RAM 713 Fan Coil room thermostat
theben
Version: Sep-11 (subject to change) Page 59 of 65
6.5.2 Response of the P-control
Max. 4l/Min.
Bandwidth
Set point value
Actual value
17l
21l
15l
Losses
1l/Min
A filling volume of 15l gives rise to a control deviation of 211 – 151 = 61
As our actual value lies outside the bandwidth, the control will operate the flow rate at 100%
i.e. at 4l / minute
The supply quantity (control variable) is calculated from the control deviation
(setpoint value – actual value) and the bandwidth.
Control variable = (control deviation / bandwidth) x 100
The table below shows the response and therefore also the limits of the P-control
Table 53
Filling level
Control variable
Supply
Loss
Increase in filling
level
15l
100%
4 l/min
1 l/min
3 l/min
19l
50%
2 l/min
1 l/min
20l
25%
1 l/min
0 l/min
The last line indicates that the filling level cannot increase any further, because the inflow
only allows the same amount of water to flow in as flows out through loss.
The result is a permanent control deviation of 11 and the setpoint value can never be reached.
If the loss was 1l higher, the permanent control deviation would increase by the same amount
and the filling level would never exceed the 19l mark.
In a room this would mean that the control deviation increases with a decreasing outside
temperature.
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben RAMSES 713 Fan Coil at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben RAMSES 713 Fan Coil in the language / languages: English as an attachment in your email.

The manual is 0,69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben RAMSES 713 Fan Coil

Theben RAMSES 713 Fan Coil User Manual - English - 56 pages

Theben RAMSES 713 Fan Coil User Manual - English - 1 pages

Theben RAMSES 713 Fan Coil User Manual - German - 65 pages

Theben RAMSES 713 Fan Coil User Manual - German - 56 pages

Theben RAMSES 713 Fan Coil User Manual - German - 1 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 57 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 57 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 1 pages

Theben RAMSES 713 Fan Coil User Manual - French - 59 pages

Theben RAMSES 713 Fan Coil User Manual - French - 59 pages

Theben RAMSES 713 Fan Coil User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info