Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Functions 19 Jun 2009
4.9 Fan control
Different fan output signals are available depending on the thermostat type:
Control output
Product no.
On/off
1- / 3-speed fan
Modulating fan
DC 0…10 V
RDG100, RDG100T Q1,Q2,Q3 (3)
RDG110 Q1,Q2,Q3 (3)
RDG140 Q1,Q2,Q3 (3)
RDG160 Y50 (1)
( ) Number of outputs
The fan operates in automatic mode or at the selected speed with manual mode.
In automatic mode, the fan speed depends on the setpoint and the current room
temperature. When the room temperature reaches the setpoint, the control valve
closes and the fan switches off or stays at fan speed 1 (parameter P60; factory
setting: 0 = fan speed 1 in dead zone).
The individual switching points for ON of each fan stage can be adjusted via control
parameters P55…P57. The fan speed switch off point is 20% below the switch on
point. The diagrams below show fan speed control for modulating PI control.
w Room temperature setpoint
Q Fan speed
Y
H
Control demand “Heating”
Y
C
Control demand “Cooling”
XpH Proportional band “Heating”
XpC Proportional band “Cooling”
X
dz
Dead zone
w
XpH
Y
C
[%]
Q
Q3
Q2
Q1
Y
H
[%]
0
0
XpC
100
100
x
dz
The diagram only shows the PI controller’s proportional part.
On applications with 2-position control:
1) The switching point for low fan speed (Q1) is synchronized to the heating /
cooling output. Parameter “Switching point fan speed low” P57 is not relevant.
2) The maximum switching range of the fan (XpH
Fan
/ XpC
Fan
) is defined by the
switching differential (SDH/SDC) via a look-up table.
T[°C] Room temperature
w Room temperature setpoint
Q Fan speed
Y Control command “Valve”
SDH Switching differential “Heating”
SDC Switching differential “Cooling”
X
dz
Dead zone
XpH
Fan
Switching range for fan “Heating”
Cool
T[°C]
w
XpH
Fan
Q
Q3
Q2
Q1
T[°C]
Y
1
0
w
XpC
Fan
x
dz
SDC
SDH
XpC
Fan
Switching range for fan “Cooling”
SDH/SDC [K] 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 >4.5
XpH
Fan
/XpC
Fan
[K] 2 3 4 5 6 7 8 9 10
Overview of fan
outputs
3-speed fan control
with modulating
heating / cooling
control
Note:
3-speed fan control
with on/off heating /
cooling control
Look-up table with
on/off control
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG110 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG110 in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG110

Siemens RDG110 User Manual - German - 64 pages

Siemens RDG110 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info