
11
××
¡
×
¡
25
¡
×××
¡
12
×
¡¡
×
¡
26
¡¡
××
¡
13
×××
¡¡
27
¡
×
¡
×
¡
14
×
¡
×
¡¡
28
¡¡¡
×
¡
VORAUSSETZUNG
Wenn die verschiedenen Kühlkreise als Gruppe
gesteuert werden, schalten Sie alle
Inneneinheiten, die zu der Gruppe gehören, ein,
wenn Sie die Adressen einrichten.
Wenn Sie die einzelnen Kühlkreise einschalten,
wird für jeden Kreis eine Haupteinheit
eingerichtet. Daher kann nach der
Adresseinrichtung der Fehler L03 (Doppelte
Hauptinneneinheit) erscheinen. Ändern Sie in
diesem Fall die Gruppenadresse über die
Kabelfernbedienung, damit nur noch eine
Inneneinheit vorhanden ist.
(Beispiel)
Verkabelungsdiagramm
Gruppenkontrolle mit mehreren
hlkreisen
Vorgehensweise 2
Richten Sie mit SW13 und 14 auf der Schnittstellen-Leiterplatte der
Außeneinheit von jedem Kreis die Kreisadresse des Kreises ein..
(Werkseinstellung: Einstellung auf Adresse 1)
Hinweis) Achten Sie darauf, dass keine doppelten Kühlkreise oder
Systemadressen vergeben werden
Kreisadressenschalter auf Schnittstellen-Leiterplatte der Außeneinheit
: Wird für die Kreisadresse nicht verwendet (Einstellung nicht ändern.)
Prüfen Sie ob das Relais zwischen den Anschlüssen [U1 U2] und [U3 U4] für die Außeneinheiten, die an die zentrale
Steuerung angeschlossen sind, geschaltet ist. (Werkseinstellung: keine Anschlüsse)
Schalten Sie die Stromversorgung für die Innen-/Außeneinheiten ein. (Reihenfolge Inneneinheit
Außeneinheit)
Prüfen Sie nach 1 Minute ob auf der 7-Segment-Anzeige der
Schnittstellen-Leiterplatte U. 1. L08 (U. 1. blinkend) angezeigt wird.
Drücken Sie SW15, um die automatische Adressierung zu starten.
(Max. 10 Minuten für 1 Kreis (normalerweise etwa 5 Minuten))
Wenn der Zähler Auto 1
Auto 2
Auto 3 auf der
7-Segmentanzeige angezeigt wird, und die Darstellung von
U. 1. - - - (U. 1. blinkend) nach U. 1. - - - (U. 1. konstant) wechselt, ist
die Einrichtung beendet.
Wiederholen Sie die Schritte
bis
für die anderen Kühlkreise.
Außeneinheit
InneneinheitInneneinheit
Fernbedienung
Außeneinheit
Inneneinheit Inneneinheit
2
U2U1
Steuerungsverdrahtung
zwischen Innen- und
Außeneinheit
U3 U4
Verkabelung
der zentralen
Steuerung
Relais
107
Wenn die Adresseinrichtung für alle Kühlkreise beendet ist,
schalten Sie den Schalter SW30-2 auf den Schnittstellen-
Leiterplatten der Kreise, die zu der gleichen zentralen
Steuerung gehören, mit Ausnahme der letzten Adresse ab.
(Die Abschlusswiderstände aller Kabel der zentralen
Steuerung der Innen-/Außeneinheiten sind einheitlich.)
Schließen Sie zwischen den Kontakten [U1 U2] und [U3 U4]
der Außeneinheit von jedem Kühlkreis ein Relais an.
Richten Sie dann die Adresse der zentralen Steuerung ein.
(Details zur Einrichtung der Adresse für die zentrale
Steuerung finden Sie im Installationshandbuch der zentralen
Steuerung.)
