Read carefully before installation, commissioning and operation
Heating-Controller HCC 5
Installation and operating instructions
Weather controlled heat circuit regulator
3
Safety instructions
Danger
Caution
A.1 EC declaration of conformity
Bya󰀩xingtheCEmarktotheunitthemanufacturerdeclaresthattheHCC5conforms
to the following relevant safety regulations:
- EC low voltage directive 2006/95/EC
- EC electromagnetic compatibility directive 2004/108/EC
Conformityhasbeenveriedandthecorrespondingdocumentationand
theECdeclarationofconformityarekeptonlebythemanufacturer.
A.2 General instructions It is essential that you read this!
These installation and operating instructions contain basic instructions and important
information regarding safety, installation, commissioning, maintenance and the optimal
use of the unit. Therefore these instructions must be read completely and understood
by the installation technician/ specialist and by the system user before installation,
commissioning and operation of the unit.
The valid accident prevention regulations, VDE regulations, the regulations of the
local power utility, the applicable DIN-EN standards and the installation and operating
instruction of the additional system components must also be observed. The controller
does not under any circumstances replace any safety devices to be provided by the
customer!
Installation, electrical connection, commissioning and maintenance of the unit may
only be carried out by specialists who possess the appropriate training.
Fortheuser:Makesurethatthespecialistgivesyoudetailedinformationonthefunc-
tionandoperationofthecontroller.Alwayskeeptheseinstructions
in the vicinity of the controller.
A.3 Explanation of symbols
Failure to observe these instructions can result in danger to life from
electric voltage.
Danger
Failure to observe these instructions can result in serious damage to
health such as scalding, or even life-threatening injuries.
Caution
Failure to observe these instructions can result in destruction of the unit
or the system, or damage to the environment.
Information which is especially importation for the function and optimal
use of the unit and the system.
4
A.4 Changes to the unit
A.5 Warranty and liability
The controller has been manufactured and tested with regard to high quality
and safety requirements. The unit is subject to the statutory guarantee
period of two years from the date of sale.
The warranty and liability shall not include, however, any injury to persons or material
damage that is attributable to one or more of the following causes:
- Failure to observe these installation and operating instructions
- Improper installation, commissioning, maintenance and operation
- Improperly executed repairs
- Unauthorised structural changes to the unit
- Installation of additional components that have not been tested together
with the unit
- Any damage resulting from continued use of the unit despite an obvious defect
- Failure to use original spare parts and accessories
- Use of the device for other than its intended purpose
- Operationaboveorbelowthelimitvalueslistedinthespecications
- Force majeure
- Changes, additions to or conversion of the unit are not permitted without
written permission from the manufacturer
- Itislikewiseforbiddentoinstalladditionalcomponentsthathavenot
been tested together with the unit
- If it becomes clear that safe operation of the unit is no longer possible,
for example because of damage to the housing, then turn the controller
o󰀨immediately
- Any parts of the unit or accessories that are not in perfect condition must
be exchanged immediately
- Use only original spare parts and accessories from the manufacturer.
- Markingsmadeontheunitatthefactorymustnotbealtered,removed
or made illegible
- Only the settings actually described in these instructions may be made
on the controller
Changes to the unit can compromise the safety and function of theunit
or the entire system.
Safety instructions
Danger
5
B.2 Temperature resistance table for Pt1000 sensors
B.1 Specications
Electrical specifications:
Mains Voltage 230VAC +/- 10%
Mains frequency 50...60Hz
Power consumption 2VA
Total switched power 460VA (Relay outputs 1-3)
Switched power per relay 460VA for AC1 / 185W for AC3
Internal fuse 2A slow blow 250V
Protection category IP40
Protection class II
Sensor inputs 5x Pt1000 temperature sensor
1x Room
Measuring range -40 to110°C
Permissible ambient conditions:
Ambient temperature
for controller operation 0°C...40°C
for transport/storage 0°C...60°C
Air humidity
for controller operation max. 85% humidity at 25°C
for transport/storage no moisture condensation permitted
Other specifications and dimensions
Housing design 2-part, ABS plastic
Installation methods Wall installation, optionally panel installation
Overall dimensions 163mm x 110mm x 52mm
Aperture installation dimensions 157mm x 106mm x 31mm
Display Fully graphical display 128 x 64 dots
Light diode Multicolour
Operation 4entrykeys
Temperature sensors: (may not be included in the scope of supply)
Immersion sensor Pt1000, e.g. immersion sensor TT/P4
Pipe-mounted sensor Pt1000, e.g. pipe-mounted sensor TR/P4
Outdoor sensor Pt1000, e.g. outdoor sensor TA52
Remote adjuster Pt1000, Typ RC21
Sensor leads 2x0.75mm² extendable up to 30m
°C 0 10 20 30 40 50 60 70 80 90 100
1000 1039 1077 1116 1155 1194 1232 1270 1308 1347 1385
Description of controller
6
B.4 Scope of supply
• Heating controller HCC 5
• 3 screws 3,5x35mm and 3 plugs 6mm for wall installation
• 6 strain reliefs with 12 screws, replacement fuse 2AT
• installation and operating instructions HCC 5
Optionally contained depending on design/order:
• 1x outdoor sensor e.g. TA52 (Pt1000)
• 1-2x pipe-mounted sensor e.g. TR/P4 (Pt1000)
• 1xbu󰀨ersensore.g.TT/P4(Pt1000)
• 1x Indoor sensor/remote adjuster with mode switch RC21
• 1x Immersion sleeve e.g. TH150
• various additional functions expansion boards
B.5 Disposal and pollutants
The unit conforms to the European RoHS directive 2002/95/EC for the restriction of
the use of certain hazardous substances in electrical and electronic equipment.
