670459
9
Zoom out
Zoom in
Previous page
1/21
Next page
CE1G2406E 9
5.4 Plant diagram VG3
Heating circuit control with mixing valve and heating circuit pump, d.h.w. control with d.h.w. pump
5.4.1 Parameter settings group C - „General parameters“
No. Function Recomm.
setting
Remarks Unit Values set
C1 Type of plant 3
Acc. to plant diagram VG…
C2 Bus address 0
Standalone
Slave
Master
C3 Set value boost mixing circuit and H-bus master 10
°C
C4 Pump overrun time 4
min
C5 Display 1
Outside temperature
Time of day
C6 Pump Q1 0
Heating circuit pump
Main pump
C7 H4 function 0
Ymin function
Min. flow temp. acc. to
U4
C8
Not used
-
C9
Not used
-
5.4.2 Parameter settings group F - „Heating circuit“
No. Function Recomm.
setting
Remarks Unit Values set
F1 Min. limitation of flow temperature 8
°C
F2 Max. limitation of flow temperature 95
°C
F3 Room temperature detector 1
Passive
Active
F4 Room temperature compensation 4
Passive
Active
F5 Optimum start control and quick setback with no room unit 8
Smaller for buildings with
poor insulation
F6 Switching differential room temp. limitation with room unit 0
¼ °C
F7 Type of building structure 1
Heavy
Light
F8 Adaptation of heating curve 0
Passive
Active
F9 Frost protection for the plant 1
Passive
Active
F10 Max. forward shift for optimum start control 0
Passive
Active
min
F11 Max. forward shift for optimum stop control 0
Passive
Active
min
F12 ECO extension 0
min
F13 Room set value temperature boost with boost heating 5
°C
F14 Type of heating system 1
Convectors
Radiators
Underfloor
V
G3
B71
B1
A6
M1
Y11
B11
T
T
T
T
B9
Y1
B7
M3
T
T
2406S16
BW1
B3
B31
M5
T
T
2406S21
BW2
B3
B31
M5
M4
T
T
T
B71
2406S22
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info