Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
The zones to be defined are as follows:
Geographical zone
(space zone)
(Apartment . Room . Subzone)
Apartment = ---, 1...126
Room = ---, 1...63
Subzone = fix 1
Zone in which an RDF KNX thermostat is physically located. Other
room-specific devices may also be located in this zone.
Information exchanged in this zone is related specifically to the device
like operating mode, setpoints, room temperature, etc.
The designations "Apartment", "Room" and "Subzone" do not need to
be taken literally. For example, Apartment can be used to refer to a
group of rooms, floor or section of a building. ”Room", however, really
does refer to a room.
Subzone is not used for HVAC devices. It is more relevant to other
disciplines, such as lighting. Subzone is fix at “1” and not visible.
The time switch information is expected from the same zone where
the thermostat is located (Residential).
If no time switch information is received from the same zone, the
thermostat will use the information received from the same apartment
but with room “1“ A.1.1 (Office).
Example:
Commercial building
In a commercial building, the
time switch information is sent by
the RMB795 central control unit.
The zones are divided in so
called “Room groups” (e.g. 1...4),
where each “Room group” can
have an individual schedule. A
room thermostat in the same
“Room group” need to have the
same Apartment Address.
Legend:
D = device address (P81)
G = geographical zone (P82, P83)
(Apartment.Room.Subzone)
D: 001
G: 3.1.1
Meeting room
Office 1
Server room
Office 2
2
4
D: 002
G: 2.1.1
D: 003
G: 2.2.1
D: 10
G: 1.1.1
Corridor
D: 12
G: 1.3.1
D: 11
G: 1.2.1
D: 004
G: 4.1.1
1
2
3
3171z20 1
Heat distribution zone
heating coil
Zone = ---, 1...31
Information related specifically to the hot water system in heating coils
is exchanged within this zone. The zone also includes a Synco device
to process the information (e.g. RMH7xx or RMU7xx with
changeover).
Refrigeration
distribution zone
cooling coil
Zone = ---, 1...31
Information related specifically to the chilled water system is
exchanged within this zone (e.g. cooling demand). This zone also
includes a Synco device to process the information (e.g. RMU7xx).
Outside temperature
zone
Zone = fixed to 31
RDF301...: SW < V3.7: fixed to 1
Outside temperature received in outside temperature zone 31 will be /
can be displayed on the room thermostat when commissioned
accordingly (parameter P07 = 2).
48


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF600KN at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF600KN in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF600KN

Siemens RDF600KN User Manual - German - 2 pages

Siemens RDF600KN User Manual - Dutch - 2 pages

Siemens RDF600KN User Manual - French - 2 pages

Siemens RDF600KN Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info