Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
P52 Fan operation 1 0 = disabled
1 = enabled
2 = heating only
3 = cooling only

P53 Fan speed 3-speed 1 = 1-speed
2 = 3-speed

P54 Fan overrun time
(only when electrical heater is used)
60 s 0...360 s

P55 Switching point fan speed high 100% 80..100%

P55 ECM fan max. output ECM: 80% ECM: fan min…100%

P56 Switching point fan speed medium 65% 30...75%

P56 ECM fan min. output ECM: 30% ECM: 0%...fan max.

P57 Switching point fan speed low 10% 1...15%

P57 ECM: Switching point fan ECM:10% ECM: 0..100%

P58 Fan start booster ON ON: Enabled
OFF: Disabled

P59 Fan min. on time 2 min. 1...6 min

P60 Fan kick interval in Comfort mode
(time until next kick)
0 0…89 min, OFF (90 min.)

P61 Fan kick interval in E-saving mode
(time until next kick)
OFF 0359 min, OFF (360 min. )

P62 Clean filter reminder running time Off (0) OFF, 100…9900 hours

P65 Protection heating setpoint 8 °C OFF, 5…W Cool Prot;
(W Cool Prot = 40 °C max.)

P66 Protection cooling setpoint OFF OFF, W Heat Prot…40;
(W Heat Prot = 5 °C min.)

P67 Fan start delay in 2P control 0 s 0...180 s


P68 Extension Comfort period OFF OFF; 15...360 min

P69 Temporary setpoint Comfort mode
(see also Comfort setpoint P08)
OFF OFF = disabled
ON = enabled

P70 Infrared receiver ON OFF = disabled
ON = enabled

P71 Reload factory settings OFF OFF = disabled
ON = reload start

Parameter
Name Factory setting Range
RDG100
RDG100T
RDG110
RDG140
RDG160
Dia
g
nostics and test
d01 Application type Diagnostics 0 = (no application)
1 = 2-pipe
2 = 2-pipe with electrical heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2 stage heating or cooling
6 = 4-pipe with electrical heater

d02 X1 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
0…49 °C = cur temp value (for AI)
00 = H/C input closed
100 = H/C input open

d03 X2 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
0…49 °C = cur temp value (for AI)
00 = H/C input closed
100 = H/C input open

d04 D1 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
00 = H/C input closed
100 = H/C input open

d05 Test mode for checking
actuator direction Y1/Y2
(press left button to escape)
--- “---“ = no signal at outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing


d06 Test mode for checking
actuator direction Y3/Y4
(press left button to escape)
--- “---“ = no signal at outputs Y3 and Y4
OPE = output Y3 forced opening
CLO = output Y4 forced closing


Parameter available
Parameter not available
48


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG100T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG100T in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG100T

Siemens RDG100T User Manual - German - 64 pages

Siemens RDG100T User Manual - Dutch - 2 pages

Siemens RDG100T User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info