Siemens RDG100…, RDG110…, RDG140..., RDG160… Basisdokumentation CE1P3076.de
Building Technologies Funktionen 19 Jun 2009
SDH/SDC [K] 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 >4.
5
XpH
Fan
/XpC
Fan
[K] 2 3 4 5 6 7 8 9 10
Der Thermostat kann einen 1- oder 3-stufigen Ventilator ansteuern (wählbar über
Parameter P53). Ein 1-stufiger Ventilator wird an Klemme Q1 angeschlossen, ein
3-stufiger an Klemmen Q1, Q2 und Q3.
RDG160 hat einen DC 0…10 V-Ausgang für ECM- (electronically commutated)
Ventilatormotoren. Die Schaltpunkte können über die Parameter P55…P57
eingestellt werden.
w Raumtemperatur-Sollwert
Q Ventilatordrehzahl
Y
H
Steuerbefehl “Heizen”
Y
C
Steuerbefehl “Kühlen”
XpH Proportionalband “Heizen”
XpC Proportionalband “Kühlen”
X
dz
Totzone
S
Fan
Schaltpunkt Ventilator
(P57)
S
Fmin
ECM-Ventilator min.
Leistung (P56)
w
XpH
Y
C
[%]
Q [%]
100
Y
H
[%]
0
0
XpC
100
100
x
dz
3181D109
S
Fan
S
Fan
S
Fmin
S
Fmax
S
Fmax
ECM-Ventilator max.
Leistung (P55)
Das Diagramm zeigt nur den Proportionalanteil der PI-Regelung.
Ventilatorstufe 1 = S
Fmin
Ventilatorstufe 2 = in der Mitte zwischen S
Fmin
und S
Fmax
Ventilatorstufe 3 = S
Fmax
w
Y
C
[%]
Q [%]
100
Y
H
[%]
0
0
100
100
3181D110
S
Fan
S
Fan
S
Fmin
S
Fmax
Fan III
Fan II
Fan I
=
=
Hinweis: Die Steuerbefehle
"Heizen" und "Kühlen"
warden von der manuellen
Ventilatorstufen-Wahl nicht
beeinflusst.
Der Ventilatorbetrieb kann eingeschränkt werden, indem er nur bei Kühlen oder nur
bei Heizen aktiv ist, oder er kann über Parameter P52 “Ventilatorbetrieb” gänzlich
gesperrt werden.
Ist der Ventilatorbetrieb gesperrt, verschwindet das Ventilatorsymbol vom Display
und das Drücken der Ventilatortaste hat keine Auswirkung.
Diese Funktion ermöglicht es, den Thermostaten für universelle Anwendungen wie
Kühldecken / Deckenheizungen und Heizkörper etc. einzusetzen (siehe Kapitel
4.7.9 und folgende).
Im
Automatikbetrieb ist eine Verweilzeit von 2 Minuten aktiv (Werkeinstellung). Der
Ventilator läuft dabei auf jeder Stufe mindestens 2 Minuten bevor er zur nächsten
wechselt. Diese minimale Einschaltdauer kann über Parameter P59 zwischen 1
und 5 Minuten eingestellt werden.
Tabelle für
2-Punkt-Regelung
1- / 3-stufiger Ventilator
Steuersequenz
für stetigen Ventilator
(ECM-Ventilator)
Hinweis:
Manueller Betrieb
(ECM-Ventilator)
Ventilatorbetrieb nach
Heiz- / Kühlbetrieb,
oder gesperrt
Minimale Einschalt-
dauer Ventilator
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG160 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG160 in the language / languages: German as an attachment in your email.

The manual is 3,17 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG160

Siemens RDG160 User Manual - English - 60 pages

Siemens RDG160 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info