Group 2: Integrated room thermostat parameters
An integrated room thermostat can control heating operation according to the data from internal temperature
sensor. It uses proportional control to set the outlet water temperature within the range defined by the tdr (P2.3)
parameter:
- if TM < ti1 - tdr (TM < P2.1 P2.3), heating is controlled to reach the maximum heating water temperature
to¯ (P3.4),
- if TM > ti1 (TM > P2.1), heating is controlled to have the minimum heating water temperature to_ (P3.3),
- if ti1 - tdr < TM < ti1 (P2.1 P2.3 < TM < P2.1), the desired heating water temperature is calculated by the
interpolation between to_ and to¯ (P3.3 a P3.4),
- if TM > ti1 + tdF, the heating is switched off completely.
The aforementioned is true if the NU binary input specification is “disconnected”. If the NU binary input
specification is “connected”, a value of ti2 (P2.2) is used instead of ti1 (P2.1).
ti1 P2.1 Desired value of the room temperature. True if NM is “disconnected”.
The setting range falls between 10 and 30°C, step of 1°C, leading value is 21°C.
ti2 P2.2 Desired value of the room temperature. True if NM is “connected”.
The setting range falls between 10 and 30°C, step of 1°C, leading value is 19°C.
tdr P2.3 Temperature range of room in which the proportional control of the desired outlet water
temperature value takes place.
The setting range falls between 2 and 10°C, step of 1°C, leading value is 3°C.
tdF P2.4 Difference (hysteresis) between the shut-down and repeated initiation of heating when the
desired room temperature has been exceeded.
The setting range falls between 0.25 and 2.50°C, step of 0.25°C, leading value is 0.5°C.
Complete heating shut-down occurs if the room temperature exceeds the set value by more than tdF (P2.4).
Heating is again switched on only when the room temperature drops below the set value.
Group 3: Heating setting and display mode
rto P3.1 Heating mode (TOP)
The boiler operation is conditioned by the connection of the external room thermostat PT terminals at all
possible settings. If the thermostat is not used at all, it is necessary to create a permanent connection between
the PT terminals.
Settings options:
--- 0 Heating switched off. It is not possible to switch it on even by means of button 3. Anti-freeze
protection is active.
tEr 1 Heating is controlled by the external room thermostat contact and the outlet water temperature
is set by buttons 1.
EtE 2 Heating is controlled by integrated equitherm regulator. Outdoor temperature sensor must be
connected.
In the case of a defective sensor or if it is not connected, the boiler is controlled in the tEr (like at P3.1 = 1) mode.
Prt 3 Heating is controlled by integrated room thermostat. The room temperature sensor must be
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Thermona THERM EL 45 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Thermona THERM EL 45 in the language / languages: English as an attachment in your email.

The manual is 0,87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info