Installation Instructions
Connecting the Flue
The flue must be installed in accordance with the
manufacturers instructions.
1.17 Fill the void at the back of the box with 6:1 vermiculite/cement
mix or any other good non-combustible insulation material. It
is important to insulate the back, top and side of the box.
CHECK THE BOILER CONNECTIONS FOR
ANY SIGN OF LEAKS BEFORE ANY INFILLING
REQUIRED IN THE INSTALLATION.
1.18 Insert the flue spigot from inside the appliance.
1.19 Connect the flue liner to the flue collar using the flue liner
adaptor.
1.20 Seal liner and adaptor with fire cement.
1.21 If the appliance is installed on an unlined, masonry flue:
Fit a non-combustible closure plate to locate the first section
of single wall flue pipe from the appliance to the old system.
Make the connection as with a flue liner system.
1.22 Do not connect the system into large voids that could
exist in older chimney systems. If this is the case consider
using a flue lining system to improve the operation of the
appliance, see Diagram 3.
3
Closure Plate
Ridged Flue
Pipe
Flue Liner
Adaptor
Supplied By
Flue Liner
Manufacturer
2. Steel Top & Optional Glass Top
The appliance is supplied with a flat steel top.
2.1 Place the top on the appliance ensuring it is central and
flush with the sides of the appliance. The front of the top
should line up with the door. The top also has 3 x threaded
bosses on the underside, see Diagram 4. Ensure the 2 x
front bosses line up with the holes in the carcass top.
4
2.2 With the door open, fix the steel top in position from the
underside using the 2 x M8 x 20 hex head screws and 2 x
M8 crinkle washers.
Washer
Screw
5
2.3 This appliance can also be fitted with an optional glass top
(part no. VW-7NGB). The top has 5 x silicon feet on the
bottom to space it off the steel top.
6
2.4 Place the glass top, feet down, on the appliance. Ensure the
glass top is flush with the front and sides of the steel top.
3. CO Alarms
All open flued appliances can be affected by temporary
atmospheric conditions which may allow fumes to enter
the house. Building regulations require that whenever
a new or replacement fixed solid fuel or wood/biomass
appliance is installed in a dwelling a carbon monoxide
alarm must be fitted in the same room as the appliance.
Further guidance on the installation of the carbon
monoxide alarm is available in the latest edition of
BS EN50292 and from the alarm manufacturer's
instructions.
HETAS recommend the unit is permanently fixed
in accordance with the manufacturer's installation
instructions or with the guidance contained in Approved
Document J where no other information is available.
Provision of an alarm must not be considered a
substitute for either installing the appliance correctly
or ensuring regular servicing and maintenance of the
appliance and chimney system.
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Stovax View 7 Inset High Output Boiler Inset at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Stovax View 7 Inset High Output Boiler Inset in the language / languages: English as an attachment in your email.

The manual is 4.77 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info