Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Functions 19 Jun 2009
The changeover sensor ensures changeover from heating to cooling mode based
on the acquired water temperature. We recommend activating the purge function
(parameter P50) with 2-port valves. This function ensures correct acquisition of the
medium temperature even if the 2-port valve is closed for an extended period of
time. The valve is then opened for 1 to 5 minutes (adjustable) at 2-hour intervals
during off hours.
The purge function (parameter P50) must be disabled if the thermostat is used in
compressor-based applications.
In very warm and humid climates, the fan can be run periodically or continuously at
a low fan speed (e.g. in empty apartments or shops) in Energy Saving mode by
setting parameter P61, in order to avoid damage from moisture due to lack of air
circulation. See also section 4.9 “Fan control”, under “Fan kick function”.
Limit the on/of
f switching cycle to protect the compressor and reduce wear and
tear. The minimum output on-time and off-time for 2-position control output can be
adjusted from 1 to 20 minutes via parameters P48 and P49.
The factory setting is 1 minute.
Readjusting the setpoint or heating / cooling mode changeover immediately results
in calculation of the output status; output Y11/Y21 may not hold the minimum 1-
minute on/off time.
If parameter P48 or P49 is set to above 1 minute, the minimum on/off time for the
control output is maintained as set, even if the setpoint or changeover mode is
readjusted.
This function is only available for on/off control with RDG100, RDG100T and
RDG110.
All heating sequences can also be used for floor heating.
You can use fan coil heating / cooling sequences for floor heating or cooling by
disabling the fan via parameter P52.
The temperature should be limited for 2 reasons: comfort and protection of the
floor.
The floor temperature sensor, connected to multifunctional input X1 or X2, acquires
the floor temperature. If the temperature exceeds the parameterized limit (parame-
ter P51), the heating valve is fully closed until the floor temperature drops to a level
2 K below the parameterized limit.
This function is factory-set to OFF (disabled).
Input X1 or X2 must be commissioned accordingly (P38 or P40 = 1).
See section 4.10 “Multifunctional input”.
Living roo
ms:
Up to 26 °C for long-term presence, up to 28 °C for short-time presence.
Bath rooms:
Up to 28 °C for long-term presence, up to 30 °C for short-time presence.
Purge function
Caution
Avoid damage from
moisture
Minimum output
on-time / off-time
Floor heating /
Floor cooling
Floor temperature
limitation function
Recommended values
for P51:
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG160 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG160 in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG160

Siemens RDG160 User Manual - German - 64 pages

Siemens RDG160 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info