6.3.3 Connecting Additional Grounding
If additional grounding or equipotential bonding is required locally, you can connect additional
grounding to the inverter. This prevents touch current if the grounding conductor at the terminal for
the AC cable fails.
Cable requirement:
Grounding cable cross-section: max. 10mm²
Procedure:
1. Strip the grounding cable insulation.
2. Release the screw using an Allen key (AF4) until
the grounding cable can be led under the
clamping bracket.
3. Feed the grounding cable under the clamping bracket. Position the grounding conductor on
the left-hand side.
4. Tighten the clamping bracket with the screw and conical spring washer (torque: 6Nm). The
teeth of the conical spring washer must face the clamping bracket.
6.4 DC Connection
6.4.1 Requirements for the DC Connection
Requirements for the PV modules per input:
All PV modules must be of the same type.
All PV modules must be aligned and tilted identically.
On the coldest day based on statistical records, the open-circuit voltage of the PV array must
never exceed the maximum input voltage of the inverter.
The same number of series-connected PV modules must be connected to each string.
The maximum input current per string must be maintained and must not exceed the through-
fault current of the DC connectors (see Section11 "Technical Data", page47).
The thresholds for the input voltage and the input current of the inverter must be adhered to
(see Section11 "Technical Data", page47).
6 Electrical Connection
SMA Solar Technology AG
Operating Manual 27SB30-50TL-21-BE-en-11
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 3600TL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 3600TL in the language / languages: English as an attachment in your email.

The manual is 2,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 3600TL

SMA Sunny Boy 3600TL User Manual - Dutch - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info