Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 9 Function block: Space heating 15.03.2011
9 Function block: Space heating
This function block performs the automatic ECO function, the optimization
functions with boost heating and quick setback, plus room influence.
9.1 Operating lines
Line Function, parameter Factory setting (range) Unit
61 NORMAL heating limit (ECO day) 17.0 (--.- / 5...25) °C
62 REDUCED heating limit (ECO night) 5.0 (--.- / –5...25) °C
63 Building time constant 20 (0...50) h
64 Quick setback 1 (0 / 1)
65 Room temperature source A (0…3 / A)
66 Type of optimization 0 (0 / 1)
67 Maximum heating up period 00:00 (00:00...42:00) h
68 Maximum early shutdown 0:00 (0:00...6:00) h
69 Maximum limitation room temperature --.-- (--.- / 0...35) °C
70 Influence of room temperature (gain factor) 4 (0...20)
71 Boost of room temperature setpoint on boost heating 5 (0...20) °C
9.2 Automatic ECO function
The automatic ECO function controls space heating depending on demand. It gives
consideration to the progression of the room temperature depending on the type of
building structure as the outside temperature varies. If the amount of heat stored in
the house or building is sufficient to maintain the room temperature setpoint cur-
rently required, the heating is switched off.
The automatic ECO function ensures that the heating system operates only, or
uses energy only, when indeed required.
9.2.1 Compensating and auxiliary variables
The compensating and auxiliary variables considered by the automatic ECO func-
tion are the progression of the outside temperature and the heat storage capacity
of the building.
The following variables are taken into account:
The building time constant: This is a measure of the type of building structure
and indicates how quickly the room temperature would vary if the outside tem-
perature suddenly changed. The following guide values can be used for setting
the building time constant: 10 hours for light, 25 hours for medium, and 50 hours
for heavy building structures
The current outside temperature (T
A
)
The composite outside temperature (T
AM
). It is the mean value of …
the current outside temperature,
the outside temperature filtered by the building time constant
Compared with the current outside temperature, the composite outside tempera-
ture is attenuated. Hence, it represents the impact of short-time outside tempera-
ture variations on the room temperature as they often occur during intermediate
seasons (spring and autumn).
The attenuated outside temperature (T
AD
): It is generated by double-filtering the
current outside temperature by the building time constant. This means that – in
comparison with the current outside temperature – the attenuated outside tem-
perature is considerably dampened. This ensures that no heating is provided in
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP351 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP351 in the language / languages: English as an attachment in your email.

The manual is 1,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP351

Siemens RVP351 User Manual - German - 108 pages

Siemens RVP351 User Manual - French - 112 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info