Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.3 Room temperature setpoints
3.3.1 Description
The factory setting for the Comfort basic setpoint is 21 °C and can be changed in
the thermostat’s EEPROM via parameter P08 or via bus with communication object
" Comfort basic setpoint". The last intervention always wins.
The Comfort setpoint can be adjusted via the +/- buttons,
or via bus from a remote device like a touchpanel, operating unit, etc.
The last intervention always wins.
If the “Temporary setpoint” function is enabled via parameter P69, the Comfort
setpoint adjusted via the +/- buttons or via bus is set back to the Comfort basic
setpoint stored in P08 when the operating mode changes.
For comfort or energy saving purposes, the setpoint setting range can be limited to
minimum (P09) and maximum (P10).
If the minimum limit P09 is set lower than the maximum limit P10, both heating
and cooling are adjustable between these 2 limits
The customer adjusts the desired setpoint and the thermostat controls the room
temperature accordingly.
For 4-pipe applications *), the selected comfort setpoint is in the middle of the
dead zone (P33). The unit stops to energize the heating / cooling outputs as
soon as the room temperature reaches the dead zone.
Example
5°C 40°C25°C18°C
P10P09
Cooling setpoint adjustable 18…25 °C
Heating setpoint adjustable 18…25 °C
If the minimum limit P09 is set higher than the limit P10, then
– The setting range of cooling setpoint is from P09…40 °C in place of 5…40 °C
– The setting range of heating setpoint is from 5…P10 °C in place of 5…40 °C.
This allows the user to limit the maximum heating setpoint and the minimum
cooling setpoint. This concept helps to save energy costs.
For 4-pipe applications *):
– The thermostat runs with the setpoint of the active sequence:
In heating mode, the heating setpoint is active and adjustable via rotary knob.
In cooling mode, the cooling setpoint is active and adjustable via rotary knob.
– Switching from the heating setpoint to the cooling setpoint and vice-versa
occurs when the room temperature reaches the adjusted limitation (P09 or
P10) of the inactive sequence. E.g. the thermostat is in heating sequence
and runs with the heating setpoint. When the room temperature reaches P09,
the thermostat switches to cooling mode and runs with the cooling setpoint, as
long as the room temperature does not drop below P10.
Example
5°C 40°C25°C21°C
P09P10
Cooling setpoint adjustable 25…40 °C
Heating setpoint adjustable 5…21 °C
For heating and cooling applications (e.g. 4-pipe):
P09 is the setpoint for cooling and P10 the setpoint for heating
– The setpoint can not be adjusted via the rotary knob
Comfort mode
Temporary setpoint
Setpoint limitation
P09 < P10
(comfort concept)
P09 P10
(energy saving concept)
*) Note: RDF301...
for 4-pipe with P09 P10
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301.50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301.50 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301.50

Siemens RDF301.50 User Manual - German - 2 pages

Siemens RDF301.50 User Manual - French - 2 pages

Siemens RDF301.50 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info