Building Technologies 74 319 0618 0 a 17.04.2008 43/276
en
120 = flow alarm
140 = inadmissible bus address
(LPB) or plant type
Settings on the “Heating engineer” level
Press
and simultaneously for 3 seconds to activate the “Heating engineer” level for
selecting the plant type and the plant-related variables.
Selecting the plant type on operating line 51:
The required plant type must be selected on operating line 51 using buttons
and . This
activates all functions required for the respective type of plant and shows the associated operat-
ing lines.
A plant type is comprised of a space heating circuit (6 different types) and a d.h.w. circuit
(5 different types). The 2 types of circuits can be combined in 29 different ways. The following
plant diagrams show all possible combinations.
The controller's operating line 51 only accepts combinations that are possible.
Example of a setting:
2540Z02
1 = heating circuit type 1
2 = d.h.w. circuit type 2
51 Plant type 11
(10 … 65)
.........................
Type numbers in the following
section
Plant types
A6 Room unit E2 Load (room)
B1 Flow boiler temperature sensor LPB Data bus
B3 Flow temperature sensor for d.h.w. K6 Electric immersion heater
B31 D.h.w. storage tank temp. sensor / thermostat 1 M1 Heating circuit pump or circulating pump
B32 D.h.w. storage tank temp. sensor / thermostat 2 M3 Charging pump
B5 Room temperature sensor M4 Circulating pump
B6 Collector sensor M5 Collector pump
B7 Return temperature sensor (primary circuit) N1 Controller RVL481
B71 Return temperature sensor (secondary circuit) Y1 Heating circuit valve
B9 Outside sensor Y3 Changeover valve
E1 Heat source (boiler / heat exchanger) Y7 D.h.w. valve
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RVL481 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RVL481 in the language / languages: English, German, Dutch, Danish, French, Italian, Swedish, Spanish, Finnish as an attachment in your email.

The manual is 2,5 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info