8.10 Menu „02 Settings“ for
Programme 10
At first, the same settings as in programme 1 must be done and
afterwards, the parameters for the charge of the second storage
tank must be set. Generally, there is no parallel operation of pump
R1 and pump R2.
Further adjustments for the priority settings must be done under
the item 10.2.
Tmax S3
Desired maximum solar temperature of storage tank 2 at sensor
S3. If the set temperature is exceeded at S3, the pump at R2
switches off and the storage tank is not charged any longer at
what the shift hysterese amounts 2°C.
Setting range:0...120°C Default value: 60°C
T R2
Here the temperature difference must be set which must be
exceeded between the collector sensor and the sensor S3 of
the second storage tank for the solar heat charge///transfer into
the second storage tank via the pump R2 to begin.
The heat is charged///transferred into this storage tank until the
temperature difference has fallen to 1/3 of the set value.
Setting range:6...18K Default value: 10K
Priority
It must be set which storage tank (storage sensor) shall be
charged with priority. The charge of the lower-level storage tank
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage tank.
Setting range:S2 / S3 Default value: S2
Tnom
The lower-level storage tank is not charged until the set Tnom
value is exceeded at the storage sensor of the prior storage tank.
Setting range:0...90°C Default value: 30°C
8.11 Menu „02 Settings“ for
Programme 11
At first, the same settings as in programme 1 must be done and
afterwards, the additional difference for the charge into the
sequence storage tank must be set.
Tmin S2
The set minimum storage temperature must be exceeded in the
solar storage tank at S2 for a heat discharge into the sequence
storage tank to be released.
Setting range:0...90°C Default value: 50°C
Tmax S3
Desired maximum storage temperature at sensor S3 in the
sequence storage tank. If the set temperature is exceeded at
S3, the pump at R2 switches off at what the shift hysterese
amounts 2°C.
Setting range:0...120°C Default value: 60°C
T R2
Here the temperature difference must be set which must be
exceeded between the solar storage sensor S2 and the sequence
storage sensor S3 for a heat discharge into the sequence storage
tank to begin.
The heat is recharged until the temperature difference has fallen
to 1/3 of the set value.
Setting range:6...18K Default value: 10K
8.6 Menu „02 Settings“ for
Programme 6
At first, the same settings as in programme 1 must be done and
afterwards, the parameters for the second storage zone of the
storage tank must be set. Further adjustments for the priority
settings must be done under the item 10.2.
Tmax S3
Desired maximum solar storage tank temperature at the upper
storage sensor S3. If the set temperature is exceeded at sensor
S3, the valve at R2 switches off at what the shift hysterese
amounts 2°C.
Setting range:0...120°C Default value: 60°C
Priority
It must be set which storage tank area (storage sensor) shall be
charged with priority. The charge of the lower-level storage part
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage area.
Setting range:S2 / S3 Default value: S2
8.7 Menu „02 Settings“ for
Programme 7
The same settings as in programme 1 must be done. After
exceeding of the difference „T R1“, the primary pump R2
switches on, though.
The secondary pump R1 does not switch on before the
temperature at the forerun sensor S3 is higher than at the storage
sensor S2. Pumps R1 and R2 switch off via sensors S1 and S2.
The rotational speed of the secondary pump R1 is controlled via
the forerun sensor S3 and the storage sensor S2.
8.8 Menu „02 Settings“ for
Programme 8
The same settings as in programme 1 must be done. The set
value of the minimum collector temperature „Tmin S1“ is for both
collector areas. The warmer collector is always perfused via the
change-over valve R2 when the solar pump R1 is active. The
change-over hysterese amounts 8°C.
The reference sensor to control the rotational speed and to switch
off the solar pump R1 is always the sensor of the collector area
which is being perfused.
8.9 Menu „02 Settings“ for
Programme 9
At first, the same settings as in programme 1 must be done and
afterwards, parameters for the charge of the second storage tank
must be set. Further adjustments for the priority settings must
be done under the item 10.2.
Tmax S3
Desried maximum solar temperature of storage tank 2 at sensor
S3. If the set temperature is exceeded at S3, the valve at R2
switches off and the storage tank is not charged any longer at
what the shift hysterese amounts 2°C.
Setting range:0...120°C Default value: 60°C
Priority
It must be set which storage tank (storage sensor) shall be
charged with priority. The charge of the lower-level storage tank
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage tank.
Setting range:S2 / S3 Default value: S2
Tnom
The lower-level storage tank is not charged until the set Tnom
value is exceeded at the storage sensor of the prior storage tank.
Setting range:0...90°C Default value: 30°C
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel DR3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel DR3 in the language / languages: English as an attachment in your email.

The manual is 0.16 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel DR3

Sorel DR3 User Manual - German - 8 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info