Schaltereinrichtung
(Zentrale Fernbedienung mit mehreren Kühlkreisen)
Außeneinheit (manuelle Einrichtung)
r die Spalten mit unterlegt dargestellten Feldern ist eine manuelle Einrichtung erforderlich.
VORSICHT
Relais
Schließen Sie das Relais erst an, wenn die Adresseinrichtung für alle Kühlkreise beendet ist, da es anderenfalls zu einem
Fehler bei der Adressierung kommt.
SW11
1
ON
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
SW30
SW30
1
ON
2
SW04
SW01
1
SW05 SW15
D600 D601 D602 D603 D604
1 1
SW02 SW03
SW15
7-Segmentanzeige
Schnittstellen-Leiterplatte
U3 U4
U1 U2 U5 U6
Außeneinheit
Außeneinheit
U3 U4
Außeneinheit
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
Kühlkreisadresse
Inneneinheitadresse
Gruppenadresse
Inneneinheit
(automatische Einrichtung)
Zentrale
Fernbedienung
Schnittstellen-
Leiterplatte Haupteinheit
Werkseinstellung
SW13, 14
(Kühlkreisadresse)
Relais
Außeneinheit Außeneinheit
Öffnen
AUS nach
Adresseinrichtung
Nach
Adresseinrichtung
kurzschließen
Nach
Adresseinrichtung
kurzschließen
Nach
Adresseinrichtung
kurzschließen
EIN
1
EIN
12
Außeneinheit
AUS nach
Adresseinrichtung
3
SW30-2
Abschlusswiderstand des
Signal-/Steuerungskabels der
Innen-/Außeneinheit
U1 U2
A B
Individuell
Gruppe
Fernbedienung Fernbedienung Fernbedienung
U1 U2
A B
U1 U2
A B
Fernbedienung
U1 U2
A B
U1 U2
A B
Relais Relais Relais
1
1
0
1
2
0
2
1
1
2
2
2
3
1
0
6
ADRESS-EINSTELLUNG
108
Manuelle Adresseinrichtung über Fernbedienung
Festlegen der Adresse einer Inneneinheit vor Fertigstellung der Verkabelung der Inneneinheiten und noch nicht
getesteter Verkabelung der Außeneinheiten (Manuelle Einstellung über die Kabel-Fernbedienung)
Gleichen Sie die Inneneinheit, deren Adresse festgelegt werden soll, 1 : 1 mit der Kabel-
Fernbedienung ab. 1.
(Verdrahtungsbeispiel für 2 Kreise)
Schalten Sie die Stromversorgung ein.
1
Drücken Sie gleichzeitig
SET
+
CL
+
TES
T
für 4
Sekunden oder länger.
Die LCD beginnt zu blinken.
2
Geben Sie mit Hilfe der Tasten zur
Temperatureinstellung
/ den Code
ein.
3
hlen Sie mit Hilfe der Tasten zur
Zeiteinstellung
/ die Adresse des
hlkreises.
(Passen Sie die Adresse der Adresse des
hlkreises auf der Schnittstellen-Leiterplatte der
Haupteinheit des gleichen Kühlkreises an.)
4
Drücken Sie
SET
.
(OK, wenn die Anzeige aufleuchtet.)
5
Geben Sie mit Hilfe der Tasten zur
Temperatureinstellung
/ den Code
! ein.
6
hlen Sie mit Hilfe der Tasten zur
Zeiteinstellung
/ die Adresse der
Inneneinheit.
7
Drücken Sie
SET
.
(OK, wenn die Anzeige aufleuchtet.)
8
Geben Sie mit Hilfe der Tasten zur
Temperatureinstellung
/ den Code
" ein.
9
Stellen Sie mit Hilfe der Tasten zur
Zeiteinstellung
/ folgende Werte ein:
Einzel =
, Haupteinheit = ,
Untereinheit =
 .
10
Drücken Sie
SET
.
(OK, wenn die Anzeige aufleuchtet.)
