RAM 713 Fan Coil room thermostat
theben
Version: Sep-11 (subject to change) Page 49 of 65
6.2.3.2 Calculating the setpoint value in cooling operation
Table 41: Current setpoint value during cooling
Operating
mode
Current setpoint value
Comfort
Baseset point value + setpoint value offset + dead zone
Standby
Base setpoint value + setpoint value offset + dead zone + increase in standby
mode
Night
Base setpoint value + setpoint value offset + dead zone + increase in night
mode
Frost / heat
protection
configured setpoint value for heat protection mode
Example:
Cooling in comfort mode.
The room temperature is too high and RAM 713 FAN COIL has switched to cooling
operation
Parameter page
Parameters
Setting
Setpoint values
Base setpoint after reset
21 °C
Cooling setpoint values
Dead zone between heating
and cooling
2 K
Increase in standby mode
(during cooling)
2 K
Operation
Maximum setpoint offset on
the rotary control
+/- 2 K
The setpoint value was previously lowered by 1 K using the rotary control.
Calculation:
Current setpoint value = base setpoint value + setpoint value offset + dead zone
= 21°C -1K +2K
= 22°C
Changing to standby mode causes a further increase in the setpoint value (energy saving) and
gives rise to the following setpoint value.
Setpoint value = base setpoint value + setpoint value offset + dead zone + increase in standby
mode
= 21°C - 1K + 2K + 2K
= 24°C
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben RAMSES 713 Fan Coil at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben RAMSES 713 Fan Coil in the language / languages: English as an attachment in your email.

The manual is 0,69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben RAMSES 713 Fan Coil

Theben RAMSES 713 Fan Coil User Manual - English - 56 pages

Theben RAMSES 713 Fan Coil User Manual - English - 1 pages

Theben RAMSES 713 Fan Coil User Manual - German - 65 pages

Theben RAMSES 713 Fan Coil User Manual - German - 56 pages

Theben RAMSES 713 Fan Coil User Manual - German - 1 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 57 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 57 pages

Theben RAMSES 713 Fan Coil User Manual - Dutch - 1 pages

Theben RAMSES 713 Fan Coil User Manual - French - 59 pages

Theben RAMSES 713 Fan Coil User Manual - French - 59 pages

Theben RAMSES 713 Fan Coil User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info