Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 17 Function block: Service functions and general settings 15.03.2011
17.4.4 Pump kick
To prevent pump seizing during longer off periods (e.g. in the summer), a periodic
pump kick can be activated on operating line 175. The input is either 0 or 1:
0 = no periodic pump kick
1 = weekly pump kick
If the pump kick is activated, all pumps run for 30 seconds, one after the other,
every Friday morning at 10:00, independent of all other functions and settings.
17.4.5 Winter-/summertime changeover
Changeover from wintertime to summertime, and vice versa, takes place automati-
cally. If international regulations change, the dates need to be reentered. The date
to be entered is the earliest possible changeover date. Changeover always takes
place on a Sunday.
If the start of summertime is specified as the "Last Sunday in March", the earliest
possible changeover date is March 25. Then, the date to be entered on operating
line 176 is 25.03.
If no winter-/summertime changeover is required, the 2 dates must be set so that
they coincide.
17.4.6 Locking signal gain
Functions "Maintained boiler return temperature", "Protective boiler startup" and
"D.h.w. priority" use locking signals that are forwarded to the heat exchangers and
consumers. With the heat exchanger and consumer controllers, operating line 173
(locking signal gain) can be used to set how intensely these controllers shall
respond to locking signals. The locking signal gain is adjustable from 0% to 200%.
Setting Response
0% Locking signal is ignored
100% Locking signal is adopted on a 1-to-1 basis
200% Locking signal is adopted as a double signal
There are 2 types of locking signals:
Uncritical locking signals
Critical locking signals
The response of the consumers depends on the type of load.
Uncritical locking signals are generated in connection with d.h.w. priority (absolute
and shifting) and only act on the heating circuits.
The response of the heating circuit depends on the type of heating circuit:
Heating circuit with mixing valve/2-port valve:
In the heating circuit, the flow temperature setpoint is reduced as a function of
the set locking signal gain. The mixing valve/2-port valve closes, the heating cir-
cuit pump continues to run
Heating circuit with pump:
When the uncritical locking signal reaches a defined value, the heating circuit
pump is deactivated, independent of the set locking signal gain. In plants using a
diverting valve, the valve is driven to the d.h.w. position
Example
Basics
Uncritical
locking signals
77


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP340 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP340 in the language / languages: English as an attachment in your email.

The manual is 1,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP340

Siemens RVP340 User Manual - German - 108 pages

Siemens RVP340 User Manual - French - 112 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info