587680
14
Zoom out
Zoom in
Previous page
1/81
Next page
11
Coupling size of brazed pipe
(Unit: mm)
Connected section
External size Internal size
Connected section
External size Internal size
Standard outer dia. (Allowable difference)
Min. depth
of insertion
Standard outer dia. of
connected copper pipe
CFKG
Oval value
Min. thickness
of coupling
6.35 6.35 (±0.03) 6.45 (
+0.04
0.02
) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 (
+0.04
0.02
) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 (
+0.04
0.02
) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 (
+0.04
0.02
) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 (
+0.03
0.03
) 11 10 0.15 or less 0.80
Minimum wall thickness for R410A application
Soft Harf Hard or Hard OD (Inch) OD (mm) Minimum wall thickness (mm)
OK OK 1/4 6.35 0.80
OK OK 3/8 9.52 0.80
OK OK 1/2 12.70 0.80
OK OK 5/8 15.88 1.00
NG * OK 3/4 19.05 1.00
* If the pipe size is Ø19.0 or more, use a
suitable material.
Table 1 Table 2
Capacity code Capacity code
Total capacity code of
connectable indoor units
Indoor unit
capacity type
Equivalent to HP Equivalent to capacity
Outdoor unit
capacity type
Equivalent to HP
No. of
connectable
indoor units
Min. (HP) Max. (HP)
007 type 0.8 2.2 0401 type 4 6 3.2 5.2
009 type 1 2.8 0501 type 5 8 4.0 6.5
012 type 1.25
3.6
0601 type 6 9 4.8 7.8
015 type 1.7
4.5
018 type 2
5.6
024 type 2.5
7.1
027 type 3
8
030 type 3.2
9
036 type 4
11.2
048 type 5
14
K
ØC
G
ØF
Selection of pipe materials and size
Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank.
The capacity codes of the outdoor units are decided at each capacity rank.
The maximum No. of connectable indoor unit and the total value of capacity codes of the indoor units are also
decided.
3
REFRIGERANT PIPING
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Toshiba MCY-MAP0401HT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Toshiba MCY-MAP0401HT in the language / languages: English, German as an attachment in your email.

The manual is 2,96 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info