555885
34
Zoom out
Zoom in
Previous page
1/82
Next page
34 / 82
Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.6.5 4-pipe fan coil unit
On 4-pipe applications, the thermostat controls 2 valves in heating and cooling
mode, heating / cooling mode by manual selection, or heating and cooling mode
with changeover. Heating and cooling mode (P01 = 4) is factory-set.
The heating or cooling output can be released via operating mode button if
parameter P01 is set to Manual (P01 = 2).
If parameter P01 is set to changeover (P01 = 3), the heating and cooling output is
swapped according to the input state of the changeover sensor / switch / bus input
(see automatic heating and cooling changeover sensor in section 3.5). This mode
is used for th
e so-called “Main and secondary” application. This is a 4-pipe fan coil
unit system with different capacities of the 2 coils. The water circuit is changed to
optimize the energy exchange depending on the season (summer / winter):
– Winter: Large coil (V1) for heating, small coil (V2) for cooling
– Summer: Large coil (V1) for cooling, small coil (V2) for heating
T
B1
V2
V1
M1
3181D112
T
B2
Y
1
0
w
w
3181D117
T[°C]
YC
YH
Changeover
YH
YC
V1
V2
Changeover
Note:
This example shows
ON/OFF control;
for modulating con-
trol, connect the
appropriate output
terminals
The parameter for the heating and cooling changeover sensor (B2 in the above
diagram) must be set to 2 (X1 or X2, P38 or P40)
The thermostat assumes winter operation when B2 > P37 (factory setting 28 °C)
The thermostat assumes summer operation when B2 < P36 (factory setting 16 °C)
Heating and cooling
4-pipe application with
manual changeover
"Main and secondary"
application (4-pipe with
changeover)
Notes:
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301.50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301.50 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301.50

Siemens RDF301.50 User Manual - German - 2 pages

Siemens RDF301.50 User Manual - French - 2 pages

Siemens RDF301.50 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info