Building Technologies 74 319 0614 0 c 20.05.2008 4/26
- If it flashes, the detector wiring may be faulty
- If it is lit, the controller is overridden by a remote operation
facility (room unit or changeover switch). Set room unit to
operating mode
or open the external switch)
4. Set operating mode selector to
.
5. Set heating curve potentiometer
to 4 and setting knob
to +8 °C:
- Flow temperature must rise: burner on, valve open, heat-
ing circuit pump on (electro-thermal actuators respond with
a certain delay!)
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
6. Set operating mode selector to
.
7. Set heating curve to 0.25 and setting knob
to –8 °C:
- Burner must switch off (observe minimum running time of
4 minutes), valve must travel toward "colder", and heating
circuit pump must remain activated
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
Commissioning the remote operation facility
1. Set the controller's operating mode selector to one of the two
Auto positions
2. If a room unit is present: select operating mode
on the
room unit
- Check the "Override" LED on the controller: must be lit
- If not: check wiring of the room unit
3. If a changeover switch is present: close it (gives operating
mode
on the controller).
- Check the "Override" LED on the controller: must be lit.
- If not: check wiring of the changeover switch
Commissioning of D.h.w. heating
(only RVP211)
1. The D.h.w. temperature must be around 30 °C (check by
touching or use a measuring instrument).
2. Set the controller's operating mode selector to
.
3. Set setting knob
to 60 °C.
- D.h.w. temperature must rise: charging pump on or
changeover valve open
- If not: check wiring of the d.h.w. temperature detector and
the heating circuit pump, or the changeover valve
4. Set setting knob
to 10 °C (observe overrun time)
- Charging pump or changeover valve must switch off
- If not: check wiring of d.h.w. temperature detector
5. Reset setting knob
to 55 °C (factory-setting).
Setting elements
Refer to figure
3
on page 24
1 Opening for time switch
2 LED for "Override"
3 Operating mode selector
4 Setting knob for heating curve
5 Setting knob for setback
6 Setting knob for d.h.w. temperature (only RVP211)
7 Setting knob for normal room temperature
8 Coding switches
9 Setting potentiometer for authority of room temperature
and quick setback active / inactive
10 Setting potentiometer for max. limitation of flow or boiler
temperature
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Coding switches
Function Switch position on the left Symbol Symbol Switch position on the right
Type of regulating unit Control of a motorized valve
Control of a atmospheric or
forced draught burner
Type of control Three-position (modulating)
Two-position (on/off)
Frost protection Yes, frost protection
No, no frost protection
D.h.w. priority (only RVP211)
With priority (absolute). Underfloor
heating systems and boiler opera-
tions: always set to abs.!
No priority (parallel)
RVP211 with boiler temperature control:
Regulating unit for d.h.w. heating Changeover valve
Charging pump
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentiometer Function Setting range Guide value Notes
Switching differential
with two-position
control
1…20 K Burner control: 6 K
Authority of room
temperature on flow
temperature control
0…100 % authority
Off = quick setback is
inactive
50 % (quick setback
is active)
Plants with no room unit: setting is inactive
Plants with no outside detector:
Setting 0…100 % = quick setback is active
Setting Off = quick setback is inactive
Heating limit for ECO
automatic energy
saver
–10…+8 K (referred to
the room temperature
set value)
–3 K (gives a heat-
ing limit of 17 °C at a
room temperature
set value of 20 °C)
Off = function disabled
Max. limitation of flow
or boiler temperature
10…100 °C Guide value for un-
derfloor and ceiling
heating systems:
55 °C max.
Off = function disabled
Settings on the controller
Seal the transparent cover, if required.
Heating curve diagram: Refer to figure
4
on page 24
T
A
Outside temperature [°C]
1. Set heating curve as specified in the planning documen-
tation or in compliance with local practices.
2. Reset setting knob
to 0 (factory-setting, corresponds
to 20 °C room temperature).
3. Leave setting knob
to –6 °C (factory-setting).
4. Set operating mode selector to one of the two
Auto posi-
tions.
5. Set time switch as indicated in the operating instructions.
T
V
Flow temperature [°C]
4


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVP201 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVP201 in the language / languages: English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish as an attachment in your email.

The manual is 0,49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RVP201

Siemens RVP201 User Manual - English - 46 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info