6 Electrical Connection SMA Solar Technology AG
26 SB13_21TL-IA-en-65 Installation Manual
6.3 AC Connection
6.3.1 Requirements for the AC Connection
Cable requirements:
External diameter: 7 mm to 14 mm
Conductor cross-section: max. 2.5 mm²
Stripping length: 5 mm
The cable must be dimensioned in accordance with any local and national guidelines on cable
dimensions which specify requirements for the minimum conductor cross-section. Factors
influencing cable dimensioning are e.g.: nominal AC current, type of cable, type of routing,
cable bundling, ambient temperature and maximum specified line losses (for calculation of line
losses, see design software "Sunny Design" from software version 2.0 at www.SMA-Solar.com).
Switch-disconnector and cable protection:
In plants with multiple inverters, each inverter must be protected with a separate miniature
circuit-breaker. Make sure that the maximum permissible fuse protection is observed
(see Section12 "Technical Data", page60). That prevents residual voltage being present in the
cable after disconnection.
Loads installed between the inverter and the miniature circuit-breaker must be fused separately.
Residual-current monitoring unit:
If an external residual-current device is a mandatory requirement, install a device that trips at a
residual current of 100 mA or higher (for information on choice of residual-current devices,
see Technical Information "Criteria for Selecting a Residual-Current Device" at
www.SMA-Solar.com).
Overvoltage Category
The inverter can be deployed in grids of installation category III or lower, as defined under
IEC 60664-1. This means that the inverter can be permanently connected at the grid-connection point
in a building. In installations involving long cable routes outdoors, additional overvoltage-reducing
measures must be taken so that the overvoltage category is reduced from IV to III (see Technical
Information "Overvoltage Protection" at www.SMA-Solar.com).
Damage to the inverter through use of screw-type fuses as switch-disconnectors
Screw-type fuses (e.g., DIAZED or NEOZED fuses) do not have load disconnection properties and
may damage the inverter if it is disconnected under load.
Do not use screw-type fuses as switch-disconnectors.
Use a switch-disconnector or miniature circuit-breaker as a load disconnection unit
(for information and examples for designing, see Technical Information
"Miniature Circuit-Breaker" at www.SMA-Solar.com).
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 1600TL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 1600TL in the language / languages: English as an attachment in your email.

The manual is 1,66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 1600TL

SMA Sunny Boy 1600TL User Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info