11
Drücken Sie
TES
T
.
Die Einrichtung ist hiermit beendet.
(Der Status wechselt in den normalen Stop-
Modus.)
(Kühlkreisadresse)
(Inneneinheits-Adresse)
(Gruppenadresse)
Richten Sie in dem obigen Beispiel die
Adresse ein, nachdem Sie die Kabel-
Fernbedienung einzeln angeschlossen haben.
Gruppenadresse
Einzel : 0000
Haupteinheit : 0001
} Bei Gruppensteuerung
Untereinheit : 0002
Kreis 1
Haupteinheit Nachfolgeeinheit
Inneneinheit
Fernbedienung
Außeneinheit
Kühlkreisadresse
1
Inneneinheits-Adresse
1
Gruppenadresse
1
Kreis 2
1
2
2
1
3
2
2
1
2
2
2
2
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Bedienung
1 2 3 4 5 6
7
8 9 10 11
Ende
11
4, 7, 10
2, 5, 8
3, 6, 9
1
Daten Code 5d
109
Hinweis 1)
Verwenden Sie bei der Einstellung der Kreisadressen über die Kabel-Fernbedienung nicht die Adressen 29 und 30.
Die Adressen 29 und 30 können nicht in der Außeneinheit verwendet werden. Werden Sie versehentlich verwendet,
erscheint als Fehler [E04] (Innen-/Außeneinheits-Kommunikationsfehler).
Hinweis 2)
Wurde eine Adresse manuell über eine Kabelfernbedienung eingerichtet und Sie wollen für den Kühlkreis eine zentrale
Steuerung einrichten und für jeden Kreis die Außeneinheit festlegen, gehen Sie wie folgt vor.
Richten Sie mit SW13 und 14 auf der Schnittstellen-Leiterplatte der Außeneinheit von jedem Kreis die Kreisadresse
des Kreises ein.
Schalten Sie den Schalter SW30-2 auf den Schnittstellen-Leiterplatten aller Außeneinheiten, die zu der gleichen
zentralen Steuerung gehören, mit Ausnahme der letzten Adresse ab.
(Die Endwiderstände aller Kabel der zentralen Steuerung der Innen-/Außeneinheiten sind einheitlich.)
Schließen Sie zwischen den Kontakten [U1 U2] und [U3 U4] der Haupteinheit von jedem Kühlkreis ein Relais an.
Richten Sie dann die Adresse der zentralen Steuerung ein. (Details zur Einrichtung der Adresse für die zentrale
Steuerung finden Sie im Installationshandbuch der zentralen Steuerung.)
Festlegung der Adresse der Inneneinheit und der Position der Inneneinheit auf der
Fernbedienung
[Festlegung der Nummer der Inneneinheit und deren Position]
1. Wenn Sie die Adresse einer Inneneinheit wissen wollen, kann auch die Position der Inneneinheit
erkannt werden.
Bei Einzelbetrieb (Kabel-Fernbedienung: Innengerät = 1 : 1) oder Gruppensteuerung
[Vorgehensweise] (Bedienung wenn die Klimaanlage in Betrieb ist)
1
Stoppt Sie, drücken Sie
ON / OFF
.
2
Drücken Sie
UNIT
.
Die Nummer zeigt die Kühlkreisadresse und die Adresse der Inneneinheit.
(Sind andere Inneneinheiten an der gleichen Fernbedienung angeschlossen (Gruppensteuerung), wird nach jedem
Drücken von
UNIT
die nächste Einheit angezeigt.)
Bedienung
1 2
Betrieb
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
6
ADRESS-EINSTELLUNG
110
2. Wollen Sie anhand der Adresse die Position der Inneneinheit wissen:
Feststellen der Nummer einer Einheit in einer Gruppensteuerung:
[Vorgehensweise] (Bedienung wenn die Klimaanlage nicht in Betrieb ist)
Die Nummern der Inneneinheiten einer Gruppe werden der Reihe nach angezeigt und die entsprechenden Lüfter
beginnen zu arbeiten.
