812340
19
Zoom out
Zoom in
Previous page
1/44
Next page
Thermostat d'ambiance
This value is used to appoint the amount of influence the room temperature has on the reference flow temperature, as a per-
centage. For every degree of the room temperature deviates from the reference room temperature, the percentage of the cal-
culated reference flow temperature set here is added to or subtracted from the reference flow temperature, so long as it is within
the limits of the min. and max. flow temperatures that can be set in the protective functions.
Example: Reference room temp.: e.g. 25 °C; room temp.: e.g. 20 °C ±5 °C. Calculated reference temp.: e.g. 40 °C: room control-
ler: 10 %= 4 °C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is
higher than the one set in max. flow temp, the resulting temperature is the one set in max. flow temp.
Pièce-cons.-jour
The desired room temperature for day mode. As long as this temperature is not reached, the reference flow temperature is rai-
sed and/or lowered according to the percent setting in room controller‘. If room controller‘ is set to 0 %, this function is deac-
tivated.
Pièce-cons.-nuit
The desired room temperature for night mode. As long as this temperature is not reached, the reference flow temperature is rai-
sed and/or lowered according to the percent setting in room controller‘. If room controller‘ is set to 0 %, this function is deac-
tivated.
In the modes Set point‘ and Set point program, the room controller has no influence.
Thermostat (X)
The room controller is selected here. If no room controller is connected and a room controller is connected via the CAN Bus,
another room controller can be selected here. The CAN bus ID of controller is shown in Menu 6, Service Data‘ under CAN Bus
ID‘. In °CALEON see the CAN Bus ID in the expert menu under Network. Choose the Room Controller with the CAN Bus ID of
the corresponding controller.
Sensor Typ
If a sensor input is connected to a room controller, it must be set here whether it is a room temperature sensor (RC20) or a swit-
ching contact.
Vannes mélangeuses
This menu contains all the settings concerning the mixer of heating circuit 1
Direction
Direction of the mixing valve can be set here.
Mixer turn time
Pendant cet intervalle en secondes la vanne sera pilotée, c-à-d ouvrir ou fermer, avant que une nouvelle mesure sera conduite
pour régler la température demandée.
Mixer off factor
Par ce facteur on gle l'intervalle intermédiaire d'arrêt avec lequel on multiplie ce temps d'arrêt calculé. If the pause factor is ‚1,
the normal pause time is used, ‚0.5 will use half the normal pause time. Setting the pause factor to 4‘ would quadruple the pause
time.
Mixer increase
En cas d'une montée rapide de la température cette valeur sera additionnée à la température demane, pour que la vanne s'ac-
tive en sense inverse. Si la température mesurée ne monte plus, cette température sera la nouvelle température de mesure pour
faire les calculs. La mesure de la température se fait toutes les minutes.
PV contact
This sensor input could be used as a PV-contact of Photovoltaic-System.
This sensor is observed to "short circuit" (PV-Contact closed).
If the PV-Contact is closed, the mode of this function is changed to "comfort" and operate
This also applies in the case that the mode "comfort" of the function currently has no time release.
Information about the operation and the connection of PV-contact, refer to the technical description of your PV sys-
tem.
Réglages eau chaude sanitaire
Les dispositifs de curités à prévoir sur place ne sont en aucun cas remplacés!
Mode de fonctionnement
Ici on gle le chauffage de l'ECS. "Auto" active le chauffage selon le programme d'intervalle glé, "Arrêt" le met à l'arrêt.
19
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel XHCC S61 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel XHCC S61 in the language / languages: French as an attachment in your email.

The manual is 4.87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel XHCC S61

Sorel XHCC S61 User Manual - English - 44 pages

Sorel XHCC S61 User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info