Room temperature controller RAM 713 S
theben
Version: Sep-12 (subject to change) Seite 38 von 56
5 Appendix
5.1 Determining the current operating mode
The current setpoint value can be adapted in line with certain requirements by selecting the
operating mode.
The operating mode can be specified by Objects 3..5.
There are two methods available:
5.1.1 New operating modes
If on the parameter page, new operating mode is selected by the “Determining operating
mode” parameter, the current operating mode can be defined as follows:
Table 19
Pre-selected operating
mode
Object 3
Presence
Object 4
Window status
Object 5
Current operating
mode
(Object 6)
Any
Any
1
Frost / heat protection
Any
1
0
Comfort
Comfort
0
0
Comfort
Standby
0
0
Standby
Night
0
0
Night
Frost / heat protection
0
0
Frost / heat protection
Typical application:
In the mornings Object 3 activates “Standby” or “Comfort” mode and in the evenings “Night”
mode via a timer (e.g. TR 648).
During holiday periods, Object 3 also selects frost / heat protection via another channel on the
timer.
Object 4 is connected to a presence indicator. If a presence is detected, RAM 713 switches to
comfort mode (see table).
Object 5 is connected to a window contact via the bus (binary inputs).
As soon as a window is opened, RAM 713 S switches to frost protection mode.
Frost protection
Night
Standby
Comfort
Comfort
Presence
Frost protection
Window
Actual operation mode
0
1
0
1
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben RAMSES 713 S KNX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben RAMSES 713 S KNX in the language / languages: English as an attachment in your email.

The manual is 0,4 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben RAMSES 713 S KNX

Theben RAMSES 713 S KNX User Manual - English - 1 pages

Theben RAMSES 713 S KNX User Manual - German - 56 pages

Theben RAMSES 713 S KNX User Manual - German - 1 pages

Theben RAMSES 713 S KNX User Manual - Dutch - 57 pages

Theben RAMSES 713 S KNX User Manual - Dutch - 1 pages

Theben RAMSES 713 S KNX User Manual - French - 59 pages

Theben RAMSES 713 S KNX User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info