1
Drücken Sie gleichzeitig
VENT
+
TES
T
für 4 Sekunden oder
nger.
Als Nummer der Einheit wird
angezeigt.
Alle Lüfter der Inneneinheiten einer Gruppe schalten sich
ein.
2
Jedes Mal, wenn Sie
UNIT
drücken, schaltet die Anzeige
von der einen Geräte-Nummer in der Gruppe zur
chsten.
Die als erste angezeigte Gerätenummer ist die Adresse
der Haupteinheit.
Nur der Lüfter der ausgewählten Inneneinheit schaltet sich
ein.
3
Drücken Sie
TES
T
, um die Funktion zu beenden.
Alle Inneneinheiten der Gruppe halten an.
Abfrage der Nummern aller Einheiten mit einer beliebigen Kabel-Fernbedienung.
[Vorgehensweise]
(Bedienung wenn die Klimaanlage nicht in Betrieb ist)
Die Nummer und die Position von Inneneinheiten des gleichen Kreises können abgefragt werden.
Eine Haupteinheit wird ausgewählt und die Nummern der Inneneinheiten des gleichen Kühlkreises werden der Reihe
nach angezeigt und der jeweilige Lüfter wird eingeschaltet.
1
Drücken Sie gleichzeitig die Tasten zur Zeiteinstellung
+
TES
T
für 4 Sekunden oder länger.
Zuerst wird für Kreis 1 der Code
)+ (Adressänderung)
angezeigt. (Wählen Sie die Außeneinheit)
2
hlen Sie mit den Tasten
UNIT
+
SWING/FIX
die
Kreisadresse.
3
Bestätigen Sie mit der Taste
SET
die gewählte
Kreisadresse.
Die Adresse der Inneneinheit, die an dem Kühlkreis des
ausgewählten Kühlkreises angeschlossen ist, wird
angezeigt und der Lüfter eingeschaltet.
4
Jedes Mal, wenn Sie
UNIT
drücken, schaltet die Anzeige
von der einen Geräte-Nummer in der Gruppe zur
chsten.
Nur der Lüfter der ausgewählten Inneneinheit schaltet sich
ein.
[Auswahl einer anderen Kreisadresse]
5
Drücken Sie
CL
, um die Funktion
2
zurückzukehren.
Die Adressen der Inneneinheiten eines anderen Kreises
nnen der Reihe nach angezeigt werden.
6
Drücken Sie
TES
T
, um die Funktion zu beenden.
Bedienung
1 2 3
Ende
Ende
3
1
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Bedienung
1 2 3
4
5 6
Ende
5
6
1
3
2
4
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
111
Änderung der Adresse einer Inneneinheit mit der Kabel-Fernbedienung
Änderung der Adresse einer einzelnen Inneneinheit (Kabel-Fernbedienung: Innengerät = 1 : 1) oder
Gruppensteuerung (Ist die automatische Einstellung der Adressen beendet, steht diese Funktion zur Verfügung.)
[Vorgehensweise] (Bedienung wenn die Klimaanlage nicht in Betrieb ist)
1
Drücken Sie gleichzeitig
SET
+
CL
+
TES
T
für 4 Sekunden oder länger.
(Bei einer Gruppensteuerung ist die erste angezeigte Nummer die Nummer der Hauptinneneinheit.)
2
hlen Sie in einer Gruppensteuerung eine Inneneinheit, die geändert werden soll, mit
UNIT
.
(Der Lüfter der ausgewählten Inneneinheit schaltet sich ein.)
3
Geben Sie mit Hilfe der Tasten zur Temperatureinstellung / den Code ! ein.
4
Ändern Sie mit Hilfe der Tasten / zur Zeiteinstellung die Daten, die Sie editieren wollen.
