Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 4 Acquisition of measured values 15.03.2011
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit. An error mes-
sage is delivered.
If both measuring circuits do not produce a valid measured value, 2 error mes-
sages are delivered. D.h.w. is no longer heated; the charging pump will be deacti-
vated.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in measuring circuit B31, an error message is delivered. D.h.w. is no longer
heated; the charging pump will be deactivated.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in one of the measuring circuits, an error message is delivered. The con-
troller continues to operate with the correctly working measuring circuit.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in both measuring circuits, 2 error messages are delivered. D.h.w. is no
longer heated; the charging pump will be deactivated.
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit, if possible. An
error message is not delivered.
If both measuring circuits do not produce a valid measured value, an error mes-
sage is delivered. D.h.w. is no longer heated; the charging pump and the collector
pump will be deactivated.
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit. An error mes-
sage is delivered.
If both measuring circuits do not produce a valid measured value, 2 error mes-
sages are delivered. D.h.w. is no longer heated; the charging pump and the collec-
tor pump will be deactivated.
If a measured value of the d.h.w. temperature is not available and the temperature
is queried, the QAW70 room unit displays ---.
4.7 Collector temperature (B6)
4.7.1 Type of sensor
The collector temperature is acquired by a Siemens sensor operating with a sens-
ing element LG-Ni1000 and an extended measuring range.
4.7.2 Error handling
In the event of an interruption of the measuring circuit, an error message is deliv-
ered with a delay of 12 hours and the collector pump is deactivated. This means
that solar d.h.w. heating is no longer provided.
2 storage tank sensors
(operating line 126 = 1)
1 storage tank thermostat
(operating line 126 = 2)
2 storage tank thermo-
stats (operating line
126 = 3)
1 storage tank sensor for
solar d.h.w. heating
(operating line 126 = 4)
2 storage tank sensors
for solar d.h.w. heating
(operating line 126 = 5)
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP351 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP351 in the language / languages: English as an attachment in your email.

The manual is 1,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP351

Siemens RVP351 User Manual - German - 108 pages

Siemens RVP351 User Manual - French - 112 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info