4/18 29.05.2002 CE1G2261xx
Sollten im Referenzraum thermostatische
Heizkörperventile installiert sein, müssen diese
vollständig geöffnet werden.
Die örtlichen Vorschriften für Elektroinstallationen sind
einzuhalten.
Commissioning
1. Mounting
Remove controller from its base by proceeding according
to Fig. A. For mounting, refer to Figs. B and C.
(also refer to “Mounting notes“).
2. Check wiring
For the electrical connections, refer to “Connection
diagram“ (also refer to Figs. D and E).
Note: do not use stranded wires, only solid wires or
stranded wires with ferrules.
3. Remove the battery transit tab
As soon as the battery transit tab is removed, the controller
starts to operate (also refer to Fig. F).
4. Configuration
4.1 Accessing the heating engineer level
The heating engineer level will be enabled by pressing
simultaneously the warmer and colder buttons and by
rolling the roller selector away from the display and then
toward the display (also refer to Fig. H).
4.2 Functions
4.2.1 Calibrating the temperature sensor
After activating the heating engineer level, the CAL symbol
will flash. When pressing the roller selector, the room
temperature currently measured flashes and can now be
recalibrated by a maximum of ± 2 °C by rolling either
toward the display or away from it. To store the re-
calibration, press the roller selector (also refer to Fig.
).
4.2.2 Setpoint limitation
There are 2 setting choices available:
or
On the heating engineer level, change from the flashing
CAL symbol to the setpoint limitation symbol by rolling
toward the display.
Press to accept. 5...29 °C will flash (factory setting). Press
to accept or continue rolling.
Setting 16...29 °C will flash.
Press to accept (also refer to Fig.
).
4.2.3 Control mode
On the heating engineer level, change from the flashing
CAL symbol to the symbols of the various control modes
by rolling away from the display (also refer to Fig.
).
Press to accept.
(factory setting) will flash. Press
to accept (Fig. 3) or continue rolling toward the display to
select one of the following control modes:
, PID 6, PID 12 or . Press to accept the
required control mode.
A brief description of the control modes is given below
(also refer to Fig.
).
Self-learning, adaptive control:
Suited for all standard applications (factory
setting).
PID 12 Normal controlled systems:
For locations with normal temperature variations.
PID 6 Fast controlled systems:
For locations with significant temperature
variations.
Difficult controlled systems:
Proper 2-position controller with a switching
differential of 0.5 °C.
4.2.4 Frost protection mode
Use operating mode selector to select symbol (also
refer to Fig.
).
If the standard value of 5 °C need to be changed, the frost
protection setpoint
must be changed via temperature
menu T (refer to the Operating Instructions).
5. Replacing the controller
Proceed according to Fig. G.
6. Functional check
a) Check the display. If there is no display, check the
correct fitting and function of the batteries.
b) Comfort mode
c) Select temperature menu T and adjust the temperature
setpoint
to 29 °C (refer to the Operating
Instructions)
d) The relay must be energized and thus the actuating
device activated within one minute. Flame symbol
will appear on the display. If that is not the case:
Check actuating device and wiring
The room temperature is possibly above 29 °C
e) Reset the setpoint temperature
to the initial value
(standard value 19 °C or individual setting)
f) Select the required operating mode
7. Reset
User-defined data:
Press the button behind the pin opening for at least one
second: this resets the user-specific settings to their
default values (the heating engineer settings will not be
changed). The clock starts at 12:00. During the reset time,
all sections of the display light up, enabling them to be
checked.
All user-defined data plus the heating engineer
settings:
Press the button behind the pin opening together with the
warmer and colder buttons for at least one second.
After this reset, the factory settings will be reloaded (also
refer to section “Factory settings“ in the operating
instructions).
4


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-rev12

Reset search

  • I had a battery symbol appear so I changed batteries. Now the display shows every symbol there is and no matter which button I press - nothing happens. I tried the reset button and nothing happened. Help please Submitted on 5-11-2021 at 23:09

    Reply Report abuse
  • I had a battery symbol appear so I changed batteries. Now the display shows every symbol there is and no matter which button I press - nothing happens. I tried the reset button and nothing happened. Help please. Submitted on 19-10-2021 at 10:54

    Reply Report abuse
  • My heating has been off for 5 months. No display on the thermostat so replaced the batteries and reset it. Still no display at all. Help?? Submitted on 31-3-2017 at 00:36

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens REV12 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens REV12 in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Swedish, Spanish as an attachment in your email.

The manual is 0,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens REV12

Siemens REV12 User Manual - English - 3 pages

Siemens REV12 User Manual - German - 2 pages

Siemens REV12 User Manual - Dutch - 10 pages

Siemens REV12 User Manual - Dutch - 2 pages

Siemens REV12 User Manual - French - 2 pages

Siemens REV12 User Manual - Turkish - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info