5
Drücken Sie
SET
.
6
hlen Sie mit
UNIT
die Einheit, die als nächstes geändert werden soll.
Wiederholen Sie die Schritte
4
bis
6
, um die Adressen so zu ändern, dass es keine Duplikate gibt.
7
Drücken Sie nach der Änderung
UNIT
, um die neuen Werte zu übernehmen.
8
Zur Übernahme und zur Beendigung der funktion drücken Sie
TES
T
.
Bedienung
1 2 3 4 5 6 7 8
Ende
3
5
8
1
4
2, 6, 7
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
6
ADRESS-EINSTELLUNG
112
Änderung aller Adressen der Inneneinheiten über eine beliebige Kabel-Fernbedienung
(Ist die automatische Einstellung der Adressen beendet, steht diese Funktion zur Verfügung.)
Inhalt: Mit einer Kabel-Fernbedienung können die Adressen der Inneneinheiten für den gleichen Kühlkreis geändert
werden.
Ändern Sie die Adresse im Modus Adressprüfung/Adressänderung.
[Vorgehensweise]
(Bedienung wenn die Klimaanlage nicht in Betrieb ist)
1
Drücken Sie gleichzeitig die Tasten zur Zeiteinstellung +
TES
T
für 4 Sekunden oder länger.
Zuerst wird für Kreis 1 der Code
)+ (Adressänderung) angezeigt.
2
hlen Sie mit den Tasten
UNIT
+
SWING/FIX
die Kreisadresse.
3
Drücken Sie
SET
.
Die Adresse der Inneneinheit, die an dem Kühlkreis der ausgewählten Haupteinheit angeschlossen ist, wird
angezeigt und der Lüfter eingeschaltet.
Zuerst wir die Adresse der momentanen Inneneinheit angezeigt. (Die Kreisadresse wird angezeigt.)
4
Mit den Tasten / der Zeiteinstellung kann nach oben/unten durch die Adressen der Inneneinheiten
geblättert werden.
Ändern Sie die Vorgabedaten in eine neue Adresse.
5
hlen Sie mit der Taste
SET
die Einstelldaten.
6
Jedes Mal, wenn Sie xx drücken, schaltet die Anzeige von der einen Geräte-Nummer in der Gruppe zur
chsten. Nur der Lüfter der ausgewählten Inneneinheit schaltet sich ein.
Wiederholen Sie die Schritte
4
bis
6
, um die Adressen so zu ändern, dass es keine Duplikate gibt.
7
Drücken Sie
SET
.
(Alle Anzeigen auf der LCD leuchten auf.)
8
Drücken Sie
TES
T
, um die Funktion zu beenden.
Wird die Nummer der Einheit nicht angezeigt,
existiert diese Außeneinheit in diesem Kreis nicht.
Drücken Sie
CL
, und wählen Sie dann
entsprechend der Funktion
2
einen Kreis.
Bedienung
1 2 3 4 5 6 7 8
Ende
4
8
3
1
5, 7
Beenden der Einstellung
2
6
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Löschen der Kreisauswahl
113
SW01 SW02 SW03 SW04 Adresse, die gelöscht wird
212
Prüfen Sie, ob auf der 7-Segment-Anzeige A.d.buS
angezeigt wird und drücken Sie SW04 für mindestens 5
Sekunden.
Kreis + Inneneinheit + Gruppenadresse
222
Prüfen Sie, ob auf der 7-Segment-Anzeige A.d.nEt
angezeigt wird und drücken Sie SW04 für mindestens 5
Sekunden.
Zentrale Adresse
schen von Adressen (Zurücksetzen auf die Werkseinstellung (keine Adressen ausgewählt)
Methode 1
Adressen können einzeln über die Kabel-Fernbedienung gelöscht werden.
