Mode M1: The controller changes to the set max. speed after the purging time. If the temperature difference ∆T between the reference
sensors is below the set switch on temperature difference ∆T R1, the speed will be reduced. If the temperature difference between the ref-
erence sensors is above the set switch on temperature difference ∆T R1, the speed will be increased. If the controller has decreased the
speed of the pump to the smallest level and the ∆T between the reference sensors is still only ∆Toff, the pump will be turned off.
Mode M2: The controller changes to the set min. speed after the Speed. If the temperature difference ∆T between the reference sensors is
above the set switch on temperature difference ∆T R1, the speed will be increased. If the temperature difference ∆T between the reference
sensors is below the set switch on temperature difference ∆T R1, the speed will be reduced. If the controller has decreased the speed of the
pump to the smallest level and the ∆T between the reference sensors is still only ∆Toff, the pump will be turned off.
Mode M3: The controller changes to the set min. speed after the Speed. If the temperature on the reference sensors is above the set value to
be set in the following, the speed will be increased. If the temperature on the reference sensors is below the set value to be set in the fol-
lowing, the speed will be reduced.
Mode M4 (2 storage system):
When the primary storage is loaded, speed control works as in M3. When the secondary storage is loaded, speed control works as in M1.
Purging time
For this time, the pump runs with its full speed (100%) in order to guarantee a secure start-up. Only after expiration of this purging time will the
pump have a controlled speed and will switch, depending on the set variant, to the max. or min. speed. Speed.
Sweep time
With the control time, the inertia of the speed control is determined in order to prevent strong temperature deviations as much as possible.
The timespan is entered here, which is needed for a complete cycle from minimum speed to maximum speed.
Max. Speed
The maximum speed of the pump is determined here in %. During the setting, the pump runs in the respective speed and the flow can be
determined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump and pump
level. 100% is the maximum possible power of the controller.
Min. Speed
The minimum speed of the pump is determined here. During the setting, the pump runs in the respective speed and the flow can be determ-
ined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump and pump
level. 100% is the maximum possible power of the controller.
Setpoint
This value is the control setpoint for mode 3 See " Variant " on page 33, only version 2.3, and 4.. If this value is below at the sensor, the speed
is reduced. When it is exceeded, the speed is increased.
Relay functions
Free, i.e. in the specific hydraulic variant unused relays, can be assigned to various additional functions. Every additional function can only be
assigned once.
R1 to R2: mechanical relay 230V
R3: Alternating contact 230 V
V1 and V2: PWM and 0-10 V outputs See " External relay at signal output V(X) (0-10V / PWM) " on page 46
Please pay special attention to the relay’s technical information (see "Specifications“).
The symbols shown here are displayed on the main overview screen when the special function is activated.
The sequence in this list does not correspond to the menu numbering in the controller.
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel LTDC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel LTDC in the language / languages: English as an attachment in your email.

The manual is 5.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel LTDC

Sorel LTDC User Manual - German - 50 pages

Sorel LTDC User Manual - Dutch - 36 pages

Sorel LTDC User Manual - French - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info