Building Technologies 74 319 0619 0 a 17.04.2008 52/288
en
2 = bypass pump parallel to
burner stage 1
3 = bypass pump with control
via return temperature
sensor B7
100 Switching differen-
tial bypass pump
6 °C
(1…20)
...................°C
Function is of importance only if
operating line 99 = 3
Block “Setpoint of return temperature limitation”
101
Setploint of return
temperature limita-
tion / bivalent start-
ing point
--- °C
(--- / 0…140)
...................°C
Entry --- = function deactivated
For explanation of "bivalent",
refer to operating lines 103 and
104
Block "Type of limitation of return temperature"
102 Type of limitation of
return temperature
0
(0 / 1)
.........................
0 = minimal
1 = maximal
If the plant has a bypass pump
controlled via return tempera-
ture sensor B7, this setting is
inactive. In that case, the type of
limitation is always minimum
limitation
Block “Bivalent maximum limitation of return temperature”
103 Maximum setback
of boiler temp. set-
point
10 °C
(1…50)
...................°C
104 End point bivalent 60 °C
(0…140)
...................°C
2542D01
OpL101
OpL104
TRt
OpL103
BoSp
BoSp = Boiler setpoint
OpL = Operating line
TRt = Return temperature
52


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVL482 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVL482 in the language / languages: English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish as an attachment in your email.

The manual is 2,54 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info