In die Kreisadresse, Adresse der Inneneinheit und Gruppenadresse wird über die Kabelfernbedienung 0099
geschrieben. (Details zur Einrichtung über die Kabel-Fernbedienung finden Sie in den oben stehenden Erklärungen.)
Methode 2
schen der Adressen der Inneneinheiten eines Kühlkreises über die Außeneinheit.
1. Schalten Sie die Stromversorgung des Kühlkreises ab, um die Geräte auf Werkseinstellung zurückzusetzen und
ändern Sie die Außeneinheit wie folgt:
1) Entfernen Sie das Relais zwischen [U1U2] und [U3U4].
(Wurde es bereits entfernt, lassen Sie das Gerät in diesem Status.)
2) Schalten Sie SW30-2 auf der Schnittstellen-Leiterplatte der Außeneinheit ein, wenn Sie AN ist.
(Wurde es bereits eingeschaltet, lassen Sie das Gerät in diesem Status.)
2. Schalten Sie die Stromversorgung der Innen-/Außeneinheit, deren Adresse gelöscht werden soll, ein. Prüfen Sie
nach 1 Minute, ob U 1 - - - angezeigt wird und führen Sie die folgenden Einstellungen an der Schnittstellen-
Leiterplatte der Außeneinheit aus, deren Adresse in einem Kühlkreis gelöscht werden soll.
3. Nachdem A.d. c.L. auf der 7-Segment-Anzeige angezeigt wir, setzen Sie SW01/SW02/SW03 auf 1/1/1 zurück.
4. War die Löschung erfolgreich, wird nach einer Weile U.1.L08 auf der 7-Segment-Anzeige angezeigt.
Wird auf der 7-Segment-Anzeige A.d. n.G. angezeigt, kann die Adresse auch einem anderen Kühlkreis zugeordnet
sein. Prüfen Sie das Relais zwischen den Anschlüssen [U1 U2] und [U3 U4].
HINWEIS)
Seien Sie vorsichtig, dass auch die Adressen der anderen Kühlkreise gelöscht werden können, wenn die Funktion
nicht korrekt ausgeführt wird.
5. Richten Sie nach dem Löschen die Adressen neu ein.
U3 U4
U1 U2 U5 U6
Außeneinheit
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
Center unit
Center unit
Center unit
Center unit
Außeneinheit Außeneinheit
U1 U2
A B
Fernbedienung Fernbedienung Fernbedienung Fernbedienung
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1
U3
U2
U4
U1 U2
A B
Zentrale
Steuerung
Einheit, deren Adresse zurückgesetzt werden soll
6
ADRESS-EINSTELLUNG
114
7
TESTLAUF
Vorbereitung
Prüfen Sie, ob das Ventil der Kältemittelleitung der Haupteinheit
ganz geöffnet ist.
Prüfen Sie mit einem 500V Multimeter, ob zwischen den
Anschlüssen 1 bis 3 und Masse 1 M oder mehr gemessen werden.
Schalten Sie das Gerät nicht eine, wenn weniger als 1 M
gemessen werden.
Ablauf des Tests
Testbetrieb mit der Kabel-Fernbedienung
Prüfen Sie die Funktion des Klimageräts im Normalbetrieb mit Hilfe der Kabel-Fernbedienung.
Details zur Bedienung finden Sie im Benutzerhandbuch.
Verwenden Sie eine Infrarot-Fernbedienung, so finden Sie Details im Installationshandbuch der Inneneinheit.
Sie können auch einen Testlauf erzwingen, wenn die Raumtemperatur das Thermostat abgeschaltet hat.
Um eine ständige Wiederholung des Tests zu verhindern schaltet diese Funktion nach 60 Minuten automatisch wieder in
den normalen Betrieb um.
Hinweis)
Verwenden Sie den Testlauf nur zum Test,
nicht für den normalen Betrieb, da er das
System besonders belastet.
Verdrahtete Standardfernbedienung
Vorgehensweise
1
2
3
4
5
Beschreibung
Halten Sie die Taste
TES
T
für 4 Sekunden oder länger gedrückt.
