Event number Message, cause and corrective measures
701
Frq. not permitted > Check parameter
The power frequency is not within the permissible range. The inverter has dis-
connected from the utility grid.
Corrective measures:
If possible, check the power frequency and observe how often
fluctuations occur.
If fluctuations occur frequently and this message is displayed often,
contact the grid operator and request approval to change the operating
parameters of the inverter.
If the grid operator gives his approval, discuss any changes to the
operating parameters with Service (see Section11 "Contact", page67).
1001
L/N swapped > Check connection
The connection of L and N is swapped.
Corrective measures:
Ensure that L and N are correctly connected (see installation manual).
1302
Waiting for grid voltage > Installation failure grid connection > Check
grid and fuses
L or N not connected.
Corrective measures:
Ensure that L and N are connected (see installation manual).
Ensure that the AC conductors are not damaged and correctly connected
(see installation manual).
Make sure that the circuit breaker is switched on.
1501
Reconnection fault grid
The changed country data set or the value of a parameter you have set does
not correspond to the local requirements. The inverter cannot connect to the
utility grid.
Corrective measures:
Ensure that the country data set has been configured correctly. To do this,
select the parameter Set country standard and check the value.
8 Troubleshooting
SMA Solar Technology America LLC
User ManualSB30-77-1SP-US-40-BA-en-1140
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 6.0-US at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 6.0-US in the language / languages: English as an attachment in your email.

The manual is 2,73 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info