4 CE1G2406E
F14 Type of heating system 1 0
1
2
Convectors
Radiators
Underfloor
F15 Min. temperature differential between flow temperature and
room temperature set value (F14)
6 0…30 °C
5.1.4 Parameter settings group H - „D.h.w.“
No. Function Recomm.
setting
Range
Remarks
Unit Values
set
H1 D.h.w. charging time 1 0
1
2
PROG1
PROG2
24h/day
H2 Enabling of d.h.w. charging 1 0
1
Once/day
Several times/day
H3 D.h.w. circulating pump 1 0
1
2
PROG1
PROG2
24h/day
H4
No function
-
H5 (Function acc. to U18) -
H6
No function
-
H7 (Function acc. to U19) -
H8 D.h.w. priority 0 0
1
2
None (parallel)
Shifting
Absolute
H9 Delay time for d.h.w. priority, shifting 3 0…15 min
H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min
H11
Not used
-
H12
Not used
-
H13
Not used
-
H14
Not used
-
5.1.5 Parameter settings group U - „Precontroller“
No. Function Recomm.
setting
Range
Remarks
Unit Values
set
U1 Control gain KP of primary control valve Y1 3 1…25.5
U2 Integral action time of primary control valve Y1 60 30/60/
120/240
s
U3 Running time of primary control valve Y1 120
0 …255
s
U4 Min. limitation of secondary flow temperature 0
0…119.5
°C
U5 Max. set value of return temperature, constant range 50
8…119.5
°C
U6 Inflection point constant/shifting max. set value of return
temperature
10
-10…20
°C
U7 Slope of shifting range max. set value of return temp. 7
0…39.5
U8 Max. set value of return temperature with d.h.w. charging 50
8…119.5
°C
U9 Limitation of return temperature differential of primary and
secondary circuit in heating mode
0
0
0.5…50
Passive
Active
°C
U10 Max. limitation of pulse rate per minute 0
0
1…2047
Passive
Active
U11 Integral action time for U8, U9, U10
4/8/16/32
min
U12 Min. limitation of primary flow rate (hydraulic creep) 4
0…15
Stroke %
U13 Locking time after min. limitation (U12) 6
0…15
min
U14 P
open
for valve Y11
Control gain (KP), multiplied by running time open, divided
by 5 For SKD32.21 (30 s open/10 s close), SQS35.53
(35 s open/close)
SKD:15
SQS:17
0…255
Contr. system oscillates:
reduce setting value
Contr. system too slow:
increase setting value
U15 Integral action time of valve Y11 60
30/60/
120/240
s
U16
Pclosed
for valve Y11
Control gain (KP), multiplied by running time close, divided
by 5 For SKD32.21 (30 s open/10 s close), SQS35.53
(35 s open/close)
SKD: 5
SQS:17
0…255
Contr. system oscillates:
reduce setting value
Contr. system too slow:
increase setting value
U17 Limitation of return temperature differential between primary
and secondary circuit during d.h.w. charging
0
0
0.5...50
Passive
Active
°C
U18 Derivative action time, d.h.w. charging, VG0 1 0...15 s
U19 Authority of cold water detector B3, VG0
0.5 °C per controller sampling rate of 2 s
4 0...15
4


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info