7.4 Commissioning the Inverter
Requirements:
The inverter must be correctly mounted.
The circuit breaker must be correctly rated and mounted.
All cables must be completely and correctly connected.
Unused DC inputs must be sealed using the corresponding DC connectors and sealing plugs.
The country data set must be set correctly for the country or the purpose.
Procedure:
1. Insert the lower enclosure lid from above and
flip it down. The screws must protrude from the
lower enclosure lid.
2. Tighten all screws of the lower enclosure lid
using an Allen key (AF3) in the order 1 to 6
(torque: 2Nm ± 0.3Nm).
Useful hint: If the screws fall out of the lower
enclosure lid, insert the short screw in the upper
middle hole and the five long screws in the other
holes.
3. If the ESS is available, plug it in. The ESS must be aligned parallel to and flush with the
enclosure.
4.
Currents in the DC cabling after plugging in the ESS
After plugging in the ESS, DC currents may occur in the DC cabling, even when there is
no AC-side supply. This is not an error but normal behavior of the inverter when in
operation.
5. Attach the supplied warning labels so that they are clearly visible on the disconnection point
on the AC side.
6. Switch on the circuit breaker.
7. If an external DC load-break switch is installed, switch it on.
8. If the multifunction relay is used, connect the supply voltage to the load.
All three LEDs start to glow and the start-up phase begins. The start-up phase may take several
minutes.
7 Commissioning
SMA Solar Technology AG
Operating ManualSB30-50TL-21-BE-en-1134
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 3600TL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 3600TL in the language / languages: English as an attachment in your email.

The manual is 2,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 3600TL

SMA Sunny Boy 3600TL User Manual - Dutch - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info