Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.3.6 Control
Prerequisites for this type of control
Outside sensor connected
No room unit connected, or
Room authority set to 0 % or to Off if a room unit is connected
The compensating variable used for weather-compensated control is the composite
outside temperature. Assignment of the flow temperature setpoint to the compensating
variable is made via the selected heating curve. The room temperature is not taken into
consideration. This type of control is used primarily in plants or buildings where
several rooms are occupied at the same time
no room is suited as a reference room for the room temperature
Prerequisites for this type of control:
Room unit connected
No outside sensor connected, or
Room authority set to 100 % if an outside sensor is connected
If no outside sensor is connected, the setting potentiometer for the room authority is
inactive.
The compensating variable used for room temperature-compensated control is the
setpoint / actual value deviation of the room temperature. The room authority is gener-
ated based on this deviation. Also, an outside temperature of 0 °C is assumed and
taken into account when generating the setpoint.
When there is no temperature deviation in the room, the controller maintains the flow
temperature setpoint resulting from
0 °C outside temperature, and
the selected heating curve slope
Any room temperature deviation produces an instant parallel displacement of the se-
lected heating curve. The correlation between the extent of temperature deviation and
the degree of displacement is defined by the room authority, which is dependent on
the setpoint / actual value deviation of the room temperature
the selected heating curve slope
The purpose of room influence is to enable the controller to exactly reach and maintain
the respective setpoint.
This type of control provides PI control during the control process, the I-part ensures
that the required room temperature will be reached and maintained with no offset. .
This type of control is used primarily in plants or buildings where a room is suited as a
reference room for the room temperature.
Prerequisites for this type of control:
Outside sensor connected
Room unit connected
Room authority set in the range 0…100 %
The compensating variables used for weather-compensated control with room influence
are:
The composite outside temperature
The setpoint / actual value deviation of the room temperature
The setpoint of the flow temperature is continuously shifted in function of the composite
outside temperature (via the heating curve). Also, any room temperature deviation pro-
duces an instant parallel displacement of the heating curve. The correlation between
the extent of the temperature deviation and the degree of displacement is defined by
the room authority, which is dependent on
the selected authority
the setpoint / actual value deviation of the room temperature
the selected heating curve slope
Weather-compensated
control
Room temperature-
compensated control
Weather-compensated
control with room
influence
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English as an attachment in your email.

The manual is 0,75 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 Installation Guide - English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish - 26 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info