11 Troubleshooting
SMA Solar Technology AG
Operating manualSBxx-1VL-40-BE-en-1374
Event number Message, cause and corrective measures
9003
Grid parameter locked
Changes to the grid parameters are now blocked. In order to be able to make
changes to the grid parameters, from now on you must log in using the SMA
Grid Guard code.
9005
Changing of grid parameters not possible > Ensure DC supply
This error can have the following causes:
The parameters to be changed are protected.
The DC voltage at the DC input is not sufficient to run the main CPU.
Corrective measures:
Enter the SMA Grid Guard code.
Ensure that at least the DC start voltage is available (green LED is
flashing, pulsing or glowing).
9007
Abort self-test
The self-test (Italy only) was terminated.
Corrective measures:
Ensure that the AC connection is correct.
Restart the self-test (see Section7.4, page41).
10110
Time synchronization failed [x]
No time information could be called up from the set NTP server.
Corrective measures:
Ensure that the NTP server was configured correctly.
Ensure that the inverter is integrated into a local network with Internet
connection.
10248
[Interface]: network busy
The network is busy. Data exchange between the devices is not at an optimum
and is greatly delayed.
Corrective measures:
Increase the query intervals.
If necessary, reduce the number of devices in the network.
10249
[Interface]: network overloaded
The network is overloaded. There is no data exchange between the devices.
Corrective measures:
Reduce the number of devices in the network.
If necessary, increase the data query intervals.
74


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 2.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 2.0 in the language / languages: English as an attachment in your email.

The manual is 1,49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 2.0

SMA Sunny Boy 2.0 User Manual - German - 98 pages

SMA Sunny Boy 2.0 User Manual - Dutch - 98 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info