Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 12 Function block: Setpoint return temperature limitation 15.03.2011
12.3.2 Mode of operation
If the return temperature falls below the set minimum limit value, the temperature
differential of minimum limit value and actual value is integrated. From this, a criti-
cal locking signal is generated and forwarded to the connected consumers. This
causes the loads to reduce their setpoints, aimed at consuming less energy.
If the return temperature returns to a level above the minimum limit value, the inte-
gral is reduced, resulting in a reduction of the critical locking signal. The connected
consumers increase their setpoints again.
When the integral reaches the value of zero, minimum limitation of the return tem-
perature becomes inactive, in which case the critical locking signal is zero.
If minimum limitation of the return temperature is active, the display shows
.
Minimum limitation of the return temperature can be deactivated.
Chapter 17.4.6 "Locking signal gain" provides information on who receives the
critical lockin
g signal and how the consumers respond to it.
The minimum limit value is to be set on operating line 101.
Setting --- = inactive.
52


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP351 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP351 in the language / languages: English as an attachment in your email.

The manual is 1,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP351

Siemens RVP351 User Manual - German - 108 pages

Siemens RVP351 User Manual - French - 112 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info