Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
The supported communication objects are different in LTE mode and S-mode
Changes via the local HMI or via tool have the same priority (last always wins)
Setting the Comfort basic setpoint will reset the runtime Comfort setpoint to the
basic setpoint
Central setpoint shift is used for summer / winter compensation in particular
Setpoint shift does not affect the setpoints stored in parameters P08, P11, P12,
P33
Local shift and central shift are added together
Applies only to Comfort and Economy setpoints; Protection setpoints are not
shifted centrally
The resulting (current) setpoint heating and cooling is limited by the Protection
setpoint; if Protection setpoint is OFF, then minimum 5 °C and maximum 40 °C
are used
The resulting setpoints for cooling and heating of the same operating mode have
a minimum distance of 0.5 K between them
The result of local and central shift, together with the room operating mode, is
used by the thermostat for temperature control (current setpoint)
General notes:
Notes on setpoint
adjustment (LTE mode
with Synco only)
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301.50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301.50 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301.50

Siemens RDF301.50 User Manual - German - 2 pages

Siemens RDF301.50 User Manual - French - 2 pages

Siemens RDF301.50 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info