[TEST] wird angezeigt und es kann zwischen verschiedene
Betriebsarten umgeschaltet werden.
Drücken Sie
ON / OFF
.
hlen Sie mit der Taste
MODE
die Betriebsart [COOL] oder [HEAT].
hlen Sie keinen anderen Betriebsmodus.
hrend des Testlaufs wird die Temperatur nicht geregelt.
Fehler werden wie im Normalbetrieb erkannt.
Nach Beendigung des Tests drücken Sie
ON / OFF
, um den Test
anzuhalten.
(Es erscheint wieder eine Anzeige wie unter Punkt
1
)
Um den Testmodus zu verlassen, drücken Sie die Taste
TES
T
.
Die Anzeige [TEST] erlischt. Die Fernbedienung kehrt in den normalen
Status zurück.
WARNUNG
Um den Kompressor beim Start zu
schützen, lassen Sie das Gerät
mindestens 12 Stunden eingeschaltet,
ehe Sie es in Betrieb setzen.
1, 5
3
2, 4
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
TEST
115
Vorgehensweise Funktion 7-Segmentanzeige
1
Stellen Sie die Betriebsart der Inneneinheit die getestet wird
über die Kabel-Fernbedienung auf [COOL] oder [HEAT].
(Wurde das System nicht eingerichtet, verwenden Sie den
momentanen Betriebsmodus.)
[A]
[U1]
[B]
[ ]
2
Stellen Sie den Wahlschalter auf der Schnittstellen-Leiterplatte
der Außeneinheit auf [16] und SW02 sowie SW03 auf die
Adresse der Inneneinheit, die den Testlauf durchführen soll.
[A]
[ ]
Adressanzeige der
entsprechenden Inneneinheit
[B]
[ ]
Start
3
Drücken Sie SW04 für mindestens 10 Sekunden.
Der Betriebsmodus der entsprechenden Inneneinheit
wechselt in den Modus, der mit der Kabel-Fernbedienung
ausgewählt wurde.
Die Temperatur kann während des Testlaufs nicht justiert
werden.
Fehler werden wie im Normalbetrieb erkannt.
Der Testlauf wird erst 3 Minuten nachdem die
Stromversorgung eingeschaltet oder der Normalbetrieb
gestoppt wurde gestartet.
[A]
[ ]
Adressanzeige der
entsprechenden Inneneinheit
[B]
[ ]
Für 5 Sekunden
wird [FF] angezeigt
Stopp 1
Setzen Sie die Wahlschalter auf der Schnittstellen-Leiterplatte
der Außeneinheit zurück, SW01 = [1], SW02 = [1], SW03 = [1].
[A]
[U1]
[B]
[ ]
Vorgehensweise Funktion 7-Segmentanzeige
1
Stellen Sie die Wahlschalter der Schnittstellenkate der
Außeneinheit auf
COOL (Kühlbetrieb) : SW01 = [2], SW02 = [5], SW03 = [1]
HEAT (Heizbetrieb) : SW01 = [2], SW02 = [6], SW03 = [1]
[A]
[C ]
[H ]
[B]
[ ]
[ ]
Start
3
Drücken Sie SW04 für mindestens 10 Sekunden.
Die Temperatur kann während des Testlaufs nicht justiert
werden.
Fehler werden wie im Normalbetrieb erkannt.
Der Testlauf wird erst 3 Minuten nachdem die
Stromversorgung eingeschaltet oder der Normalbetrieb
gestoppt wurde gestartet.
[A]
[C ]
[H ]
[B]
[ C ]
[ H ]
Stopp 1
Setzen Sie die Wahlschalter auf der Schnittstellen-Leiterplatte
der Außeneinheit zurück, SW01 = [1], SW02 = [1], SW03 = [1].