Caution
The unit must not under any circumstances be disposed of with ordina-
ry household refuse. Dispose of the unit only at appropriate collection
pointsorshipitbacktothesellerormanufacturer.
B.3 About the controller
TheweathercontrolledHeatCircuitControllerHCC5facilitatese󰀩cientuseand
function control of your heating system. The device is impressive most of all for its
functionality and simple, almost self-explanatory operation. For each step in the input
processtheindividualentrykeysareassignedtoappropriatefunctionsandexplained.
The controller menu contains headwords for the measured values and settings, as well
as help texts or clearly-structured graphics.
Important characteristics of the HCC 5:
• Depiction of graphics and texts in a lighted display
• Simple viewing of the current measurement values
• Statistics and monitoring of the system by means of statistical graphics, etc.
• Extensive setting menus with explanations
• Menublockcanbeactivatedtopreventunintentionalsettingchanges
• Resetting to previously selected values or factory settings
• various additional functions are available e.g. 0...10V connection for boiler control
Description of controller
7
1
2
3
Mixed heat circuit with buffer
Mixed heat circuit with buffer and domestic hot water buffer
Mixed heat circuit and domestic hot water buffer
Caution
M
M
M
In heating installations where domestic hot water is not needed, the DHW heat-
ing can be deactivated in menu 4 „Operating mode“.
Inheatinginstallationswithoutbu󰀨erthebu󰀨ersensorhastoinstalledinanap-
propriate position ahead of the mixer.
B.6 Hydraulic variants
Description of controller
Caution
The following illustrations should be viewed only as schematic dia-
grams showing the respective hydraulic systems, and do not claim to
be complete. The controller does not replace safety devices under any
circumstances.Dependingonthespecicapplication,additionalsystem
componentsandsafetycomponentsmaybemandatory,suchascheck
valves, non-return valves, safety temperature limiters, scalding protec-
tors, etc., and must therefore be provided.
8
C.1.1
C.1.2
Caution
C.1 Wall installation
Install the controller only in dry areas and under the ambient conditions descri-
bedunderB.1„Specications“.Carryoutthefollowingsteps1-8.
1. Unscrew cover screw completely
2. Carefully pull upper part of housing
from lower part.
3. Set upper part of housing aside, being
sure not to touch the electronics when
doing so.
4. Hold the lower part of the housing up
totheselectedpositionandmarkthe3
mountingholes.Makesurethatthewall
surface is as even as possible so that
the housing does not become distorted
when it is screwed on.
5. Using a drill and size 6 bit, drill 3 holes
atthepointsmarkedonthewalland
push in the plugs.
6. Insert the upper screw and screw it in
slightly.
7. Fit the upper part of the housing and
insert the other two screws.
8. Align the housing and tighten the three
screws.
Installation
10
Installation
C.3 Installing the temperature sensors
C.4 Installation of the additional functions via clamps Z1/Z2
Der Regler arbeitet mit Pt1000-Temperaturfühlern, die für eine gradgenaue Tempera-
turerfassungsorgen,umdieAnlagenfunktionregeltechnischoptimalsicherzustellen.
Caution
If desired the sensor cables can be extended to a maximum of 30m
using a cable with a cross-section of at least 0.75mm².
Makesurethatthereisnocontactresistance!
Position the sensor precisely in the area to be measured!
Onlyuseimmersion,pipe-mountedorat-mountedsensorsuitablefor
thespecicareaofapplicationwiththeappropriatepermissibletempe-
rature range.
Caution
S6isbydefaultconnectedbyjumperwiththeterminalblockS-toena-
ble the heating circuit functions. If the jumper is removed, the heating
circuitisswitchedo󰀨.WhenconnectingtheremoteadjusterRC21the
jumper has to be removed. If a third party external thermostat is con-
nected,itselectricalcontactshastobeoatingandoflowresistance=
0 Ohm.
The temperature sensor cables must be routed separately from mains
voltage cables, and must not, for example, be routed in the same cable
duct!
