F14
Type of heating system
1
0
1
2
Convectors
Radiators
Underfloor
F15
Min. temperature differential between flow temperature and
room temperature set value with convectors (F14)
6
0…30
°C
5.8.3 Parameter settings group H - „D.h.w.“
No. Function Recomm.
setting
Range
Remarks Unit
Values
set
H1
D.h.w. charging time
1
0
1
2
PROG1
PROG2
24h/day
H2
Enabling of d.h.w. charging
1
0
1
Once/day
Several times/day
H3
D.h.w. circulating pump
1
0
1
2
PROG1
PROG2
24h/day
H4
Enabling of d.h.w. circulating pump during d.h.w. charging
0
0
1
Enabled
Disabled
H5
Boost with d.h.w. charging
16
0…30
°C
H6
Set value of flow temperature during d.h.w. charging
1
0
1
Max. selection
D.h.w. charging set value
H7
Switching differential d.h.w.
8
0…15
°C
H8
D.h.w. priority
0
0
1
2
None (parallel)
Shifting
Absolute
H9
Delay time for d.h.w. priority, shifting
3
0…15
min
H10
Heating circuit locking time with d.h.w. charging, shifting
10
0…150
min
H11
Min. actual value of flow temp. with d.h.w. charging (for M4)
50
8…119.5
°C
H12
D.h.w. charging detector (B71)
0
0
1
No
Yes
H13
Set value of d.h.w. temperature during the legionella
function
65
0
1…80
Passive
Active
°C
H14
Pump overrun time for M4 (after M3)
0
0...15
min
5.8.4 Parameter settings group U - „Precontroller“
No. Function Recomm.
setting
Range
Remarks Unit
Values
set
U1 Control gain KP of primary control valve Y1 3
1…25.5
U2 Integral action time of primary control valve Y1 60
30/60/
120/240
s
U3 Running time of primary control valve Y1 120
0 …255
s
U4 Min. limitation of secondary flow temperature 0
0…119.5
°C
U5 Max. set value of return temperature, constant range 50
8…119.5
°C
U6 Inflection point constant/shifting max. set value of retur temp. 10
-10…20
°C
U7 Slope of shifting range max. set value of return temperature 7
0…39.5
U8 Max. set value of return temperature with d.h.w. charging 50
8…119.5
°C
U9 Limitation of return temperature differential between primary
and secondary circuit in heating mode
0
0
0.5…50
Passive
Active
°C
U10 Max. limitation of pulse rate per minute 0
0
1…2047
Passive
Active
U11 Integral action time for U8, U9, U10 16
4/8/16/32
min
U12 Min. limitation of primary flow rate (hydraulic creep) 4
0…15
Stroke%
U13 Locking time after min. limitation (U12) 6
0…15
min
U14 P
open
for valve Y11
Control gain (KP), multiplied by running time open,
divided by 5
72
0…255
Controlled system oscilates:reduce
setting value/ Controlled system
too slow: increase setting value
U15 Integral action time of valve Y11 60
30/60/
120/240
s
U16
Pclosed
for valve Y11
Control gain (KP), multiplied by running time close,
divided by 5
72
0…255
Controlled system oscilates:reduce
setting value/ Controlled system
too slow: increase setting value
U17
Limitation of return temperature differential between primary
and secondary circuit during d.h.w. charging
0
0
0.5...50
Passive
Active
°C
U18 (Function according to H5) -
U19 (Function according to H7) -
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info