3.2.1 Different ways to influence the operating mode
The operating mode can be influenced by different interventions.
The source of the effective room operating mode state can be monitored using the
"Cause" diagnostic data point in the ACS tool, operator unit RMZ792 or web server
OZW772 / 775.
Source Description Value of DP "Cause"
Operating mode is not Auto Timer
No time schedule via bus
Room operating mode selector
(preselection)
Temporary Comfort extension is active
“Timer” function
Local operation
via operating
mode button
Operating mode switchover contact
Room operating mode contact
"Window state" sent via bus
Room operating mode contact
Bus command
KNX
R
Room op. mode
Time schedule available via bus
local operating mode is set to Auto Timer
Time schedule sends Protection mode via bus
operating mode cannot be changed locally
Time switch
The following table shows the priorities of different interventions.
A lower number means a higher priority.
Priority Description Remark
Commissioning In parameter setting mode (highest priority), you can always
command an operating mode independent of all other settings or
intervention via bus and local input.
Protection mode via bus
from time schedule
Protection mode, sent by a time schedule, has priority 2.
It cannot be overridden by the user nor by an operating mode
switchover contact.
Operating mode
switchover contact
If the contact is closed, the operating mode changes to Economy.
This overrides the operating mode on the thermostat.
"Window state" via bus
"Window state" sent via bus has the same effect as the operating
mode switchover contact.
Note: Only one input source must be used, either local input
X1/X2 or KNX bus.
Operating mode button The user can switch the operating mode using the operating
mode button.
Operating mode via bus The operating mode can be changed via bus
Temporary extended
Comfort mode via
operating mode button
The operating mode can be temporarily set from Economy to
Comfort by pressing the operating mode button, if...
– Economy was sent via bus
– extended Comfort period >0 (parameter P68)
The last intervention wins, either locally or via bus
Time schedule via bus
The operating mode sent via bus can be overridden by all other
interventions. Exception: Protection mode has priority 2.
Source for change of
operating mode
ACS
Priority of operating
mode interventions
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301.50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301.50 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301.50

Siemens RDF301.50 User Manual - German - 2 pages

Siemens RDF301.50 User Manual - French - 2 pages

Siemens RDF301.50 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info