6.13. - Pressure monitor
6.13.1. - Pressure monitor
The relay is switched on when the pressure drops below set minimum or exceeds the set maximum pressure.
Settings range: On, Off / Default setting: Off
This menu is used to con gure the system pressure montoring via direct sensor. As soon as the set limits are exceed-
ed, the relay is switched on.
6.13.1.1. - RPS1 / RPS2
Type of pressure sensor
This menu is used to determine the type of pressure sensor used.
Please note: If e.g. VFS1 is connected, RPS1 option is not shown.
Settings range: Off; 0-0,6 bar; 0-1 bar; 0-1,6 bar; 0-2,5 bar; 0-4 bar; 0-6 bar; 0-10 bar
Default setting: Off
6.13.1.2. - Pmin
Minimum pressure. If this value is undershot, an error message is displayed and the relay is switched on (Hysteresis
0.5 bar).
Settings range: Off; 0,0 to 1,6 bar
Default setting:
6.13.1.3. - Pmax
Maximum pressure. If this value is exceeded, an error message is displayed and the relay is switched on (Hysteresis
0.5 bar).
Settings range: Off; 0,0 to 10 bar
Default setting: 1,6 bar
Special functions
Relay functions
Relay functions
6.14. - Booster pump
6.14.1. - Filling time
Additional pump that lls the system at the start of every solar charge.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.15. - Parallel operation R (X)
The relais is switched on at the same time as the set relay R1 or R2.
Settings range: On, Off
Time the pump is switched on
This setting determines the length of time the pump is switched on at the start of a solar charge.
Settings range: 0-120 seconds / Default setting: 30 seconds
6.15.1. - Delay
This menu determines how long after the start of R1 or R2 the parallel relay is switched on.
Settings range: 0-120 seconds / Default setting: 30 seconds
6.15.2. - Followup time
This menu determines how long after the switch off of R1 or R2 the parallel relay is switched off.
Settings range: 0-120 seconds / Default setting: 30 seconds
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel XTDC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel XTDC in the language / languages: English as an attachment in your email.

The manual is 1.73 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel XTDC

Sorel XTDC User Manual - German - 48 pages

Sorel XTDC User Manual - French - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info