11 Troubleshooting
SMA Solar Technology AG
Operating manualSTP3-6-3AV-40-BE-en-1272
Event number Message, cause and corrective measures
7347
Incompatible file
The configuration file is not suitable for this inverter.
Corrective measures:
Ensure that the selected configuration file is suitable for this inverter.
Retry import.
7348
Incorrect file format
The configuration file is not of the required format or is damaged.
Corrective measures:
Ensure that the selected configuration file is of the required format and is
not damaged.
Retry import.
7349
Incorrect login rights for configuration file
The user group logged in does not have the user rights necessary to be able
to import a configuration.
Corrective measures:
Log in as Installer.
Import configuration file again.
7350
Transfer of a configuration file has started
The configuration file is being transferred.
7351
Update WLAN
The inverter is updating the WLAN module.
7352
Update of WLAN not successful
The update of the WLAN module failed.
Corrective measures:
Retry update.
If this message is displayed again, contact the Service (see Section14,
page96).
7353
Update time zone database
The inverter is updating the time zone database.
72


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Tripower 4.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Tripower 4.0 in the language / languages: English as an attachment in your email.

The manual is 2,37 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Tripower 4.0

SMA Sunny Tripower 4.0 User Manual - German - 104 pages

SMA Sunny Tripower 4.0 User Manual - Dutch - 106 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info