SMA Solar Technology AG 10 Troubleshooting
Installation Manual SB13_21TL-IA-en-65 47
10.2.3 Errors, Disturbances, Warnings
Errors, disturbances and warnings are shown in the display and start in the first line with the word
"Error", "Fault" or "Warning". In the second line of the display, the cause of the error, fault or warning
is shown.
MPP Peak The inverter is operating in MPP mode above its nominal power.
MPP-Search The inverter is calculating the MPP.
Grid
monitoring
Grid monitoring. If irradiation is low or an error has occurred, this message
appears before the inverter is connected to the electricity grid.
Offset Offset alignment of the measurement electronics
Riso Measuring the insulation resistance of the PV plant
Disturbance The inverter has detected a disturbance. The specific disturbance message is also
displayed (see Section10.2.3 "Errors, Disturbances, Warnings", page47).
Stop Operation interrupted
V-Const Constant voltage mode.
Waiting The conditions for grid connection are not (yet) fulfilled.
Message Description and Corrective Measures
!PV-Overvoltage!
!DISCONNECT DC!
Overvoltage at the DC input. The inverter may be destroyed. This message
is additionally highlighted by rapid flashing of the backlight.
Corrective measures:
1. Disconnect the miniature circuit-breaker.
2. If there is an external DC switch-disconnector, turn it off.
3. If an ESS is in use, disconnect it.
4. Release and disconnect all DC connectors using a screwdriver
(blade width 3.5 mm).
Insert a screwdriver into one of the side slots.
–Pull the DC connectors out.
5. Check whether the DC voltage is below the maximum input voltage of
the inverter. If the DC voltage is below the maximum input voltage of
the inverter, reconnect the DC connectors to the inverter.
If the DC voltage is above the maximum input voltage of the inverter,
check the PV plant design or contact the installer of the PV array.
6. If this message recurs frequently, disconnect the inverter from voltage
sources (see Section 8) and contact the SMA Service Line.
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 2100T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 2100T in the language / languages: English as an attachment in your email.

The manual is 1,66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info