Caution
The instructions are supplied with the expansion board. The installation
has to be commenced accordingly and all warnings have to be obser-
ved.
Caution
11
Caution
Left-hand terminal compartment
only for low voltage if max. 12VAC/
DC Danger
Right-hand terminal com-
partment only for mains volt-
ages of 230VAC 50-60Hz
Low voltage max. 12VAC/DC
connection in the left-hand terminal compart-
ment!
Terminal: Connection for:
- JumperterminalblockS-
S1 outdoor
S2 heating circuit
S3 Domestic hot water
S4 bu󰀨er
S5 indoor sensor
S6 remote adjuster*
+ not used
Z1 Option / add. function
Z2 Option / add. function
UseterminalblockS-forconnectingthe
sensor earths of S1-S6.
The polarity of the sensors is freely selecta-
ble.
The sensors S4-S6 are optional, depending
on the hydraulic variant chosen.
Mains Voltage 230VAC 50-60Hz connec-
tion in the right-hand terminal compartment.
Terminal: Connection for:
N JumperterminalblockN
L Mains phase conductor L
R1 Heat circuit pump
R2 Mixer open
R3 Mixer close
R4 Valve/DHW pump
R5 add. heating
R5I add. heating
The PE protective conductor must
beconnectedtothePEmetalterminalblock!
*Note:IftheremoteadjusterRC21oradi󰀨erentexternaloatingthermostatiscon-
nected, the bridge at S6 has to be removed.
Connections Mains Voltage:
- Protective conductor PE metal terminal
block
-NeutralconductorterminalblockN
- Mains phase conductor L
- Switch output R1-R4
- Floating contact at R5/R5I
Caution: Only suitable for 230V!
Connections low voltage:
- Temperature sensors S1 - S6
(polarity freely selectable)
- Optional additional functions Z1/Z2
D Electrical terminals
Installation
12
Examples of display symbols:
Heating circuit pump
(rotates when active)
Heating circuit mixer
(blackwhenactive)
HC -Day mode (Time progr.)
HC-Night mode (Time progr.)
HC-Comfort mode (Time progr.)
Day mode
Night mode
Day mode due to RC21
Night mode due to RC21
Additional heating
Reference value mode
Reference value 14 day
externalthermostato󰀨
Warning / Error message
New information available
(1)
(2)
(3)
(4)
The display (1), with its extensive text and
graphics mode, is almost self-explanatory,
allowing easy operation of the controller.
The LED (2) lights up green when a relay
is switched on.
The LED (2) lights up red when operating
mode„O󰀨“isset.
TheLED(2)ashesslowlyredinthe
operating mode „Manual“.
TheLED(2)ashesquicklyredwhenan
error is present.
Entriesaremadeusingfourkeys(3+4),to
whichdi󰀨erentfunctionsareassignedde-
pendingonthesituation.The„esc“key(3)
is used to cancel an entry or to exit a menu.
If applicable there will be a request for con-
firmation as to whether the changes which
have been made should be saved.
The function of each of the other three
keys(4)isshowninthedisplaylinedirect-
lyabovethekeys;theright-handkeyis
generallyhasaconrmationandselec-
tion function.
Examplesofkeyfunctions:
+/- =enlarge/shrinkvalues
▼/▲ =scrollmenudown/up
yes/no =approve/reject
Info =additionalinformation
Back =topreviousscreen
ok =conrmselection
Conrm =conrmsetting
Operation
E.1 Display and input
14
1. Measurements
4. Operating
7. Protections
2. Statistics
5. HC settings
8. Special functions
3. Times
6. DHW settings
9. Menu lock
10. Service Data
11. Language
E.4 Menu sequence and menu structure
Operation
The graphics or overview mode appears
whennokeyhasbeenpressedfor2mi-
nutes, or when the main menu is exited by
pressing „esc.
Pressingakeyingraphicsoroverview
modetakesyoudirectlytothemainmenu.
The following menu items are then availa-
ble for selection there:
Current temperature values with
explanations
Function control of the system with operating
hours, etc.
Operating times for heating circuit and hot water,
settingtheclock
Operating times for heating circuit and hot water,
manual mode
Set parameters for the heating circuit
Anti-seizing protection, Frost prot.,
Anti-Legionella activation
Sensor calibration, Remote adjuster, Mixer,
etc.
Against unintentional setting changes at
critical points
For diagnosis in the event of an error
Selection of the menu language
Set parameters for Domestic Hot Water
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel HCC5 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel HCC5 in the language / languages: English as an attachment in your email.

The manual is 1.34 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel HCC5

Sorel HCC5 User Manual - German - 36 pages

Sorel HCC5 User Manual - French - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info