Special functions
6.18.10. - Pressure monitor
6.18.11. - Pressure monitor
6.18.11.1. - RPS1 / RPS2
6.18.11.2. - Pmin
6.18.11.3. - Pmax
A message is shown when the pressure drops below set minimum or exceeds the set maximum pressure. No relay
is switched, for that see „7.3.20. - Pressure monitor“ on page 47.
Maximum pressure.
If this value is exceeded, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 to 10 bar
Default setting: 1.6 bar
Minimum pressure.
If this value is undershot, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 to 1.6 bar
Default setting:
Type of pressure sensor
This menu is used to determine the type of pressure sensor used.
Please note: If e.g. VFS1 is connected, RPS1 option is not shown.
Settings range: Off; 0-0.6 bar; 0-1 bar; 0-1.6 bar; 0-2.5 bar; 0-4 bar; 0-6 bar; 0-10 bar
Default setting: Off
A message is shown and the LED ashes when the pressure deviates from the set minimum or maximum value.
Settings range: On, Off / Default setting: Off
6.19. - Sensor calibration
Caution
Caution
May only be started by a specialist during commissioning! Incorrect settings may cause malfunctions.
Starting the commissioning help guides you in the correct order through the basic settings necessary for commissioning, and
provides brief descriptions of each parameter in the display.
Pressing the “esc” key takes you back to the previous value so you can look at the selected setting again or adjust it if desi-
red. Pressing the “esc” more than once takes you back to the selection mode, thus cancelling the commissioning help.
6.20. - Commissioning
May only be started by a specialist during commissioning! Observe the explanations for the the individual
parameters in these instructions, and check whether further settings are necessary for your application.
Deviations in the temperature values displayed, for example due to cables which are to long or sensors which are not positi-
oned optimally, can be compensated for manually here. The settings can be made for each individual sensor in steps of 0.8°C
(temperature) resp. 0.2% of the measuring range of the VFS / RPS sensor ( ow rate / pressure) per step.
Offset Sensor Settings range: -100 ... +100 / Default setting: 0
Caution
All of the settings that have been made can be reset, thus returning the controller to its delivery state.
6.21. - Factory settings
The entire parametrisation, analyses, etc. of the controller will be lost irrevocably. The controller must
then be commissioned once again.
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel XTDC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel XTDC in the language / languages: English as an attachment in your email.

The manual is 1.73 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel XTDC

Sorel XTDC User Manual - German - 48 pages

Sorel XTDC User Manual - French - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info