[A]
[U1]
[B]
[ ]
Testlauf über die Schnittstellen-Leiterplatte der Haupteinheit
Dieses Klimagerät verfügt über eine Funktion, die den Testlauf auch anhand der Steuerung über die Schalter auf der
Schnittstellen-Leiterplatte der Haupteinheit durchführen kann.
Diese Funktion wird in Individueller Testlauf, bei dem der Testlauf für einzelne Einheiten durchgeführt wird, und
Sammeltestlauf, bei dem alle angeschlossenen Einheiten getestet werden, unterteilt.
[Individueller Testlauf]
[Sammeltest]
Schnittstellen-Leiterplatte
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
SW02
1
SW01
1
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW03
1
Schalter
drücken
Schalter
drücken
7-Segmentanzeige
[B]
7-Segmentanzeige
[A]
Wahlschalter
SW02
1
SW01
1
7
TESTLAUF
116
Einstellung des
Wahlschalters
SW01 SW02 SW03
Anzeigeinhalt LED
ANr. Außeneinheit (nur U1)
1 1 1 Fehlercode der Außeneinheit
B Fehlercode-Anzeige
Fehlercode
(7-Segmentanzeige,
Außeneinheit)
Hilfscode Fehlercode-Bezeichnung
E06 Anzahl der normal empfangenen Inneneinheiten Senken der Anz. der Raumeinheiten
E07 Kommunikationsfehler / Inneneinheit/Außeneinheit
E08 Doppelte Raumgeräteadresse Doppelte Raumgeräteadresse
E12
01: Kommunikation zwischen Innen- u. Außeneinheit
02: Kommunikation zwischen Außeneinheiten
Startfehler automatische Adressen
E15 Keine Raumeinheit während automatischer Adressierung
E16
00: Überkapazität
01 ~: Anzahl der angeschlossenen Einheiten
Anzahl der angeschlossenen Einheiten / Überkapazität
E19
00: Keine Haupteinheit
02: Zwei oder mehr Haupteinheiten
Fehler bei Anzahl der Außeneinheiten
E20
01: Außeneinheit an anderem Kreis angeschlossen
02: Inneneinheit an anderem Kreis angeschlossen
Bei automatischer Adressierung anderer Kreis angeschlossen
E31 IPDU Anzahl IPDU-Kommunikationsfehler
F04 TD1-Sensorfehler
F06 TE1-Sensorfehler
F07 TL-Sensorfehler
F08 TO-Sensorfehler
F12 01: TS1-Sensorfehler TS1-Sensorfehler
F13 01: Verdichter 1 TH-Sensorfehler
F15 Verdrahtungsfehler Außentemperatursensors (TE, TL)
F16 Verdrahtungsfehler Außendrucksensors (Pd, Ps)
F23 Ps-Sensorfehler
F24 Pd-Sensorfehler
F31 Außeneinheit EEPROM-Fehler
8
FEHLERSUCHE
Zusätzlich zur Überprüfung der Inneneinheit über die Fernteuerung können Probleme an der Außeneinheit durch die 7-
Segment-Anzeige auf der Leiterplatte der Außeneinheit diagnostiziert werden. Verwenden Sie diese Funktion für die
unterschiedlichsten Tests. Schalten Sie nach dem test alle DIP-Schalter wieder in die Position OFF.
n 7-Segment-Anzeige und Fehlercode
Existiert ein Hilfscode werden
abwechselnd der Fehlerode (für 3
Sekunden) und dann der zusätzliche
Code (für 1 Sekunde) angezeigt.
Fehlercode (7-Segmentanzeige [B], Außeneinheit)
Anzeige wenn SW01: 1, SW02: 1, SW03: 1
D600
AB
D601 D602 D603 D604
79


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Toshiba MCY-MAP0601HT2D at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Toshiba MCY-MAP0601HT2D in the language / languages: English, German as an attachment in your email.

The manual is 2,96 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info