Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 24 of 71
3.4.4 Heating control
Table 14
Designation
Values
Meaning
Setting of control parameters
Via type of system
User-defined
Standard application
Prof. application Self-
configure P/PI control
Type of system
Radiator heating
floor heating
PI control with:
Integrated time = 150 minutes
Bandwidth = 4 k
Integrated time = 210 minutes
Bandwidth = 6 k
Minimum actuating value in
heating mode
0%, 5%, 10%
15%, 20%, 25%
30%, 40%
Smallest permitted actuating
value (Exception: actuating
value of 0% is always used)
Behaviour at minimum
actuating value underflow
(heating mode)
0%
0 % = 0 % otherwise min.
actuating value
Run to 0% as soon as the
defined min. actuating value
is underrun.
Runs to the min. actuating
value as long as the value is
greater than 0% and smaller
or equivalent to the min.
actuating value.
However, if a actuating value
of 0%
is required (set point
temperature reached), Cheops
control returns to 0%.
Object “actuating value
heating”
available
not available
The heating actuating value is
not to be sent on the bus
(Object 8 can be read).
The heating actuating value is
required to control other
actuators (Cheops drive).
Object 7 is added.
Transmission of actuating
value heating
At change by 1%
At change by 2 %
At change by 3 %
At change by 5 %
At change by 7 %
At change by 10 %
At change by 15 %
After how many % change*
in the actuating value is the
new value to be sent.
Small values increase control
accuracy but also the bus
load.
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Theben CHEOPS control KNX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Theben CHEOPS control KNX in the language / languages: English as an attachment in your email.

The manual is 0,6 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Theben CHEOPS control KNX

Theben CHEOPS control KNX User Manual - English - 1 pages

Theben CHEOPS control KNX User Manual - German - 72 pages

Theben CHEOPS control KNX User Manual - German - 1 pages

Theben CHEOPS control KNX User Manual - Dutch - 76 pages

Theben CHEOPS control KNX User Manual - French - 74 pages

Theben CHEOPS control KNX User Manual - French - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info