Setting the programmable timers
The RDG100T
provides 8 programmable timers A1…A8 each of which can be assigned to one or several
days. To set an auto timer, proceed as follows:
1. Press the program mode button twice to select auto timer setting
.
2. Turn the rotary knob to the desired timer A1…A8 that you wish to set and press button (OK).
3. Turn the rotary knob to set the Comfort mode start time and confirm by pressing button (OK)
4. Turn the rotary knob to set the Comfort end time
or Economy start time and confirm by pressing
button (OK).
5. Weekday
, and blink. Press button (OK) to select or
(Esc) to deselect each day and
advance to the next day.
6.
After the 7th day is set, all selected weekdays blink. Confirm setting for actual timer by pressing
button
(OK) and advance to the next timer. To set the next timer, repeat steps 3 through 6, or
press (Esc) to leave the setting mode.
Notes:
- To save your settings, remember to press OK in step 6 above before pressing Esc to leave the setting mode.
- The timer function can be disabled by setting P02 = 3 or P02 = 4 (only RDG160T)
Viewing the settings
1. Press the program mode button twice to select auto timer setting .
2. Turn the rotary knob to review the 8 auto timers.
3. Press button
(Esc) to return to normal operation.
Temporary timer for extended presence or absence
The Comfort and Economy modes can be temporarily extended from 0.5 to 9.5 hours using
the
temporary timer.
1. To set the temporary timer, press and hold the operating mode button for maximum 3 seconds.
While holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob clockwise to extend Comfort mode.
Display:
0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display: 0....-9:30
After the temporary timer has elapsed, the thermostat will resume operation in Auto Timer mode.
Reloading the default timer settings
1. Press the program mode button twice to select auto timer setting .
2. Press button
(OK) to enter the timer setting mode.
3. Press the program mode button for at least 3 seconds; then “rES” is displayed.
4. Press button
(OK) to confirm reloading the default timer settings, or
(Esc) to leave without
change.
Default
settings
Weekdays Time of day when thermostat is in Comfort mode
Mon(1)- Fri(5) 06:30 08:30 (A1) 17:30 – 22:30 (A2)
Sat (6) 08:00-23:00 (A3)
Sun (7) 08:00-22:30(A4)
For the remaining time, the thermostat is in Economy mode.
Timers A5 - A8 are free with no default settings.
Button lock
To lock or unlock the buttons manually, press and hold
the fan mode button for 3
seconds. The buttons are locked or unlocked in this manner if P14 is set to 2
If P14 is set to 1, the thermostat automatically locks the button 10 seconds
after the
last adjustment
Control parameters
If you want to change control parameters, proceed as follows:
1. Press left and right buttons simultaneously for at least 4 seconds.
2. Release them and, within 2 seconds, press the right button again until “P01” is displayed.
3. Select the required parameter by turning the rotary knob.
4. Press button (OK). The current value of the selected parameter starts blinking and
can be changed
by turning the rotary knob.
5. Press button
(OK) to confirm the adjusted value, or (Esc) to cancel the change.
If you wish to adjust additional parameters, repeat steps 3 through 5, or press
(Esc) to leave the
parameter setting mode.
No.
Parameter name Default value
Setting range Adj.
P01
Control sequence 2-pipe / 2-stage:
1 = cooling only
4-pipe:
4 = H and C
0 = heating only
1 = cooling only
2 = H/C changeover, manually
3 = H/C changeover, auto
4 = heating and cooling
P02 Mode selection via operating mode button 1
RDG100T: 1, 2
RDG160T: 1…4
1 = Auto / Comfort /
Protection mode
2 = Auto / Comfort / Economy /
Protection mode
3 = Comfort / Protection mode
4 = Comfort / Economy /
Protection mode
P03 Mode selection via fan mode button 0 0 = Auto / Manually
1 = Manually
2 = Auto / Manually /
Protection mode
P04 Selection of °C or °F 0 0 = °C
1 = °F
P05 Sensor calibration 0.0 K – 3 ... 3 K
P06 Standard temperature display 0 0 = Room temperature
1 = Setpoint
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort mode 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort mode 35 °C 5 ... 40 °C
P11 Setpoint for heating in Economy mode
(WheatEco)
15 °C OFF, 5 °C…WcoolEco
P12 Setpoint for cooling in Economy mode
(WcoolEco)
30 °C OFF, WheatEco…40 °C
P13 Electric heater in cooling mode ON OFF = Disabled
ON = Enabled
P14 Button lock 0 0 = Disabled
1 = Automatically
2 = Manually
P15 Fan speed in dead zone
(Comfort mode)
0 0 = Disabled
1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)
The control parameters displayed depend on the DIP switch settings made
Siemens Switzerland Ltd
Subject to change
B3181.5en
18.09.2013
2


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG160T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG160T in the language / languages: English as an attachment in your email.

The manual is 0,45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG160T

Siemens RDG160T User Manual - German - 2 pages

Siemens RDG160T User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info