5.4 Monitoring the actual value
5.4.1 Application
Case 1: A sensor is connected to interface E2.
Its connection line could be inadvertently interrupted or short-circuited, e.g. during building
or renovation work.
Case 2: The temperature is determined by a different EIB device and sent to Cheops control.
This external temperature transmitter could fail (bus line short circuited etc…) and not longer
be able to perform its function, for a short time or permanently.
Because control is not possible if the actual value fails, this value must be monitored.
5.4.2 Principle
If an external sensor is connected to E2, it is constantly monitored for short-circuit or line
break.
If the temperature is received via Object 2, Cheops control can monitor whether new actual
value telegrams are received at regular intervals.
In both cases, either an emergency program can be started or further control can be handled
by the internal sensor, should the actual value fail.
5.4.3 Practice
The response is defined as follows on the "Actual value" parameter page:
External sensor on E2
Emergency program (0…100%)
or internal measurement:
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben CHEOPS control KNX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben CHEOPS control KNX in the language / languages: English as an attachment in your email.

The manual is 0,6 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben CHEOPS control KNX

Theben CHEOPS control KNX User Manual - English - 1 pages

Theben CHEOPS control KNX User Manual - German - 72 pages

Theben CHEOPS control KNX User Manual - German - 1 pages

Theben CHEOPS control KNX User Manual - Dutch - 76 pages

Theben CHEOPS control KNX User Manual - French - 74 pages

Theben CHEOPS control KNX User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info